All MIBs › HUAWEI-SITE-MONITOR-MIB
Organization: Huawei Technologies Co.,Ltd.
Last Updated: 2011-03-04
Description: HUAWEI-SITE-MONITOR-MIB module
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is HUAWEI-SITE-MONITOR-MIB?
HUAWEI-SITE-MONITOR-MIB is a Huawei Technologies proprietary MIB providing multi-site load/backup and patch-management NMS interfaces for centrally managing distributed sites. Its objects cover site ID/name/admin-address/description, network identifier, site IP/netmask/gateway and default-gateway work status, device/alarm trap ordinal numbers, alarm quantity, a site-alarm table (index, text, level, signature description, row status), and a monitoring-group table (ID, name, quantity) with a per-monitor table. As a configuration/status MIB it lets an administrator confirm a remote site's gateway reachability and review active alarms across a multi-site Huawei deployment. It is deployed on Huawei Technologies multi-site management platforms. Engineers can download the HUAWEI-SITE-MONITOR-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in HUAWEI-SITE-MONITOR-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Huawei Technologies multi-site management platforms
Monitoring Examples
An administrator checks hwSiteDGWorkStatus and hwSiteAlarmTable to confirm gateway reachability and active alarms at a remote site in a Huawei multi-site deployment.
What Can Be Monitored
- remote-site gateway reachability and alarm status
This MIB depends on
Related MIBs
Imported Objects
From HUAWEI-MIB
| huaweiUtility | OBJECT-IDENTITY |
From SNMPv2-CONF
| NOTIFICATION-GROUP | |
| OBJECT-GROUP |
From SNMPv2-SMI
| Integer32 | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| Unsigned32 |
From SNMPv2-TC
| TEXTUAL-CONVENTION |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| hwSiteMonitorMIB | 1.3.6.1.4.1.2011.6.164 | Site Monitor MIB defines MIB objects which provides load and backup management, patch management NMS interfaces. The current version is V1.01 | ||
| hwSiteMonitorMIBObjects | 1.3.6.1.4.1.2011.6.164.1 | |||
| hwSiteInfo | 1.3.6.1.4.1.2011.6.164.1.1 | |||
| hwSiteSummary | 1.3.6.1.4.1.2011.6.164.1.1.1 | |||
| U32 hwSiteId | 1.3.6.1.4.1.2011.6.164.1.1.1.1 | Unsigned32 | read-only | Site ID, default value: 000,000. Naming rule of the site device ID (six digits): The first three digits indicate the device name and the last three digits indicate the serial number (SN) of the device. If the last three digits are 000, it indicates a virtual device. |
| OCT hwSiteName | 1.3.6.1.4.1.2011.6.164.1.1.1.2 | OCTET STRING | read-write | Site name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English. |
| U32 hwSiteAdminAddr | 1.3.6.1.4.1.2011.6.164.1.1.1.3 | Unsigned32 | read-write | Site administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535. |
| OCT hwSiteDescription | 1.3.6.1.4.1.2011.6.164.1.1.1.4 | OCTET STRING | read-write | Site description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure. Otherwise, the configured character can not be any other languages except English. |
| OCT hwNetIdentifier | 1.3.6.1.4.1.2011.6.164.1.1.1.5 | OCTET STRING | read-write | NE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network. Otherwise, the configured character can not be any other languages except English. |
| OCT hwSiteIp | 1.3.6.1.4.1.2011.6.164.1.1.1.6 | OCTET STRING | read-only | Site IP address, default value is 192.168.0.10. Users need to configure the site IP address. |
| OCT hwSiteNetmask | 1.3.6.1.4.1.2011.6.164.1.1.1.7 | OCTET STRING | read-only | Site netmask, default value is 255.255.0.0. Users need to configure the site netmask. |
| OCT hwSiteGateway | 1.3.6.1.4.1.2011.6.164.1.1.1.8 | OCTET STRING | read-only | Site gateway, default value: 192.168.0.1. Users need to configure the site gateway. |
| INT hwSiteDGWorkStatus | 1.3.6.1.4.1.2011.6.164.1.1.1.9 | INTEGER | read-only | State of the diesel working state. It is an enumeration type: If the enumeration value is 1, it indicates that the diesel is in the idle state; If the enumeration value is 2, it indicates that the diesel is in the working state; If the enumeration value is 255, it indicates diesel operation status unknown. |
| hwSiteAlarms | 1.3.6.1.4.1.2011.6.164.1.1.2 | |||
| U32 hwDeviceTrapOrdinalNumber | 1.3.6.1.4.1.2011.6.164.1.1.2.1 | Unsigned32 | read-write | Site device event trap serial number (SN) is the unique ID of the device event trap. It is used to resend and synchronize event traps. Its value range is 0 to 4294967296. When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967296. If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the event trap number required. So the monitor send the 50 event trap messages in maximum, after consequencial number required by NMS again. Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically. |
| U32 hwAlarmTrapOrdinalNumber | 1.3.6.1.4.1.2011.6.164.1.1.2.2 | Unsigned32 | read-write | Site alarm serial number (SN) is the unique ID of the alarm Trap. It is used to resend and synchronize alarms. Its value range is 0 to 4294967296. When the value exceeds the maximum value, the system automatically clears the value and numbers the alarm from 0 to 4294967296. If the network management system (NMS) recieve the alarm number is not consequential, in such case that it notifies the SNMP agent the alarm number required. So the monitor send the 50 alarm messages in maximum, after consequencial number required by NMS again. Specially, if NMS set the value to 0, the agent would clear the alarm queue automatically. |
| U32 hwAlarmQuantity | 1.3.6.1.4.1.2011.6.164.1.1.2.3 | Unsigned32 | read-only | Alarm number in site alarm list which are support. It is used for alarm list management by NMS, and value range is 0 to 65535. |
| hwSiteAlarmTable | 1.3.6.1.4.1.2011.6.164.1.1.2.100 | not-accessible | Site alarms table. The table containing alarm information on the site management. Use this table to get site alarm name, alarm level, alarm signal description, and alarm port description, which can be used as VB of alarm traps. This table's index is hwAlarmIndex, clone site alarms table. | |
| hwSiteAlarmEntry | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1 | not-accessible | Site alarms table entry. | |
| I32 hwAlarmIndex | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.1 | Integer32 | read-only | Site alarm table index. It is the unique ID of the site alarm. |
| OCT hwAlarmText | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.2 | OCTET STRING | read-only | Alarm name. It is of the character string type, and used to specify the content of a specific alarm. |
| INT hwAlarmLevel | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.3 | INTEGER | read-write | Alarm level, which users can configure the alarm severity, is an enumeration type: If the enumeration value is 1, it indicates a critical alarm; If the enumeration value is 2, it indicates a major alarm; If the enumeration value is 3, it indicates a minor alarm; If the enumeration value is 4, it indicates a warning; If the enumeration value is 5, it indicates the alarm is cleared. |
| OCT hwAlarmSigDesc | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.4 | OCTET STRING | read-write | Alarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm. Otherwise, the configured character can not be any other languages except English. |
| ROW hwAlarmRowStatus | 1.3.6.1.4.1.2011.6.164.1.1.2.100.1.100 | RowStatus | read-create | RowStatus of site alarms table. |
| hwSiteMonitors | 1.3.6.1.4.1.2011.6.164.1.2 | |||
| hwMonitorsGroup | 1.3.6.1.4.1.2011.6.164.1.2.1 | |||
| U32 hwMonsGroupId | 1.3.6.1.4.1.2011.6.164.1.2.1.1 | Unsigned32 | read-only | Site monitor group ID, is the unique ID of the site monitors. |
| OCT hwMonsGroupName | 1.3.6.1.4.1.2011.6.164.1.2.1.2 | OCTET STRING | read-write | Site monitor group name is of the character string type, used to specify the monitor group. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| U32 hwMonsQuantity | 1.3.6.1.4.1.2011.6.164.1.2.1.3 | Unsigned32 | read-only | Total site intelligent monitors. |
| hwMonitor | 1.3.6.1.4.1.2011.6.164.1.2.2 | |||
| hwMonitorTable | 1.3.6.1.4.1.2011.6.164.1.2.2.1 | not-accessible | Site monitors table. Use this table to get site monitor equipment ID, site monitor equipment name, equipment software version, equipment PCB version, manufacturer, manufacture date, equipment serial No, equipment description, total runing time, and equipment controlled status, as well as to control monitor reset. This table's index is hwMonIndex, clone site monitors table. | |
| hwMonitorEntry | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1 | not-accessible | Site monitors table entry. | |
| I32 hwMonIndex | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.1 | Integer32 | read-only | Table index of the site monitors (hwSiteMonsTab) is restricted by the quantity of the site monitors (hwMonsQuantity). Value range: 1 to 100 |
| U32 hwMonEquipId | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.2 | Unsigned32 | read-only | Site monitor ID. Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwMonEquipName | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.3 | OCTET STRING | read-write | Monitor name. It is of the character string type, and users can set the name of the monitor. Otherwise, the configured character can not be any other languages except English. |
| OCT hwMonEquipDescription | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.4 | OCTET STRING | read-write | Monitor description. It is of the character string type. Users can set the description of the monitor. Otherwise, the configured character can not be any other languages except English. |
| OCT hwMonEquipSoftwareVersion | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.5 | OCTET STRING | read-only | Monitor software version. It is of the character string type. |
| OCT hwMonEquipPcbVersion | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.6 | OCTET STRING | read-only | Monitor printed circuit board (PCB) hardware version. It is of the character string type. |
| OCT hwMonEquipManufacturer | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.7 | OCTET STRING | read-only | Monitor manufacture. It is of the character string type, and is an inherent attribute of the device. |
| OCT hwMonEquipManuDate | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.8 | OCTET STRING | read-only | Monitor production date. It is of the character string type, and is an inherent attribute of the device. |
| OCT hwMonEquipSerialNo | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.9 | OCTET STRING | read-only | Production SN of the monitor. It is the electronic tag of the products. |
| U32 hwMonEquipOperTotalTime | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.10 | Unsigned32 | read-only | Total monitor runtime. The monitor counts the data in real time. The value is an integer (.0), and unit is hour (h). It is used for performance measurement and evaluation of the monitor. |
| INT hwSetMonEquipCtrlState | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.11 | INTEGER | read-write | Monitor control status. It is an enumeration type: If the enumeration value is 1, it indicates the background control; If the enumeration value is 2, it indicates the automatic control. In manual state, monitor works under background commands; while monitors runs well automatically in auto state. For details, see the corresponding user manual of the monitor. |
| INT hwCtrlMonEquipReset | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.12 | INTEGER | read-write | Warm-reset control of the monitor. It is an enumeration type: If the network management system (NMS) notifies the SNMP agent that this node is set to 1, it indicates that the reset of the monitor is not triggered; If the NMS notifies the SNMP agent that this node is set to 2, it indicates that the background starts the reset of the monitor. |
