All MIBs › SPSv1-MIB
Category: Generic / Unclassified
Description: Manages SPS v1 device configuration, power status, and operational parameters.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is SPSv1-MIB?
SPSv1-MIB is a vendor-specific MIB, apparently from Powertek/a PDU (power distribution unit) product line, covering device identity and network configuration for a smart PDU. It exposes agent software version and serial number identity plus IPv4/IPv6 network configuration (DHCP control, address, gateway, subnet, DNS servers, IPv6 autoconfig and prefix). Its monitoring value centers on software/configuration status: pduIdentAgentSoftwareVersion confirms the management firmware level, while the pduNetworkTcpip* objects reveal whether the unit has a valid, reachable network configuration, which is a prerequisite for polling any power/environmental data it may also expose. Given the object naming, it likely depends on or accompanies a broader PDU power-monitoring MIB from the same vendor tree (product/pdu) for load, outlet, and power-status objects. It is deployed on rack-mounted PDUs in data centers or server rooms managed over IP, where SPSv1-MIB SNMP monitoring confirms the unit's network reachability before assuming a power or hardware fault.
IPNetwork Monitor allows you to monitor SNMP objects defined in SPSv1-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Powertek/SPS-series rack PDU
Monitoring Examples
An administrator would check pduIdentAgentSoftwareVersion and pduIdentSerialNumber to inventory which firmware version a given PDU is running, and would poll pduNetworkTcpipIpv4Address, pduNetworkTcpipIpv4Gateway, and pduNetworkTcpipIpv4DhcpControl to confirm the unit obtained or was assigned correct network settings. pduNetworkTcpipIpv6Control and pduNetworkTcpipIpv6Address would be checked in dual-stack environments to verify IPv6 reachability. A PDU that stops responding to SNMP would first be checked here for a changed IP or failed DHCP lease before assuming a hardware fault.
What Can Be Monitored
- agent firmware version
- serial number identity
- IPv4 address/gateway/subnet/DNS
- DHCP state
- IPv6 configuration and prefix
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| enterprises |
From RFC1213-MIB
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| powertek | 1.3.6.1.4.1.42610 | |||
| product | 1.3.6.1.4.1.42610.1 | |||
| pdu | 1.3.6.1.4.1.42610.1.4 | |||
| sps | 1.3.6.1.4.1.42610.1.4.4 | |||
| pduObjects | 1.3.6.1.4.1.42610.1.4.4.1 | |||
| pduIdent | 1.3.6.1.4.1.42610.1.4.4.1.1 | |||
| STR pduIdentAgentSoftwareVersion | 1.3.6.1.4.1.42610.1.4.4.1.1.1 | DisplayString | read-only | The firmware version of the device. |
| STR pduIdentSerialNumber | 1.3.6.1.4.1.42610.1.4.4.1.1.2 | DisplayString | read-only | A Model of this device. |
| pduNetwork | 1.3.6.1.4.1.42610.1.4.4.1.2 | |||
| pduNetworkTcpip | 1.3.6.1.4.1.42610.1.4.4.1.2.1 | |||
| INT pduNetworkTcpipDhcpControl | 1.3.6.1.4.1.42610.1.4.4.1.2.1.1 | INTEGER | read-write | Enable/disable DHCP protocol |
| pduNetworkTcpipIpv4 | 1.3.6.1.4.1.42610.1.4.4.1.2.1.2 | |||
| IP pduNetworkTcpipIpv4Address | 1.3.6.1.4.1.42610.1.4.4.1.2.1.2.1 | IpAddress | read-write | The ip address that NMS can identify the managed device. |
| IP pduNetworkTcpipIpv4Gateway | 1.3.6.1.4.1.42610.1.4.4.1.2.1.2.2 | IpAddress | read-write | The default gateway that allow device managed through routers. |
