ATEN-PE-CFG-STR :: bankMinCurMT

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsATEN-PE-CFG-STRbankMinCurMT

bankMinCurMT

Module: ATEN-PE-CFG-STR

OID (symbolic): ATEN-PE-CFG-STR::bankMinCurMT

OID (numeric): 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Display or set the outlet minimum electric current measurment threshold. Example: range 0.0 ~16.0 rerpresnts 0~160 NOTICE: Minimum threshold should be smaller than maximum threshold. Empty value: -3000. If the device does not support this OID, it returns value -2000000.

What is bankMinCurMT?

This read-write integer sets the minimum current threshold (in tenths of amps) for monitoring bank current. When actual bank current falls below this value, an alert triggers. Setting it to 100 means an alert fires if bank current drops below 10.0 amps.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3
snmpwalk -v2c -c public <target> ATEN-PE-CFG-STR::bankMinCurMT

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3.1
snmpget -v2c -c public <target> ATEN-PE-CFG-STR::bankMinCurMT.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3.1 i <value>

Start monitoring ATEN PE-series intelligent PDUs with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ATEN-PE-CFG-STR::bankMinCurMT OID value, configure state conditions and alerts, and monitor any ATEN PE-series intelligent PDUs from a single console.

OID Breakdown

Upper-level ancestors (15 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.21317atenATEN-PE-CFG
1.3.6.1.4.1.21317.1atenProductsATEN-PE-CFG
1.3.6.1.4.1.21317.1.3overipATEN-PE-CFG
1.3.6.1.4.1.21317.1.3.2poweroveripATEN-PE-CFG
1.3.6.1.4.1.21317.1.3.2.2peATEN-PE-CFG
1.3.6.1.4.1.21317.1.3.2.2.2controlATEN-PE-CFG
1.3.6.1.4.1.21317.1.3.2.2.2.3bankATEN-PE-CFG
1.3.6.1.4.1.21317.1.3.2.2.2.3.3bankConfigTableATEN-PE-CFG
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1bankConfigEntryATEN-PE-CFG
Numeric OIDNameModule
1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3bankMinCurMTATEN-PE-CFG-STR