| INT hwMonitorOperStatus | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.99 | INTEGER | read-only | State of the site monitor module. It is an enumeration type: If the enumeration value is 1, it indicates that the site monitor module is in the normal state; If the enumeration value is 2, it indicates that the monitor module RS485 port communication failed; If the enumeration value is 3, it indicates that the monitor module net port communication failed; If the enumeration value is 4, it indicates that a fault occurs on the monitor module; If the enumeration value is 254, it indicates monitor module alarm resume; If the enumeration value is 255, it indicates monitor module operation status unknown. |
| ROW hwMonRowStatus | 1.3.6.1.4.1.2011.6.164.1.2.2.1.1.100 | RowStatus | read-create | RowStatus of site monitor. |
| hwSiteRectifiers | 1.3.6.1.4.1.2011.6.164.1.3 | |||
| hwRectsGroup | 1.3.6.1.4.1.2011.6.164.1.3.1 | |||
| U32 hwRectsGroupId | 1.3.6.1.4.1.2011.6.164.1.3.1.1 | Unsigned32 | read-only | Device group ID of the rectifier module. It is the unique ID of the rectifier module group, and its default value: 002,000. The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwRectsGroupName | 1.3.6.1.4.1.2011.6.164.1.3.1.2 | OCTET STRING | read-write | Name of the rectifier module group, character string type, is used to specify the rectifier module group. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| U32 hwRectsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.3.1.3 | Unsigned32 | read-only | Total current of the rectifier module group on the site. It indicates the real-time statistics of the rectifier module group on the site. unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwRectsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.3.1.4 | Unsigned32 | read-only | Total quantity of the rectifier modules. Value range: 0 to 256. |
| U32 hwRectsRatedVoltage | 1.3.6.1.4.1.2011.6.164.1.3.1.5 | Unsigned32 | read-only | Rated voltage of the rectifier module group. It is an inherent attribute. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal place (.1). |
| U32 hwModifyRectsOutputVoltage | 1.3.6.1.4.1.2011.6.164.1.3.1.6 | Unsigned32 | read-write | Voltage adjustment of the rectifier module, which users can configure it. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal space (.1). Based on the actual requirements, users can modify the output voltage of the rectifier module by modifying the value of the node. NOTES: Be cautious about changing the value of the node. |
| INT hwSetRectsRedundEnable | 1.3.6.1.4.1.2011.6.164.1.3.1.7 | INTEGER | read-write | Sleep function of the rectifier module group on the site. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it means to disable the sleep function of the rectifier module group; If the NMS notifies the SNMP agent that this node is set to 2, it means to enable the sleep function of the rectifier module group. If NMS get the node value is 3, it indicates that this function is not support, and in such case the value set to the agent is invalid. Default value: to disable the sleep function of the rectifier module group. For details, see the corresponding user manual of the monitor. |
| INT hwCtrlRectsAllOnOff | 1.3.6.1.4.1.2011.6.164.1.3.1.8 | INTEGER | read-write | Power-on or power-off of the rectifier module group (all the rectifier modules) on the site. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of all rectifier modules; If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of all the rectifier modules. |
| hwRectifier | 1.3.6.1.4.1.2011.6.164.1.3.2 | |||
| hwRectConfigTable | 1.3.6.1.4.1.2011.6.164.1.3.2.1 | not-accessible | Rectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and to control equipment on or off. This table's index is hwRectConfigIndex, clone Rectifier config information table. | |
| hwRectConfigEntry | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1 | not-accessible | Rectifier config table entry. | |
| I32 hwRectConfigIndex | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.1 | Integer32 | read-only | Index of the device configuration list for the rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectTotleQuantity). |
| U32 hwRectEquipId | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.2 | Unsigned32 | read-only | Rectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN. |
| OCT hwRectEquipName | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.3 | OCTET STRING | read-write | Device name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| INT hwRectType | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.4 | INTEGER | read-only | Specific type of the rectifier module. It is an enumeration type: If the enumeration value is 1, it indicates a 5A rectifier module; If the enumeration value is 2, it indicates a 15A rectifier module; If the enumeration value is 3, it indicates a 30A rectifier module; If the enumeration value is 4, it indicates a 50A rectifier module; If the enumeration value is 5, it indicates a 100A rectifier module. |
| OCT hwRectSoftwareVersion | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.5 | OCTET STRING | read-only | Software version of the rectifier module. It indicates the software version ID of the module. |
| OCT hwRectManufacturer | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.6 | OCTET STRING | read-only | Manufacture of the rectifier module. |
| OCT hwRectManuDate | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.7 | OCTET STRING | read-only | Manufacture date of rectifiers is of string type. |
| OCT hwRectSerialNo | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.8 | OCTET STRING | read-only | Rectifier module SN. It indicates the electronic tag of the product. |
| U32 hwRectRatedCurrent | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.9 | Unsigned32 | read-only | Rated voltage of the rectifier module, is an inherent attribute. Value range: 0 to 100, Unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwRectEfficency | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.10 | Unsigned32 | read-only | Efficiency of the rectifier module, is an inherent attribute. Value range: 80 to 100, Unit: %, and the value is accurate to one decimal place (.1). |
| INT hwRectInputAcType | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.11 | INTEGER | read-only | Input AC type of the rectifier module. It is an enumeration value: If the value of the node is 1, it indicates single-phase AC input; If the value of the node is 2, it indicates three-phase AC input. |
| INT hwCtrlRectOnOff | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.12 | INTEGER | read-write | Power-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on or power-off of the rectifier module: If the NMS notifies the SNMP agent that this node is set to 1, it indicates power-on of the rectifier module; If the NMS notifies the SNMP agent that this node is set to 2, it indicates power-off of the rectifier module. |
| ROW hwRectConfigRowStatus | 1.3.6.1.4.1.2011.6.164.1.3.2.1.1.100 | RowStatus | read-create | RowStatus of rectifier config table. |
| hwRectOperTable | 1.3.6.1.4.1.2011.6.164.1.3.2.2 | not-accessible | Rectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status. This table's index is hwRectRunIndex, clone rectifier runing information table. | |
| hwRectOperEntry | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1 | not-accessible | Rectifier runing table entry. | |
| I32 hwRectOperIndex | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.1 | Integer32 | read-only | Table index of the running rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modules (hwRectTotleQuantity). |
| U32 hwRectOutputCurrent | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.2 | Unsigned32 | read-only | Output current of the rectifier module. It is a real-time analog parameter. Value range: 0 to 200, Unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwRectOutputVoltage | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.3 | Unsigned32 | read-only | Output voltage of the rectifier module. It is a real-time analog parameter. Value range: 0 to 60, Unit: V, the value is accurate to one decimal place (.1). |
| U32 hwRectTotalOperTime | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.4 | Unsigned32 | read-only | Total runtime of the rectifier module. Value unit: minute (m), and the value is an integer (.0). |
| INT hwRectOperStatus | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.99 | INTEGER | read-only | State of the rectifier module. It is an enumeration type: If the enumeration value is 1, it indicates that the rectifier module is in the normal state; If the enumeration value is 2, it indicates that a fault occurs on the rectifier module; If the enumeration value is 3, it indicates the automatic protection of the rectifier module; If the enumeration value is 4, it indicates that communication of the rectifier module fails; If the enumeration value is 5, it indicates that the rectifier module is shut down; If the enumeration value is 6, it indicates that the rectifier module is invalid; If the enumeration value is 7, it indicates that this rectifier is not configured; If the enumeration value is 254, it indicates rectifier alarm resume; If the enumeration value is 255, it indicates rectifier operation status unknown. |
| ROW hwRectOperRowStatus | 1.3.6.1.4.1.2011.6.164.1.3.2.2.1.100 | RowStatus | read-create | RowStatus of rectifier runing table. |
| hwSiteBatterys | 1.3.6.1.4.1.2011.6.164.1.4 | |||
| hwBattsConfig | 1.3.6.1.4.1.2011.6.164.1.4.1 | |||
| U32 hwBattsGroupId | 1.3.6.1.4.1.2011.6.164.1.4.1.1 | Unsigned32 | read-only | Battery group ID. It is the unique ID of the battery group device. The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwBattsGroupName | 1.3.6.1.4.1.2011.6.164.1.4.1.2 | OCTET STRING | read-write | Device name of the battery group. It is of the character string type, which can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwBattsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.4.1.3 | Unsigned32 | read-write | Total quantity of battery strings, which value range: 0 to 100. |
| INT hwSetBattsHighTempAction | 1.3.6.1.4.1.2011.6.164.1.4.1.4 | INTEGER | read-write | Battery high-temperature protection mode. It is an enumeration value, and can be configured. If the enumeration value is 1, it indicates the power-off protection mode; If the enumeration value is 2, it indicates the protection mode of lowering the output voltage of the rectifier module. unknown(255) it is do nothing |
| U32 hwSetBattsHighTempVoltLimit | 1.3.6.1.4.1.2011.6.164.1.4.1.5 | Unsigned32 | read-write | Battery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be configured by users. If the low-voltage power-off protection mode (that is, the enumeration value is 1) is selected, the node is a low-voltage power-off node. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1). |
| I32 hwSetBattsHTDLimit | 1.3.6.1.4.1.2011.6.164.1.4.1.6 | Integer32 | read-write | Upper threshold of the battery high temperature disconnection(HTD), can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integer (.0). |
| INT hwSetBattsHTDEnable | 1.3.6.1.4.1.2011.6.164.1.4.1.7 | INTEGER | read-write | Battery high temperature disconnection enable. It is an enumeration type: If the enumeration value is 1, enable the operation of the battery disconnection in high temperature; If the enumeration value is 2, disable the operation of the battery disconnection in high temperature. The operation of the battery disconnection in high temperature is disabled by default. |
| U32 hwSetBattsFloatVoltage | 1.3.6.1.4.1.2011.6.164.1.4.1.8 | Unsigned32 | read-write | Float charge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1) |
| U32 hwSetBattsBoostVoltage | 1.3.6.1.4.1.2011.6.164.1.4.1.9 | Unsigned32 | read-write | Boostcharge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1). |
| U32 hwSetBattsCurrLimitCoefficient | 1.3.6.1.4.1.2011.6.164.1.4.1.10 | Unsigned32 | read-write | Current-limiting point coefficient of the batteries, can be configured by users. Value range: 0.05 to 0.25, unit: C10, and the value is accurate to two decimal places (.2). |
| U32 hwSetBattsCompFactor | 1.3.6.1.4.1.2011.6.164.1.4.1.11 | Unsigned32 | read-write | Temperature compensated coefficient of the batteries, can be configured by user. Value range: 0 to 500, unit: mv per centigrade, and the value is an integer (.0). |