| IP pduNetworkTcpipIpv4Subnet | 1.3.6.1.4.1.42610.1.4.4.1.2.1.2.3 | IpAddress | read-write | Internet address subnet mask |
| IP pduNetworkTcpipIpv4PrimaryDNS | 1.3.6.1.4.1.42610.1.4.4.1.2.1.2.4 | IpAddress | read-write | Internet address of Primary DNS Server |
| IP pduNetworkTcpipIpv4SecondaryDNS | 1.3.6.1.4.1.42610.1.4.4.1.2.1.2.5 | IpAddress | read-write | Internet address of Secondary DNS |
| pduNetworkTcpipIpv6 | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3 | |||
| INT pduNetworkTcpipIpv6Control | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.1 | INTEGER | read-write | Enable/disable IPv6 protocol |
| INT pduNetworkTcpipIpv6AutoConfig | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.2 | INTEGER | read-write | IPv6 Auto-config or Maual setting |
| STR pduNetworkTcpipIpv6Address | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.3 | DisplayString | read-only | The ipv6 address that NMS can identify the managed device. |
| INT pduNetworkTcpipIpv6Prefix | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.4 | INTEGER | read-only | The prefix length for ipv6 address. |
| STR pduNetworkTcpipIpv6Router | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.5 | DisplayString | read-only | The default gateway that allow device managed through routers. |
| STR pduNetworkTcpipIpv6PrimaryDNS | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.6 | DisplayString | read-write | Internet address of Primary DNS Server |
| STR pduNetworkTcpipIpv6SecondaryDNS | 1.3.6.1.4.1.42610.1.4.4.1.2.1.3.7 | DisplayString | read-write | Internet address of Secondary DNS |
| pduNetworkSecurity | 1.3.6.1.4.1.42610.1.4.4.1.2.2 | |||
| INT pduNetworkSecurityControl | 1.3.6.1.4.1.42610.1.4.4.1.2.2.1 | INTEGER | read-write | Enable/disable Network Access Protection |
| pduNetworkSecuritySsh | 1.3.6.1.4.1.42610.1.4.4.1.2.2.2 | |||
| INT pduNetworkSecuritySshControl | 1.3.6.1.4.1.42610.1.4.4.1.2.2.2.1 | INTEGER | read-write | Enable/disable SSH Access Protection |
| INT pduNetworkSecuritySshInterval | 1.3.6.1.4.1.42610.1.4.4.1.2.2.2.2 | INTEGER | read-write | Detecting Interval of SSH Access Protection |
| INT pduNetworkSecuritySshFailTimes | 1.3.6.1.4.1.42610.1.4.4.1.2.2.2.3 | INTEGER | read-write | Unsuccessful attempts of SSH Access Protection |
| INT pduNetworkSecuritySshBlock | 1.3.6.1.4.1.42610.1.4.4.1.2.2.2.4 | INTEGER | read-write | Block Time of SSH Access Protection |
| pduNetworkSecuritySnmp | 1.3.6.1.4.1.42610.1.4.4.1.2.2.3 | |||
| INT pduNetworkSecuritySnmpControl | 1.3.6.1.4.1.42610.1.4.4.1.2.2.3.1 | INTEGER | read-write | Enable/disable SNMP Access Protection |
| INT pduNetworkSecuritySnmpInterval | 1.3.6.1.4.1.42610.1.4.4.1.2.2.3.2 | INTEGER | read-write | Detecting Interval of SNMP Access Protection |
| INT pduNetworkSecuritySnmpFailTimes | 1.3.6.1.4.1.42610.1.4.4.1.2.2.3.3 | INTEGER | read-write | Unsuccessful attempts of SNMP Access Protection |
| INT pduNetworkSecuritySnmpBlock | 1.3.6.1.4.1.42610.1.4.4.1.2.2.3.4 | INTEGER | read-write | Block Time of SNMP Access Protection |
| pduNetworkSecurityHttp | 1.3.6.1.4.1.42610.1.4.4.1.2.2.4 | |||
| INT pduNetworkSecurityHttpControl | 1.3.6.1.4.1.42610.1.4.4.1.2.2.4.1 | INTEGER | read-write | Enable/disable HTTP Access Protection |
| INT pduNetworkSecurityHttpInterval | 1.3.6.1.4.1.42610.1.4.4.1.2.2.4.2 | INTEGER | read-write | Detecting Interval of HTTP Access Protection |
