All MIBs › HUAWEI-SITE-MONITOR-MIB › hwSetBattsHighTempVoltLimit
hwSetBattsHighTempVoltLimit
Module: HUAWEI-SITE-MONITOR-MIB
OID (symbolic): HUAWEI-SITE-MONITOR-MIB::hwSetBattsHighTempVoltLimit
OID (numeric): 1.3.6.1.4.1.2011.6.164.1.4.1.5
Node type: OBJECT-TYPE
Type: Unsigned32
Access: read-write
Description: Battery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be configured by users. If the low-voltage power-off protection mode (that is, the enumeration value is 1) is selected, the node is a low-voltage power-off node. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1).
What is hwSetBattsHighTempVoltLimit?
Battery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be configured by users. If the low-voltage power-off protection mode (that is, the enumeration value is 1) is selected, the node is a low-voltage power-off node. An administrator tunes this setpoint (for example to 24 V) to change equipment protection, charging, or alarm-threshold behavior rather than just observing it.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.2011.6.164.1.4.1.5 snmpwalk -v2c -c public <target> HUAWEI-SITE-MONITOR-MIB::hwSetBattsHighTempVoltLimit
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.2011.6.164.1.4.1.5.1 snmpget -v2c -c public <target> HUAWEI-SITE-MONITOR-MIB::hwSetBattsHighTempVoltLimit.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.2011.6.164.1.4.1.5.1 i <value>
Start monitoring Huawei multi-site management platform (load/backup/patch management) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the HUAWEI-SITE-MONITOR-MIB::hwSetBattsHighTempVoltLimit OID value, configure state conditions and alerts, and monitor any Huawei multi-site management platform (load/backup/patch management) from a single console.
OID Breakdown
Upper-level ancestors (8 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.2011 | huawei | EXPERTV2-MIB |
| 1.3.6.1.4.1.2011.6 | huaweiUtility | HUAWEI-3COM-OID-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.2011.6.164 | hwSiteMonitorMIB | HUAWEI-SITE-MONITOR-MIB |
| 1.3.6.1.4.1.2011.6.164.1 | hwSiteMonitorMIBObjects | HUAWEI-SITE-MONITOR-MIB |
| 1.3.6.1.4.1.2011.6.164.1.4 | hwSiteBatterys | HUAWEI-SITE-MONITOR-MIB |
| 1.3.6.1.4.1.2011.6.164.1.4.1 | hwBattsConfig | HUAWEI-SITE-MONITOR-MIB |
| 1.3.6.1.4.1.2011.6.164.1.4.1.5 | hwSetBattsHighTempVoltLimit | HUAWEI-SITE-MONITOR-MIB |