| INT hwCtrlBattsBoostFloat | 1.3.6.1.4.1.2011.6.164.1.4.1.12 | INTEGER | read-write | Control batteries charge mode between boost and float. It is an enumeration value. Users actively control the conversion. If the NMS notifies the SNMP agent that this node is set to 1, it means to start the float charge mode of the batteries; If the NMS notifies the SNMP agent that this node is set to 2, it means to start the boost charge mode of the batteries. |
| hwBattsOperate | 1.3.6.1.4.1.2011.6.164.1.4.2 | |||
| I32 hwBattsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.4.2.1 | Integer32 | read-only | Total current of the battery group. It indicates the real-time statistics of the battery group on the site. Value range: -1000 to +1000, unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwBattsPreDischargeTime | 1.3.6.1.4.1.2011.6.164.1.4.2.2 | Unsigned32 | read-only | Battery group backup time. It indicates the real-time statistics of the battery group. Value range: 0 to 65536, Unit: minute (m), and the value is an integer (.0). |
| INT hwBattsChargeStatus | 1.3.6.1.4.1.2011.6.164.1.4.2.3 | INTEGER | read-only | Battery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type. If the enumeration value is 1, it indicates a battery group in the float charging state. If the enumeration value is 2, it indicates a battery group in the boost charging state. If the enumeration value is 3, it indicates a battery group in the discharging state. |
| INT hwBattsCurrLimitStatus | 1.3.6.1.4.1.2011.6.164.1.4.2.4 | INTEGER | read-only | Battery group current-limiting state, indicates the state information about the battery group. It is an enumeration value. If the enumeration value is 1, it indicates that the current of the battery group is not limited. If the enumeration value is 2, it indicates the current of the battery group is limited. |
| hwBattsTest | 1.3.6.1.4.1.2011.6.164.1.4.3 | |||
| U32 hwBattsTestRecordCount | 1.3.6.1.4.1.2011.6.164.1.4.3.1 | Unsigned32 | read-only | Battery test records number. |
| U32 hwSetBattsManuStdTestTime | 1.3.6.1.4.1.2011.6.164.1.4.3.2 | Unsigned32 | read-write | Battery standard test time, It can be configured by users, and its value is an integer (.0). Here, if battery manual test is standard mode, value range defines between 1 to 6000, unit: minutes(m) |
| U32 hwSetBattsManuStdTestEndVolt | 1.3.6.1.4.1.2011.6.164.1.4.3.3 | Unsigned32 | read-write | Voltage when the battery test is ended, can be configured by users. Unit: V/cell, and the value is accurate to two decimal place (.2). Here, if battery manual test is standard mode, value range defines between 1.7 to 2.2 |
| U32 hwSetBattsManuStdTestCellNum | 1.3.6.1.4.1.2011.6.164.1.4.3.4 | Unsigned32 | read-write | Battery cell number in each Group, which is used in the battery standard manual test, can be configured by users. Unit: psc or cell, value range defines between 1 to 50. and the value is accurate to one decimal place (.0). |
| U32 hwSetBattsManuShortTestTime | 1.3.6.1.4.1.2011.6.164.1.4.3.5 | Unsigned32 | read-write | Battery short test time, It can be configured by users, and its value is an integer (.0). If battery manual test is simple mode, value range defines between 1 to 240, unit: minutes(m) |
| U32 hwSetBattsManuShortTestEndVolt | 1.3.6.1.4.1.2011.6.164.1.4.3.6 | Unsigned32 | read-write | Voltage when the battery short test is ended, can be configured by users. Unit: V, and the value is accurate to one decimal place (.1). Here, if battery manual test is standard mode, value range defines between 40 to 54. |
| INT hwCtrlBattsTestStartStop | 1.3.6.1.4.1.2011.6.164.1.4.3.7 | INTEGER | read-write | Battery manualtest start and stop. It is an enumeration value. If the NMS notifies the SNMP agent that the node is set to 1, it means to start a standard manual test; If the NMS notifies the SNMP agent that the node is set to 2, it means to start a short manual test; If the NMS notifies the SNMP agent that the node is set to 3, it means to stop the battery test. Set the parameters, such as battery test time, and voltage when the battery test stops before the node controls the start of the battery test. If the parameters are not set this time, the system uses the configuration parameters by default; and if the battery test is started at the first time, the system uses the default value. Battery test can only start up in some conditions, so that the reason of Start of battery short test failed may be as follow: 1. Interval between this test and the latest AC outage or test is longer than the preset duration. 2. No major alarm is raised. 3. The number of healthy modules is greater than 0. 4. The number of battery strings is greater than 0. |
| hwBattsTestResultTable | 1.3.6.1.4.1.2011.6.164.1.4.3.100 | not-accessible | Battery test result record table. Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, average current, discharge AH value, test temperature and test terminated course. This table's index is hwBattsTestResultIndex, clone Battery test result record table. | |
| hwBattsTestResultEntry | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1 | not-accessible | Battery test result table entry. | |
| I32 hwBattsTestResultIndex | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.1 | Integer32 | read-only | Table index of the battery test results. Currently up to 10 times of the battery test results are saved by default. |
| INT hwBattsTestType | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.2 | INTEGER | read-only | Record test type of the battery test. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test; If the NMS notifies the SNMP agent that this node is set to 2, it indicates a simplified test; If the NMS notifies the SNMP agent that this node is set to 3, it indicates a timed test; If the NMS notifies the SNMP agent that this node is set to 4, it indicates a short test; If the NMS notifies the SNMP agent that this node is set to 255, it indicates a other test. |
| OCT hwBattsTestStartTime | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.3 | OCTET STRING | read-only | Test start time of the record in the battery test. It is of the character string type. |
| INT hwBattsTestResult | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.4 | INTEGER | read-only | Battery test result. It is an enumeration value. If the enumeration value of the node is 1, it indicates that the battery test has no result: If the enumeration value of the node is 2, it indicates that the battery is in the normal state: If the enumeration value of the node is 3, it indicates that the battery is in the minor abnormal state, If the enumeration value of the node is 4, it indicates that the battery is in the alarm state, If the enumeration value of the node is 255, it indicates that the battery state is unknown, |
| I32 hwBattsEfficiency | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.5 | Integer32 | read-only | Battery efficiency test. Value range: 0 to 100, Unit: %, and the value is an integer (.0). If the value is -1, it indicates that the test value is inefficient. |
| U32 hwBattsDischargeTime | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.6 | Unsigned32 | read-only | Discharge time of the battery test records. Value range: 0 to 100, unit: hour (h), and the value is accurate to two decimal places (.2). |
| U32 hwBattsDischargeEndVoltage | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.7 | Unsigned32 | read-only | Discharge termination voltage of the battery test. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1). |
| I32 hwBattsDischargeAvCurrent | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.8 | Integer32 | read-only | Average discharge current of the battery test. Value range: -10000 to 10000, unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwBattsDischargeAhValue | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.9 | Unsigned32 | read-only | Discharge ampere per hour the battery test. Value range: 0 to 5000, Unit: Ah, and the value is an integer (.0). |
| I32 hwBattsTestTemprature | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.10 | Integer32 | read-only | Battery temperature of the battery test termination. Value range: -50 to +100, Unit: centigrade (°„C), and the value is an integer (.0). If the value is -1024, it indicates that no battery temperature value sensor is detected. |
| INT hwBattsTestEndCourse | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.11 | INTEGER | read-only | Termination factors of the battery test. It is an enumeration value. If the enumeration value is 1, it indicates that the voltage value of the battery test reaches the set termination voltage; If the enumeration value is 2, it indicates that the voltage value of the battery test reaches the timing limit; If the enumeration value is 3, it indicates that an alarm related to the battery leads to the stop of the battery test; If the enumeration value is 4, it indicates that a battery test is stopped manually, If the enumeration value is 5, it indicates that battery fault alarm happened, If the enumeration value is 255, it indicates that battery test end for other courses. |
| ROW hwBattsTestResultRowStatus | 1.3.6.1.4.1.2011.6.164.1.4.3.100.1.100 | RowStatus | read-create | RowStatus of battery test table. |
| hwBattString | 1.3.6.1.4.1.2011.6.164.1.4.4 | |||
| hwBattStringConfigTable | 1.3.6.1.4.1.2011.6.164.1.4.4.1 | not-accessible | Battery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as well. This table's index is hwBattStringConfigIndex, clone battery string config table. | |
| hwBattStringConfigEntry | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1 | not-accessible | Battery string config table entry. | |
| I32 hwBattStringConfigIndex | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.1 | Integer32 | read-only | Device table index of the battery string, which value range: 1 to 100. |
| U32 hwBattStringEquipId | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.2 | Unsigned32 | read-only | Batteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three specify the device SN. |
| OCT hwBattStringEquipName | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.3 | OCTET STRING | read-write | Batteries device name, of the character string type, is used to specify the batteries. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| I32 hwSetBattsTempUpperLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.4 | Integer32 | read-write | Upper threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetBattsTempLowerLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.5 | Integer32 | read-write | Lower threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetBattsTempMeasureUpperLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.6 | Integer32 | read-write | Upper threshold of the battery temperature measurement, can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetBattsTempMeasureLowerLimit | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.7 | Integer32 | read-write | Lower threshold of the battery temperature measurement, can be configured by users. Value range: -50 to 0, Unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetBattStdCapacity | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.8 | Integer32 | read-write | Set battery standard capacity, is an inherent attribute of the device. Value range: 0 to 10000, unit: Ah, the value is an integer (.0). |
| OCT hwSetBattInstallTime | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.9 | OCTET STRING | read-write | Set battery install time, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| ROW hwBattStringConfigRowStatus | 1.3.6.1.4.1.2011.6.164.1.4.4.1.1.100 | RowStatus | read-create | RowStatus of battery string config table. |
| hwBattStringOperTable | 1.3.6.1.4.1.2011.6.164.1.4.4.2 | not-accessible | Battery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as well as battery temperature. This table's index is hwBattStringRunIndex, clone battery string runing table. | |
| hwBattStringOperEntry | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1 | not-accessible | Battery string runing table entry. | |