| INT pduNetworkSecurityHttpFailTimes | 1.3.6.1.4.1.42610.1.4.4.1.2.2.4.3 | INTEGER | read-write | Unsuccessful attempts of HTTP Access Protection |
| INT pduNetworkSecurityHttpBlock | 1.3.6.1.4.1.42610.1.4.4.1.2.2.4.4 | INTEGER | read-write | Block Time of HTTP Access Protection |
| pduNetworkService | 1.3.6.1.4.1.42610.1.4.4.1.2.3 | |||
| pduNetworkServiceSsh | 1.3.6.1.4.1.42610.1.4.4.1.2.3.1 | |||
| INT pduNetworkServiceSshControl | 1.3.6.1.4.1.42610.1.4.4.1.2.3.1.1 | INTEGER | read-write | Enable/disable SSH Server Service |
| INT pduNetworkServiceSshPort | 1.3.6.1.4.1.42610.1.4.4.1.2.3.1.2 | INTEGER | read-write | The Port Number of SSH Server Service |
| pduNetworkServiceSsl | 1.3.6.1.4.1.42610.1.4.4.1.2.3.2 | |||
| INT pduNetworkServiceSslControl | 1.3.6.1.4.1.42610.1.4.4.1.2.3.2.1 | INTEGER | read-write | Enable/disable HTTPs Server Service |
| INT pduNetworkServiceSslPort | 1.3.6.1.4.1.42610.1.4.4.1.2.3.2.2 | INTEGER | read-write | The Port Number of HTTPs Server Service |
| INT pduNetworkServiceSslForce | 1.3.6.1.4.1.42610.1.4.4.1.2.3.2.3 | INTEGER | read-write | Force use HTTPs Server Service only. |
| INT pduNetworkServicePingControl | 1.3.6.1.4.1.42610.1.4.4.1.2.3.3 | INTEGER | read-write | Enable/disable to response to PING request. |
| pduNetworkServiceRadius | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4 | |||
| INT pduNetworkServiceRadiusControl | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4.1 | INTEGER | read-write | Enable/disable RADIUS Client Service |
| STR pduNetworkServiceRadiusIp | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4.2 | DisplayString | read-write | The IP Address of RADIUS Client Service |
| INT pduNetworkServiceRadiusPort | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4.3 | INTEGER | read-write | The Port Number of RADIUS Client Service |
| STR pduNetworkServiceRadiusSecretKey | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4.4 | DisplayString | read-write | The Secret Key of RADIUS Client Service |
| INT pduNetworkServiceRadiusTimeout | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4.5 | INTEGER | read-write | The Timeout Interval of RADIUS Client Service in seconds |
| INT pduNetworkServiceRadiusRetry | 1.3.6.1.4.1.42610.1.4.4.1.2.3.4.6 | INTEGER | read-write | The Retry Times of RADIUS Client Service |
| pduSystem | 1.3.6.1.4.1.42610.1.4.4.1.3 | |||
| STR pduSystemName | 1.3.6.1.4.1.42610.1.4.4.1.3.1 | DisplayString | read-write | The name of system. |
| STR pduSystemContact | 1.3.6.1.4.1.42610.1.4.4.1.3.2 | DisplayString | read-write | The contact of system. |
| STR pduSystemLocation | 1.3.6.1.4.1.42610.1.4.4.1.3.3 | DisplayString | read-write | The location of system. |
| INT pduSystemLogInterval | 1.3.6.1.4.1.42610.1.4.4.1.3.4 | INTEGER | read-write | The Log Interval of device |
| INT pduSystemWebRefresh | 1.3.6.1.4.1.42610.1.4.4.1.3.5 | INTEGER | read-write | The Web Refresh Interval of device |
| pduSystemTime | 1.3.6.1.4.1.42610.1.4.4.1.3.6 | |||
| STR pduSystemTimeDisplay | 1.3.6.1.4.1.42610.1.4.4.1.3.6.1 | DisplayString | read-only | The date/time in agent |
| INT pduSystemTimeZone | 1.3.6.1.4.1.42610.1.4.4.1.3.6.2 | INTEGER | read-write | Time Zone to use when synchronize with NTP server. |
| INT pduSystemTimeFormat | 1.3.6.1.4.1.42610.1.4.4.1.3.6.3 | INTEGER | read-write | Date Format |
| INT pduSystemTimeSetting | 1.3.6.1.4.1.42610.1.4.4.1.3.6.4 | INTEGER | read-write | Time Setting |