| I32 hwBattStringOperIndex | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.1 | Integer32 | read-only | Device table index of the battery string, which value range: 1 to 100. |
| I32 hwBattStringCurrent | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.2 | Integer32 | read-only | Batteries current. It is an analog parameter collected by the battery string in real time. Value range: -1000 to +1000, unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwBattStringRemainCapacityPercent | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.3 | Unsigned32 | read-only | Remaining capacity percentage of the battery string. Value range: 0 to 100, unit: %, and the value is accurate to one decimal place (.1). |
| U32 hwBattStringRemainCapacity | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.4 | Unsigned32 | read-only | Remaining capacity of the battery string. It is an analog parameter collected by the battery string in real time. Value range: 0 to 5000, unit: Ah, and the value is an integer (.0). |
| U32 hwBattStringActualCapacity | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.5 | Unsigned32 | read-only | Batteries actual capacity. It is an analog parameter collected by the battery string in real time.Value range: 0 to 5000, unit: Ah, the value is an integer (.0). |
| I32 hwBattStringTemprature | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.6 | Integer32 | read-only | Battery temperature. It is a battery parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.1). If the value is -99999, it indicates that battery temperature sensor is not configured. |
| INT hwBattStringOperStatus | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99 | INTEGER | read-only | State of the site battery string module. It is an enumeration type: If the enumeration value is 1, it indicates that the site battery string is in the normal state; If the enumeration value is 2, it indicates that the battery string is over upper alarm threshold of temperature; If the enumeration value is 3, it indicates that the battery string is under lower alarm threshold of temperature; If the enumeration value is 4, it indicates that battery string loop has disconnected; If the enumeration value is 5, it indicates that the current of batery is over upper charging threshold; If the enumeration value is 254, it indicates battery string alarm resume; If the enumeration value is 255, it indicates battery string operation status unknown. |
| ROW hwBattStringOperRowStatus | 1.3.6.1.4.1.2011.6.164.1.4.4.2.1.100 | RowStatus | read-create | RowStatus of battery string runing table. |
| hwSiteAcDistributions | 1.3.6.1.4.1.2011.6.164.1.5 | |||
| hwAcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.1.5.1 | |||
| U32 hwAcsGroupId | 1.3.6.1.4.1.2011.6.164.1.5.1.1 | Unsigned32 | read-only | AC group ID, is the unique ID of the AC group. The first three digits indicate the device type and the last three indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwAcsGroupName | 1.3.6.1.4.1.2011.6.164.1.5.1.2 | OCTET STRING | read-write | Device name of the AC group. It is of the character string type, and can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwAcsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.5.1.3 | Unsigned32 | read-only | Total current of the AC group. It indicates the real-time statistics of the AC group. Value range: 0 to 1000, unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwAcsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.5.1.4 | Unsigned32 | read-only | Total quantity of the site ACUs. Value range: 0 to 100. |
| U32 hwSetAcsUpperVoltLimit | 1.3.6.1.4.1.2011.6.164.1.5.1.5 | Unsigned32 | read-write | Upper threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0). |
| U32 hwSetAcsLowerVoltLimit | 1.3.6.1.4.1.2011.6.164.1.5.1.6 | Unsigned32 | read-write | Lower threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0). |
| hwAcDistribution | 1.3.6.1.4.1.2011.6.164.1.5.2 | |||
| hwAcInputTable | 1.3.6.1.4.1.2011.6.164.1.5.2.1 | not-accessible | AC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA line voltage, AC input breaker status, as well as AC output breakers quantity, which defines hwAcOutputBreakerTable row number. This table's index is hwAcInputIndex, clone AC input table. | |
| hwAcInputEntry | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1 | not-accessible | AC input table entry. | |
| I32 hwAcInputIndex | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.1 | Integer32 | read-only | ACU device table index, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity). |
| U32 hwAcEquipId | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.2 | Unsigned32 | read-only | ACU device ID, which users can configure. Value range: 004,001 to 004,100, in which The first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwAcEquipName | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.3 | OCTET STRING | read-write | ACU device name, of the character string type, is used to specify the alternating current unit (ACU). Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| U32 hwApOrAblVoltage | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.4 | Unsigned32 | read-only | ACU A-phase or AB-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1). |
| U32 hwBpOrBclVoltage | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.5 | Unsigned32 | read-only | ACU B-phase or BC-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1). |
| U32 hwCpOrCalVoltage | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.6 | Unsigned32 | read-only | ACU C-phase or CA-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1). |
| I32 hwAphaseCurrent | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.7 | Integer32 | read-only | ACU A-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1). |
| I32 hwBphaseCurrent | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.8 | Integer32 | read-only | ACU B-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1). |
| I32 hwCphaseCurrent | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.9 | Integer32 | read-only | ACU C-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwAcInputBreakersQuantity | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.10 | Unsigned32 | read-only | Quantity of the AC air circuit breakers. As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each ACU lower-level subset. Value range: 0 to 100. |
| INT hwAcInputOperStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.99 | INTEGER | read-only | State of the site AC distribution uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site AC distribution uint is in the normal state; If the enumeration value is 2, it indicates that AC distribution uint power off; If the enumeration value is 3, it indicates that AC input phase absent; If the enumeration value is 4, it indicates that AC voltage is over upper alarm threshold; If the enumeration value is 5, it indicates that AC voltage is under lower alarm threshold; If the enumeration value is 254, it indicates AC distribution uint alarm resume; If the enumeration value is 255, it indicates AC distribution uint operation status unknown. |
| ROW hwAcRowStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.1.1.100 | RowStatus | read-create | RowStatus of ACU. |
| hwAcInputBreakerTable | 1.3.6.1.4.1.2011.6.164.1.5.2.2 | not-accessible | Ac input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index is hwAcInputBreakerIndex, which qualificated by hwAcInputBreakersQuantity in hwAcInputTable, clone Ac input breaker table. | |
| hwAcInputBreakerEntry | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1 | not-accessible | Ac input breaker table entry. | |
| I32 hwAcInputBreakerIndex | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.1 | Integer32 | read-only | Device table index of the AC air circuit breaker. Value range: 1 to 100. An input air circuit breaker device can be uniquely identified through the ACU table index and device index of the AC air circuit breaker. |
| U32 hwAcInputBreakerEquipId | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.2 | Unsigned32 | read-only | AC input air circuit breaker ID. Value range: 005,001 to 005,100. The first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwAcInputBreakerEquipName | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.3 | OCTET STRING | read-write | AC input air circuit breaker name, of the character string type, can configured by users. Otherwise, the configured character can not be any other languages except English. |
| INT hwAcInputBreakerOperStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.99 | INTEGER | read-only | Operation state of the site AC input breaker. It is an enumeration type: If the enumeration value is 1, it indicates that the site AC input breaker is in the normal state; If the enumeration value is 2, it indicates that the AC input breaker disconnect; If the enumeration value is 254, it indicates AC input breaker alarm resume; If the enumeration value is 255, it indicates AC input breaker operation status unknown. |
| ROW hwAcInputBreakerRowStatus | 1.3.6.1.4.1.2011.6.164.1.5.2.2.1.100 | RowStatus | read-create | RowStatus of AC input breaker. |
| hwSiteDcDistributions | 1.3.6.1.4.1.2011.6.164.1.6 | |||
| hwDcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.1.6.1 | |||
| U32 hwDcsGroupId | 1.3.6.1.4.1.2011.6.164.1.6.1.1 | Unsigned32 | read-only | DC group ID: unique ID of the DC group. in which The first digits indicate the device type and the last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwDcsGroupName | 1.3.6.1.4.1.2011.6.164.1.6.1.2 | OCTET STRING | read-write | Device name of the DC group, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwDcsTotalVoltage | 1.3.6.1.4.1.2011.6.164.1.6.1.3 | Unsigned32 | read-only | Total voltage of the DC group. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1). |
| U32 hwDcsTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.6.1.4 | Unsigned32 | read-only | Total current of the DC group. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal place (.1). |
| U32 hwDcsTotalPower | 1.3.6.1.4.1.2011.6.164.1.6.1.5 | Unsigned32 | read-only | Total power of the DC group. Value range: 0 to 10000, unit: W, and the value is an integer (.0). |
| U32 hwDcsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.6.1.6 | Unsigned32 | read-only | Total quantity of the DC units, and its Value range: 0 to 100. |
| U32 hwSetDcsUpperVoltLimit | 1.3.6.1.4.1.2011.6.164.1.6.1.7 | Unsigned32 | read-write | Upper threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1). |
| U32 hwSetDcsLowerVoltLimit | 1.3.6.1.4.1.2011.6.164.1.6.1.8 | Unsigned32 | read-write | Lower threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1). |
| hwDcDistribution | 1.3.6.1.4.1.2011.6.164.1.6.2 | |||
| hwDcOutputTable | 1.3.6.1.4.1.2011.6.164.1.6.2.1 | not-accessible | DC output table. Use this table to get DC distribution unit ID, DC distribution unit name, DC output voltage, DC output power, and loads quantity in each DC distribution unit, which defines hwLoadsOutputTable row number. This table's index is hwDcOutputIndex, clone Dc output table. | |
| hwDcOutputEntry | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1 | not-accessible | Dc output table entry. | |
| I32 hwDcOutputIndex | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.1 | Integer32 | read-only | Device table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity). |
| U32 hwDcOutputEquipId | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.2 | Unsigned32 | read-only | DC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwDcOutputEquipName | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.3 | OCTET STRING | read-write | DC unit device name, of the character string type, can be configued by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwDcOutputVoltage | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.4 | Unsigned32 | read-only | DC output voltage. It is an analog parameter collected by the DC power in real time. Value range: 0 to 60, unit: V, and the value is accurate to one decimal space (.1). |
| U32 hwDcOutputCurrent | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.5 | Unsigned32 | read-only | DC output current. It is an analog parameter collected by the DC power in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal space (.1). |
| U32 hwDcOutputPower | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.6 | Unsigned32 | read-only | DC output power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0). |
| U32 hwLoadsQuantity | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.7 | Unsigned32 | read-only | Quantity of the DC load output branches, which value range: 0 to 100. As the DC unit lower-level subset, the node indicates the quantity of the DC load output branches contained by each DC unit lower-level subset. |
| INT hwDcOutputOperStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.99 | INTEGER | read-only | State of the site DC distribution uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site DC distribution uint is in the normal state; If the enumeration value is 2, it indicates that DC voltage is over the upper alarm threshold; If the enumeration value is 3, it indicates that DC voltage is under the lower alarm threshold; If the enumeration value is 254, it indicates DC distribution uint alarm resume; If the enumeration value is 255, it indicates DC distribution uint operation status unknown. |
| ROW hwDcOutputRowStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.1.1.100 | RowStatus | read-create | RowStatus of Dc output equipments. |
| hwLoadBranchTable | 1.3.6.1.4.1.2011.6.164.1.6.2.2 | not-accessible | Loads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index is hwLoadBranchIndex, which qualificated by hwloadsQuantity in hwDcOutputTable, clone loads output table. | |
| hwLoadBranchEntry | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1 | not-accessible | Loads output table entry. | |
| I32 hwLoadBranchIndex | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.1 | Integer32 | read-only | Device table index of the DC load output branch, which value range: 1 to 100. A DC load output branch can be uniquely identified through the DC unit table index and device index of the DC load output branch. |
| U32 hwLoadBranchEquipId | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.2 | Unsigned32 | read-only | Device ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of the device. |
| OCT hwLoadBranchEquipName | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.3 | OCTET STRING | read-write | Device name of the DC load output branch, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwLoadBranchCurrent | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.4 | Unsigned32 | read-only | DC load output branch current. It is an analog parameter collected by the load branch in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal space (.1). |
| U32 hwLoadBranchPower | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.5 | Unsigned32 | read-only | DC load branch power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0). |
| INT hwLoadBranchOperStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.99 | INTEGER | read-only | State of the site load output branch. It is an enumeration type: If the enumeration value is 1, it indicates that the site load output branch is in the normal state; If the enumeration value is 2, it indicates that the load output branch disconnect; If the enumeration value is 254, it indicates load output branch alarm resume; If the enumeration value is 255, it indicates load output branch operation status unknown. |
| ROW hwLoadBranchRowStatus | 1.3.6.1.4.1.2011.6.164.1.6.2.2.1.100 | RowStatus | read-create | RowStatus of loads output branch. |
| hwLvdUnits | 1.3.6.1.4.1.2011.6.164.1.7 | |||
| hwLvdsGroup | 1.3.6.1.4.1.2011.6.164.1.7.1 | |||
| U32 hwLvdsGroupId | 1.3.6.1.4.1.2011.6.164.1.7.1.1 | Unsigned32 | read-only | LVD unit group ID. It is the unique ID of the LVD unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwLvdsGroupName | 1.3.6.1.4.1.2011.6.164.1.7.1.2 | OCTET STRING | read-write | Low-voltage power-off unit group name, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwLvdsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.7.1.3 | Unsigned32 | read-only | Total quantity of power-off units. Value range: 0 to 100. |
| hwLvdUnit | 1.3.6.1.4.1.2011.6.164.1.7.2 | |||
| hwLvdBranchTable | 1.3.6.1.4.1.2011.6.164.1.7.2.1 | not-accessible | Power-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as control power-off unit disconnected. This table's index is hwLvdBranchIndex, which qualificated by hwLvdsQuantity, clone power-off unit table. | |
| hwLvdBranchEntry | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1 | not-accessible | Power-off table entry. | |
| I32 hwLvdBranchIndex | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.1 | Integer32 | read-only | Device table index of a power-off unit. Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTotalQuantity). |
| U32 hwLvdUnitEquipId | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.2 | Unsigned32 | read-only | Device ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwLvdUnitEquipName | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.3 | OCTET STRING | read-write | Device name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| INT hwSetLvdEnable | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.4 | INTEGER | read-write | Control power-off unit enabling. It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to enable the power-off unit; If the enumeration value is 2, it means to disable the power-off unit. When the power-off unit control is not configured, the power-off unit is enabled by default. |
| I32 hwSetLvdVoltage | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5 | Integer32 | read-write | Low-voltage power-off voltage of a power-off unit can be configured by users. Its value range: 35 to 60, unit: V, and the value is accurate to one decimal space (.1). |
| INT hwCtrlLvd | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.6 | INTEGER | read-write | Control of the power-off unit. It is an enumeration value, users control it manually. If the NMS notifies the SNMP agent that the node is set to 1, it means to power off the power-off unit; If the NMS notifies the SNMP agent that the node is set to 2, it means that the background controls the power-on of the LVD unit. |
| INT hwLvdBranchOperStatus | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99 | INTEGER | read-only | State of the site LVD uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site LVD uint is in the normal state; If the enumeration value is 2, it indicates that the power-off uint disconnect for low voltage; If the enumeration value is 3, it indicates that the power-off uint disconnect bakeground; If the enumeration value is 4, it indicates that the power-off uint local disconnect manually; If the enumeration value is 5, it indicates that the power-off uint disconnect for under temperature; If the enumeration value is 6, it indicates that the power-off uint disconnect for over temperature; If the enumeration value is 254, it indicates that the power-off uint alarm resume; If the enumeration value is 255, it indicates LVD uint operation status unknown. |
| ROW hwLvdBranchRowStatus | 1.3.6.1.4.1.2011.6.164.1.7.2.1.1.100 | RowStatus | read-create | RowStatus of lvd table. |
| hwSiteEnvUnits | 1.3.6.1.4.1.2011.6.164.1.8 | |||
| hwEnvUnitsGroup | 1.3.6.1.4.1.2011.6.164.1.8.1 | |||
| U32 hwEnvUnitsGroupId | 1.3.6.1.4.1.2011.6.164.1.8.1.1 | Unsigned32 | read-only | Unit group ID of the site environment. It is the unique ID of the unit group on the site. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwEnvUnitsGroupName | 1.3.6.1.4.1.2011.6.164.1.8.1.2 | OCTET STRING | read-write | Unit group name of the site environment, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| INT hwCtrlSmokeReset | 1.3.6.1.4.1.2011.6.164.1.8.1.3 | INTEGER | read-write | Smoke sensor reset. It manually controls clearance of the smoke sensor alarm, and this node is of the enumeration type. If the enumeration value is 1, it indicates that the reset of the smoke sensor is not required. If the enumeration value of the node is 2, it indicates that the background controls the reset of the smoke sensor. |
| INT hwCtrlDoorReset | 1.3.6.1.4.1.2011.6.164.1.8.1.4 | INTEGER | read-write | Door actuator reset control. It manually controls clearance of the door actuator alarm. This node is of the enumeration type. If the enumeration value is 1, it indicates that clearance of the door actuator is not required; If the enumeration value is 2, it indicates that the background controls clearance of the door actuator. |
| INT hwCtrlBuzzerEnable | 1.3.6.1.4.1.2011.6.164.1.8.1.5 | INTEGER | read-write | Buzzer enabling. It manually controls the enabling of the buzzer alarm. This node is of the enumeration type. When the enumeration value is 1, it means to enable the buzzer; When the enumeration value is 2, it means to disable the buzzer. |
| U32 hwEnvTempSensorsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.8.1.6 | Unsigned32 | read-only | Quantity of the environment temperature sensors, and its value range: 0 to 256. |
| U32 hwEnvHumiSensorsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.8.1.7 | Unsigned32 | read-only | Quantity of the environment humidity sensors, and its value range: 0 to 256. |
| U32 hwSpareDigitalsTotalQuantity | 1.3.6.1.4.1.2011.6.164.1.8.1.8 | Unsigned32 | read-only | Quantity of the Spare digitals, and its value range: 0 to 256. |
| hwEnvSensor | 1.3.6.1.4.1.2011.6.164.1.8.2 | |||
| hwEnvTempSensorTable | 1.3.6.1.4.1.2011.6.164.1.8.2.1 | not-accessible | Site environment temperature table. Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment temperature, set environment temperature upper limit, environment temperature lower limit, and environment temperature alarm enable. This table's index is hwEnvTempSensorIndex, which qualificated by hwEnvTempSensorsQuantity, clone site environment temperature table. | |
| hwEnvTempSensorEntry | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1 | not-accessible | Site environment temperature table entry. | |
| I32 hwEnvTempSensorIndex | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.1 | Integer32 | read-only | Table index of the environment temperature sensors. Value range: 1 to 256. Lines of the device table are restricted by the quantity of environment temperature sensors (hwEnvTempSensorsTotalQuantity). |
| U32 hwEnvTempEquipId | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.2 | Unsigned32 | read-only | Environment temperature sensor ID. Value range: 009'001 to 009'255, in which the first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwEnvTempEquipName | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.3 | OCTET STRING | read-write | Environment temperature sensor name, of the character string type, is used to specify an environment temperature sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| I32 hwEnvTemperature | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.4 | Integer32 | read-only | Environment temperature. It is an environment parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.0). If the value is -1024, it indicates that the temperature sensor is not configured. |
| I32 hwSetEnvTempUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.5 | Integer32 | read-write | Upper threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetEnvTempLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.6 | Integer32 | read-write | Lower threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetEnvTempMeasureUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.7 | Integer32 | read-write | Upper threshold of the environment temperature measurement, can be configured by users. Value range: 0 to 100, unit: centigrade (°„C), and the value is an integer (.0). |
| I32 hwSetEnvTempMeasureLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.8 | Integer32 | read-write | Lower threshold of the environment temperature measurement, can be configured by users. Value range: -50 to 0, unit: centigrade (°„C), and the value is an integer (.0). |
| INT hwSetEnvTempAlarmEnable | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.9 | INTEGER | read-write | Environment temperature alarm. It is an enumeration type: If the enumeration value is 1, enable the alarm of the environment temperature; If the enumeration value is 2, disable the alarm of the environment temperature. |
| INT hwEnvTempSensorOperStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.99 | INTEGER | read-only | State of the site environment temperature sensor. It is an enumeration type: If the enumeration value is 1, it indicates that the site environment temperature sensor is in the normal state; If the enumeration value is 2, it indicates that the environment temperature sensor is over temperature; If the enumeration value is 3, it indicates that the environment temperature sensor is under temperature; If the enumeration value is 4, it indicates that the environment temperature sensor is not in slot; If the enumeration value is 254, it indicates that environment temperature alarm resume; If the enumeration value is 255, it indicates environment temperature sensor operation status unknown. |
| ROW hwEnvTempSensorRowStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.1.1.100 | RowStatus | read-create | RowStatus of Environment temperature table. |
| hwEnvHumiSensorTable | 1.3.6.1.4.1.2011.6.164.1.8.2.2 | not-accessible | Environment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set environment humidity upper limit, environment humidity lower limit, and environment humidity alarm enable. This table's index is hwEnvHumiSensorIndex, which qualificated by hwEnvHumiSensorIndex, clone site environment humidity table. | |
| hwEnvHumiSensorEntry | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1 | not-accessible | Environment humidity table entry. | |
| I32 hwEnvHumiSensorIndex | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.1 | Integer32 | read-only | Table index of the environment humility sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of environment humility sensors (hwEnvHumiSensorsTotalQuantity). |
| U32 hwEnvHumiEquipId | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.2 | Unsigned32 | read-only | Environment humility sensor ID, can be configured by users. Value range: 010'001 to 010'255, in which the first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwEnvHumiEquipName | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.3 | OCTET STRING | read-write | Environment humility sensor name, of the character string type, is used to specify an environment humility sensor. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| I32 hwEnvHumidity | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.4 | Integer32 | read-only | Environment humility. It is an environment parameter collected in real time. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). If the value is 255, it indicates that the humidity sensor is not configured. |
| I32 hwSetEnvHumidityUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.5 | Integer32 | read-write | Upper threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). |
| I32 hwSetEnvHumidityLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.6 | Integer32 | read-write | Lower threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). |
| I32 hwSetEnvHumidityMeasureUpperLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.7 | Integer32 | read-write | Upper threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). |
| I32 hwSetEnvHumidityMeasureLowerLimit | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.8 | Integer32 | read-write | Lower threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). |
| INT hwSetEnvHumiAlarmEnable | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.9 | INTEGER | read-write | Environment humility alarm. It is an enumeration type: If the enumeration value is 1, enable the alarm of the environment humility; If the enumeration value is 2, disable the alarm of the environment humility. The environment humility alarm is enabled by default. |
| INT hwEnvHumiSensorOperStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.99 | INTEGER | read-only | State of the site environment humidity sensor. It is an enumeration type: If the enumeration value is 1, it indicates that the site environment humidity sensor is in the normal state; If the enumeration value is 2, it indicates that the environment humidity sensor is over humidity; If the enumeration value is 3, it indicates that the environment humidity sensor is under humidity; If the enumeration value is 4, it indicates that the environment humidity sensor is not in slot; If the enumeration value is 254, it indicates that environment humidity alarm resume; If the enumeration value is 255, it indicates environment humidity sensor operation status unknown. |
| ROW hwEnvHumiSensorRowStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.2.1.100 | RowStatus | read-create | RowStatus of Environment humidity table. |
| hwSpareDigitalTable | 1.3.6.1.4.1.2011.6.164.1.8.2.3 | not-accessible | Spare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to set Spare digital alarm enable. This table's index is hwSpareDigitalIndex, which qualificated by hwSpareDigitalsTotalQuantity, clone switch input table. | |
| hwSpareDigitalEntry | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1 | not-accessible | Spare digital table entry. | |
| I32 hwSpareDigitalIndex | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.1 | Integer32 | read-only | Spare digital table index, which value range: 1 to 256. Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity). |
| U32 hwSpareDigitalEquipId | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.2 | Unsigned32 | read-only | Spare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwSpareDigitalEquipName | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.3 | OCTET STRING | read-write | Spare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| INT hwSetSpareDigitalAlarmTension | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.4 | INTEGER | read-write | Spare digital alarm state. It is an enumeration value. If the value of the node is 0, it indicates a low-tension alarm; If the value of the node is 1, it indicates a high-tension alarm. |
| INT hwSetSpareDigitalAlarmEnable | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.5 | INTEGER | read-write | Spare digital alarm enabling. It is an enumeration type: If the enumeration value is 1, it means to enable the alarm; If the enumeration value is 2, it means to disable the alarm. |
| INT hwSpareDigitalOperStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.99 | INTEGER | read-only | State of the site Spare digital. It is an enumeration type: If the enumeration value is 1, it indicates that the Spare digital operation state is normal; If the enumeration value is 2, it indicates that a alarm occurs on the Spare digital; If the enumeration value is 254, it indicates that spare digital alarm resume; If the enumeration value is 255, it indicates Spare digital operation status unknown. |
| ROW hwSpareDigitalRowStatus | 1.3.6.1.4.1.2011.6.164.1.8.2.3.1.100 | RowStatus | read-create | RowStatus of Spare digital device table. |
| hwSitePDEs | 1.3.6.1.4.1.2011.6.164.1.9 | |||
| hwPDEGroup | 1.3.6.1.4.1.2011.6.164.1.9.1 | |||
| U32 hwPDEGroupId | 1.3.6.1.4.1.2011.6.164.1.9.1.1 | Unsigned32 | read-only | PDE unit group ID. It is the unique ID of the PDE unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the last three digits are 000, it indicates a virtual device. |
| OCT hwPDEGroupName | 1.3.6.1.4.1.2011.6.164.1.9.1.2 | OCTET STRING | read-write | PDE unit group name, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except English. |
| U32 hwPDEGroupNum | 1.3.6.1.4.1.2011.6.164.1.9.1.3 | Unsigned32 | read-only | PDE Num,Value range: 0 to 100. |
| U32 hwPDEGroupCommNum | 1.3.6.1.4.1.2011.6.164.1.9.1.4 | Unsigned32 | read-only | Communication PDE Num,Value range: 0 to 100. |
| U32 hwPDEGroupTotalPower | 1.3.6.1.4.1.2011.6.164.1.9.1.5 | Unsigned32 | read-only | PDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1). |
| U32 hwPDEGroupTotalCurrent | 1.3.6.1.4.1.2011.6.164.1.9.1.6 | Unsigned32 | read-only | PDE Total Current,Value range: 0.0 to 300.0.Unit: A.and the value is accurate to one decimal space (.1). |
| INT hwPDEGroupCommStatus | 1.3.6.1.4.1.2011.6.164.1.9.1.7 | INTEGER | read-only | PDE Communication Status. It is an enumeration type: If the enumeration value is 1, it indicates that communication is normal; If the enumeration value is 2, it indicates that communication is abnormal. If the enumeration value is 255, it indicates that communication is unknown. |
| hwPDE | 1.3.6.1.4.1.2011.6.164.1.9.3 | |||
| hwPDETable | 1.3.6.1.4.1.2011.6.164.1.9.3.1 | not-accessible | PDE table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE status. This table's index is hwPDEIndex. | |
| hwPDEEntry | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1 | not-accessible | PDE table entry. | |
| I32 hwPDEIndex | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.1 | Integer32 | read-only | PDE table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE. |
| U32 hwPDEEquipId | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.2 | Unsigned32 | read-only | PDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwPDEEquipName | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.3 | OCTET STRING | read-write | PDE name, of the character string type, is used to specify PDEs. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| U32 hwPDETotalRunningTime | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.4 | Unsigned32 | read-only | PDE Total Running Time,Value range: 0 to 876000.Unit: H. |
| U32 hwPDEBranchNum | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.5 | Unsigned32 | read-only | PDE Branch Number,Value range: 0 to 6. |
| U32 hwPDETotalPower | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.6 | Unsigned32 | read-only | PDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1). |
| U32 hwPDETotalCurrent | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.7 | Unsigned32 | read-only | PDE Total Current,Value range: 0.0 to 30000.0.Unit: A.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch1Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.8 | Unsigned32 | read-only | PDE Branch1 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch2Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.9 | Unsigned32 | read-only | PDE Branch2 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch3Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.10 | Unsigned32 | read-only | PDE Branch3 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch4Power | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.11 | Unsigned32 | read-only | PDE Branch4 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch1Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.12 | Unsigned32 | read-only | PDE Branch1 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch2Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.13 | Unsigned32 | read-only | PDE Branch2 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch3Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.14 | Unsigned32 | read-only | PDE Branch3 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch4Current | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.15 | Unsigned32 | read-only | PDE Branch4 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch1Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.16 | Unsigned32 | read-only | PDE Branch1 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch2Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.17 | Unsigned32 | read-only | PDE Branch2 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch3Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.18 | Unsigned32 | read-only | PDE Branch3 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch4Voltage | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.19 | Unsigned32 | read-only | PDE Branch4 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1). |
| U32 hwPDEBranch1Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.20 | Unsigned32 | read-only | PDE Branch1 Temperature,Value range: 0 to 300.Unit: deg. |
| U32 hwPDEBranch2Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.21 | Unsigned32 | read-only | PDE Branch2 Temperature,Value range: 0 to 300.Unit: deg. |
| U32 hwPDEBranch3Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.22 | Unsigned32 | read-only | PDE Branch3 Temperature,Value range: 0 to 300.Unit: deg. |
| U32 hwPDEBranch4Temperature | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.23 | Unsigned32 | read-only | PDE Branch4 Temperature,Value range: 0 to 300.Unit: deg. |
| INT hwPDEOperStatus | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.24 | INTEGER | read-only | State of the PDE. It is an enumeration type: If the enumeration value is 1, it indicates that the PDE is in the normal state; If the enumeration value is 2, it indicates that the PDE is in the alarm state; If the enumeration value is 254, it indicates that the PDE is in the resume state; If the enumeration value is 255, it indicates PDE operation status unknown. |
| ROW hwPDERowStatus | 1.3.6.1.4.1.2011.6.164.1.9.3.1.1.100 | RowStatus | read-create | RowStatus of PDE table. |
| hwPDEConfigTable | 1.3.6.1.4.1.2011.6.164.1.9.3.2 | not-accessible | PDE Config table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE config parameter. This table's index is hwPDEConfigIndex. | |
| hwPDEConfigEntry | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1 | not-accessible | PDE Config table entry. | |
| I32 hwPDEConfigIndex | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.1 | Integer32 | read-only | PDE Config table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE. |
| U32 hwPDEConfigEquipId | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.2 | Unsigned32 | read-only | PDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN. |
| OCT hwPDEConfigEquipName | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.3 | OCTET STRING | read-write | PDE name, of the character string type, is used to specify PDEs. Users can configure it. Otherwise, the configured character can not be any other languages except English. |
| U32 hwPDEOverTempProtect | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.4 | Unsigned32 | read-write | PDE Over Temperature Protect,Value range: 100 to 120.Unit: deg. |
| INT hwPDEVolProtectEnable | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.5 | INTEGER | read-write | PDE Over Protect Enable,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to enable the PDE voltage protect; If the enumeration value is 2, it means to disable the PDE voltage protect. |
| U32 hwPDEOverVoltageProtect | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.6 | Unsigned32 | read-write | PDE Over Voltage Protect,Value range: 58 to 60.Unit: V. |
| U32 hwPDEUnderVoltageProtect | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.7 | Unsigned32 | read-write | PDE Under Voltage Protect,Value range: 40 to 48.Unit: V. |
| U32 hwPDEHysteresis | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.8 | Unsigned32 | read-write | PDE Hysteresis,Value range: 1 to 3.Unit: V. |
| INT hwPDEReset | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.9 | INTEGER | read-write | PDE Reset Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to reset the PDE; |
| INT hwPDEBranch1Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.10 | INTEGER | read-write | PDE Branch1 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch1; If the enumeration value is 2, it means to close the branch1; |
| INT hwPDEBranch2Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.11 | INTEGER | read-write | PDE Branch2 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch2; If the enumeration value is 2, it means to close the branch2; |
| INT hwPDEBranch3Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.12 | INTEGER | read-write | PDE Branch3 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch3; If the enumeration value is 2, it means to close the branch3; |
| INT hwPDEBranch4Control | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.13 | INTEGER | read-write | PDE Branch4 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch4; If the enumeration value is 2, it means to close the branch4; |
| U32 hwPDEBranch1CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.14 | Unsigned32 | read-write | PDE Branch1 Current Limit,Value range: 1 to 20.Unit: A. |
| U32 hwPDEBranch2CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.15 | Unsigned32 | read-write | PDE Branch2 Current Limit,Value range: 1 to 30.Unit: A. |
| U32 hwPDEBranch3CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.16 | Unsigned32 | read-write | PDE Branch3 Current Limit,Value range: 1 to 30.Unit: A. |
| U32 hwPDEBranch4CurrentLimit | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.17 | Unsigned32 | read-write | PDE Branch4 Current Limit,Value range: 1 to 20.Unit: A. |
| ROW hwPDEConfigRowStatus | 1.3.6.1.4.1.2011.6.164.1.9.3.2.1.100 | RowStatus | read-create | RowStatus of PDE config table. |
| hwSiteMonitorMIBTraps | 1.3.6.1.4.1.2011.6.164.2 | |||
| hwSiteAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1 | |||
| hwSiteAlarmTrapsPrefix | 1.3.6.1.4.1.2011.6.164.2.1.0 | |||
| NTF hwRectifierFaultAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.1 | When rectifiers fault alarms happen, a alarm trap will be send. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwRectifierFaultAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.2 | Rectifier Fault alarm resolved.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwRectifierAbnormalAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.3 | Rectifier abnormal alarm, because of communication failure, module protection, or turnoff. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwRectifierAbnormalAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.4 | Rectifier abnormal alarm resume. Description.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattLoopBreakAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.5 | Battery loop disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattLoopBreakAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.6 | Battery loop break alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattLvdAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.7 | Battery disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattLvdAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.8 | Battery LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery LVD unit equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattOverCurrAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.9 | Batterys charge in over current. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattOverCurrAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.10 | Batterys over current alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattStringTempAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.11 | Battery string temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | ||
| NTF hwBattStringTempAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.12 | Battery string temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | ||
| NTF hwBattDischargeAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.13 | Battery group discharge alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | ||
| NTF hwBattDischargeAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.14 | Battery group discharge alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery group ID and group name are also include in VB(variable bondings). | ||
| NTF hwAcInputAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.15 | AC absent or AC power off alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcInputAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.16 | AC input alarm resumed. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcVoltAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.17 | AC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcVoltAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.18 | AC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwDcVoltAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.19 | DC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwDcVoltAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.20 | DC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, DC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwLoadLvdAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.21 | Loads disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwLoadLvdAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.22 | Load LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, load LVD unit equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwLoadFuseAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.23 | Load fuse broken down. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwLoadFuseAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.24 | Load fuse alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwEnvTempAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.25 | Environment temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwEnvTempAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.26 | Environment temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment temperature sensor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwEnvHumiAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.27 | Environment humidity is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwEnvHumiAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.28 | Environment humidity alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment humidity sensor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwSpareDigitalAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.29 | Spare digital fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwSpareDigitalAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.30 | Spare digital alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, Spare digital equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwDoorAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.31 | Door open. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwDoorAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.32 | Door alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwWaterAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.33 | Water alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwWaterAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.34 | Water alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwSmokeAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.35 | Site is on fire, which is detected by smoke sensors. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwSmokeAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.36 | Smoke alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwWireAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.37 | Wire alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwWireAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.38 | Wire alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, envirenment unit group ID and group name are also include in VB(variable bondings). | ||
| NTF hwAcBreakerAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.39 | AC breaker alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings). | ||
| NTF hwAcBreakerAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.40 | AC breaker alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC distribution unit ID and its name are also include in VB(variable bondings). | ||
| NTF hwMultiRectFailureAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.41 | More than one rectifier reported fault alarms in the same time. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | ||
| NTF hwMultiRectFailureAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.42 | Multi-rectifiers fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | ||
| NTF hwRectRedundAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.43 | Rectifiers work redundantly, in this case that some of rectifiers will going to sleep. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | ||
| NTF hwRectRedundAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.44 | Rectifiers redundant alarm resume, when the power supply and requirement were in balance. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, rectifier group ID and group name are also include in VB(variable bondings). | ||
| NTF hwBattUnbalanceAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.45 | Battery works in unbalance state. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwBattUnbalanceAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.46 | Battery unbalance alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, battery string equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcFreqFaultAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.47 | AC frequency is fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcFreqFaultAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.48 | AC frequency alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwXmuSelfFaultAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.49 | There are some fault in XMU itself. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwXmuSelfFaultAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.50 | XMU fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwRs485CommAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.51 | RS485 communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwRs485CommAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.52 | RS485 communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwNetCommAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.53 | Network communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwNetCommAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.54 | Network communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, monitor equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcOffLongTimeAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.55 | AC power off for a long time alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwAcOffLongTimeAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.56 | AC power off for a long time alarms resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm severity, and Site alarm SN. Additionally, in order to identify the device, AC equipment ID and equipment name are also include in VB(variable bondings). | ||
| NTF hwSpdAlarmTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.57 | Description. | ||
| NTF hwSpdAlarmResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.58 | Description. | ||
| NTF hwBadBatteryTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.59 | Description. | ||
| NTF hwBadBatteryResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.60 | Description. | ||
| NTF hwLvd2DisconnectingTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.61 | Description. | ||
| NTF hwLvd2DisconnectingResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.62 | Description. | ||
| NTF hwBattHighTempTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.63 | Description. | ||
| NTF hwBattHighTempResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.64 | Description. | ||
| NTF hwBattLowTempTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.65 | Description. | ||
| NTF hwBattLowTempResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.66 | Description. | ||
| NTF hwDcUltraOverVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.67 | Description. | ||
| NTF hwDcUltraOverVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.68 | Description. | ||
| NTF hwDcUltraUnderVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.69 | Description. | ||
| NTF hwDcUltraUnderVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.70 | Description. | ||
| NTF hwUmiCommFailTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.71 | Description. | ||
| NTF hwUmiCommFailResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.72 | Description. | ||
| NTF hwShortTestFailTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.73 | Description. | ||
| NTF hwShortTestFailResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.74 | Description. | ||
| NTF hwMissingBattTempSensorTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.75 | Description. | ||
| NTF hwMissingBattTempSensorResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.76 | Description. | ||
| NTF hwBattTempSensorFaultTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.77 | Description. | ||
| NTF hwBattTempSensorFaultResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.78 | Description. | ||
| NTF hwAcOverVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.79 | Description. | ||
| NTF hwAcOverVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.80 | Description. | ||
| NTF hwAcUnderVoltageTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.81 | Description. | ||
| NTF hwAcUnderVoltageResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.82 | Description. | ||
| NTF hwPDELoadFaultTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.83 | Description. | ||
| NTF hwPDELoadFaultResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.84 | Description. | ||
| NTF hwPDENoResponseTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.85 | Description. | ||
| NTF hwPDENoResponseResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.86 | Description. | ||
| NTF hwPDEFailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.87 | Description. | ||
| NTF hwPDEFailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.88 | Description. | ||
| NTF hwPDEBr1FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.89 | Description. | ||
| NTF hwPDEBr1FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.90 | Description. | ||
| NTF hwPDEBr2FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.91 | Description. | ||
| NTF hwPDEBr2FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.92 | Description. | ||
| NTF hwPDEBr3FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.93 | Description. | ||
| NTF hwPDEBr3FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.94 | Description. | ||
| NTF hwPDEBr4FailureTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.95 | Description. | ||
| NTF hwPDEBr4FailureResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.96 | Description. | ||
| NTF hwPDEBr1ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.97 | Description. | ||
| NTF hwPDEBr1ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.98 | Description. | ||
| NTF hwPDEBr2ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.99 | Description. | ||
| NTF hwPDEBr2ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.100 | Description. | ||
| NTF hwPDEBr3ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.101 | Description. | ||
| NTF hwPDEBr3ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.102 | Description. | ||
| NTF hwPDEBr4ProtectTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.103 | Description. | ||
| NTF hwPDEBr4ProtectResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.104 | Description. | ||
| NTF hwPDELostTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.105 | Description. | ||
| NTF hwPDELostResumeTraps | 1.3.6.1.4.1.2011.6.164.2.1.0.106 | Description. | ||
| hwSiteDevicesTraps | 1.3.6.1.4.1.2011.6.164.2.2 | |||
| hwDevicesTrapsPrefix | 1.3.6.1.4.1.2011.6.164.2.2.0 | |||
| NTF hwRectifiersInslotChange | 1.3.6.1.4.1.2011.6.164.2.2.0.1 | When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable. | ||
| NTF hwBatterysInslotChange | 1.3.6.1.4.1.2011.6.164.2.2.0.2 | When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as loopBreak (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable. | ||
| NTF hwBattTestRecordsAdd | 1.3.6.1.4.1.2011.6.164.2.2.0.3 | After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently. This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable. The battery test table allows you only to add entries. | ||
| NTF hwEnvTempSensInslotChange | 1.3.6.1.4.1.2011.6.164.2.2.0.4 | When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable. | ||
| NTF hwEnvHumiSensInslotChange | 1.3.6.1.4.1.2011.6.164.2.2.0.5 | When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable. | ||
| NTF hwPDEsInslotChange | 1.3.6.1.4.1.2011.6.164.2.2.0.6 | Description. | ||
| hwV101SiteDevicesTraps | 1.3.6.1.4.1.2011.6.164.2.3 | |||
| hwV101DevicesTrapsPrefix | 1.3.6.1.4.1.2011.6.164.2.3.1 | |||
| NTF hwV101RectifiersInslotChange | 1.3.6.1.4.1.2011.6.164.2.3.1.1 | When the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable or hwRectOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the rectifier are bound to identify the specific rectifier and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as commFail (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwRectConfigTable or hwRectOperTable. | ||
| NTF hwV101BatterysInslotChange | 1.3.6.1.4.1.2011.6.164.2.3.1.2 | When the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigTable or hwBatttOperTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the battery string are bound to identify the specific battery string and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as loopBreak (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwBatttConfigTable or hwBatttOperTable. | ||
| NTF hwV101BattTestRecordsAdd | 1.3.6.1.4.1.2011.6.164.2.3.1.3 | After a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site description, and NE identifier. The NMS needs to add the corresponding entry to the battery test table. The test records are sorted by time in descending order. The battery test table holds a maximum of 10 test records. If the number of test records exceeds 10, the earlier records starting from the last but one record are deleted at a time because the last record is saved permanently. This trap is the unique trigger condition that causes the NMS to add entries from hwBattsTestResultTable. The battery test table allows you only to add entries. | ||
| NTF hwV101EnvTempSensInslotChange | 1.3.6.1.4.1.2011.6.164.2.3.1.4 | When the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnTempSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment temperature sensor are bound to identify the specific environment temperature sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvTempSensorTable. | ||
| NTF hwV101EnvHumiSensInslotChange | 1.3.6.1.4.1.2011.6.164.2.3.1.5 | When the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from hwEvnHumiSensorTable. The bound information includes the site address, site name, site description, and NE identifier. In addition, the ID, name, and status of the environment humidity sensor are bound to identify the specific environment humidity sensor and its operation type. When an entry is added, the device status is reported as normal (1); when an entry is deleted, the device status is reported as notInslot (4). This trap is the unique trigger condition that causes the NMS to add or delete entries to or from hwEnvHumiSensorTable. | ||
| NTF hwV101PDEsInslotChange | 1.3.6.1.4.1.2011.6.164.2.3.1.6 | Description. | ||
| hwSiteMonitorMIBConformance | 1.3.6.1.4.1.2011.6.164.3 | |||
| hwSiteMonitorGroups | 1.3.6.1.4.1.2011.6.164.3.1 | |||
| hwSiteInfoGroup | 1.3.6.1.4.1.2011.6.164.3.1.1 | Site information group. | ||
| hwSiteMonitorsGroup | 1.3.6.1.4.1.2011.6.164.3.1.2 | Site monitor group. | ||
| hwSiteRectifiersGroup | 1.3.6.1.4.1.2011.6.164.3.1.3 | Site rectifier group. | ||
| hwSiteBatterysGroup | 1.3.6.1.4.1.2011.6.164.3.1.4 | Site battery group. | ||
| hwSiteAcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.3.1.5 | Site AC distribution group. | ||
| hwSiteDcDistributionsGroup | 1.3.6.1.4.1.2011.6.164.3.1.6 | Site DC distribution group. | ||
| hwSiteLvdUnitsGroup | 1.3.6.1.4.1.2011.6.164.3.1.7 | Site low voltage disconnection unit group. | ||
| hwSiteEnvUnitsGroup | 1.3.6.1.4.1.2011.6.164.3.1.8 | Site envirenment unit group. | ||
| hwSiteAlarmTrapsGroup | 1.3.6.1.4.1.2011.6.164.3.1.9 | Site alarm trap group. | ||
| hwSiteDeviceTrapsGroup | 1.3.6.1.4.1.2011.6.164.3.1.10 | Description. | ||
| hwSiteEfusesGroup | 1.3.6.1.4.1.2011.6.164.3.1.11 | Description. |
RFC description
Management Information Base for Huawei site monitoring and management. Defines objects for site device identification, alarm tracking, patch management, and NMS interface control on Huawei telecommunications equipment.