| INT pduSystemTimeDayLightSaving | 1.3.6.1.4.1.42610.1.4.4.1.3.6.5 | INTEGER | read-write | Enable/disable the Day Light Saving when synchronize with NTP server. |
| pduSystemTimeManual | 1.3.6.1.4.1.42610.1.4.4.1.3.6.6 | |||
| STR pduSystemTimeManualDate | 1.3.6.1.4.1.42610.1.4.4.1.3.6.6.1 | DisplayString | read-write | The date in agent, format is (dd/mm/yyyy) |
| STR pduSystemTimeManualTime | 1.3.6.1.4.1.42610.1.4.4.1.3.6.6.2 | DisplayString | read-write | The time in agent, format is (hh:mm:ss) |
| pduSystemTimeNtp | 1.3.6.1.4.1.42610.1.4.4.1.3.6.7 | |||
| INT pduSystemTimeNtpControl | 1.3.6.1.4.1.42610.1.4.4.1.3.6.7.1 | INTEGER | read-write | Enable or disable the agent to synchronize date/time with NTP server. |
| STR pduSystemTimeNtpServer | 1.3.6.1.4.1.42610.1.4.4.1.3.6.7.2 | DisplayString | read-write | The ip address of NTP server. |
| INT pduSystemTimeNtpSyncInterval | 1.3.6.1.4.1.42610.1.4.4.1.3.6.7.3 | INTEGER | read-write | The Sync Interval with NTP server. |
| INT pduSystemTimeNtpSyncUnit | 1.3.6.1.4.1.42610.1.4.4.1.3.6.7.4 | INTEGER | read-write | The Unit of Sync Interval |
| INT pduSystemResetToDefault | 1.3.6.1.4.1.42610.1.4.4.1.3.7 | INTEGER | read-write | Reset the parameter of PDU to default. |
| INT pduSystemReboot | 1.3.6.1.4.1.42610.1.4.4.1.3.8 | INTEGER | read-write | Reboot the system of PDU. |
| pduSNMP | 1.3.6.1.4.1.42610.1.4.4.1.4 | |||
| INT pduSnmpControl | 1.3.6.1.4.1.42610.1.4.4.1.4.1 | INTEGER | read-write | Enable/disable SNMP protocol. |
| INT pduSnmpPort | 1.3.6.1.4.1.42610.1.4.4.1.4.2 | INTEGER | read-write | The UDP port for SNMP. |
| INT pduSnmpVersion | 1.3.6.1.4.1.42610.1.4.4.1.4.3 | INTEGER | read-write | Set SNMP version. |
| pduSnmpTrapsReceiversTable | 1.3.6.1.4.1.42610.1.4.4.1.4.4 | not-accessible | A list of managers to send traps to. The number of entries is given by the value of pduSnmpNumTrapReceivers | |
| pduSnmpTrapsReceiversEntry | 1.3.6.1.4.1.42610.1.4.4.1.4.4.1 | not-accessible | The managers to send traps to. | |
| INT trapsIndex | 1.3.6.1.4.1.42610.1.4.4.1.4.4.1.1 | INTEGER | read-only | The index to a trap receiver entry. |
| STR trapsReceiverAddr | 1.3.6.1.4.1.42610.1.4.4.1.4.4.1.2 | DisplayString | read-write | The IP address of the manager to send a trap to. |
| INT receiverEventLevel | 1.3.6.1.4.1.42610.1.4.4.1.4.4.1.3 | INTEGER | read-write | The severity level of traps to be received by this manager. |
| INT receiverSnmpVer | 1.3.6.1.4.1.42610.1.4.4.1.4.4.1.4 | INTEGER | read-write | The SNMP Trap version of trap receivers. |
| STR receiverDescription | 1.3.6.1.4.1.42610.1.4.4.1.4.4.1.5 | DisplayString | read-write | Description of trap receivers |
| pduEmail | 1.3.6.1.4.1.42610.1.4.4.1.5 | |||
| STR pduEmailServer | 1.3.6.1.4.1.42610.1.4.4.1.5.1 | DisplayString | read-write | The address of Email server. |
| INT pduEmailPort | 1.3.6.1.4.1.42610.1.4.4.1.5.2 | INTEGER | read-write | The UDP port for Email Server. |
| STR pduEmailSenderEmail | 1.3.6.1.4.1.42610.1.4.4.1.5.3 | DisplayString | read-write | The sender's Email address |
| STR pduEmailPrefix | 1.3.6.1.4.1.42610.1.4.4.1.5.4 | DisplayString | read-write | The prefix string of mail subject |
| INT pduEmailAuthControl | 1.3.6.1.4.1.42610.1.4.4.1.5.5 | INTEGER | read-write | Enable/disable SMTP Authentication. |
| STR pduEmailAuthUsername | 1.3.6.1.4.1.42610.1.4.4.1.5.6 | DisplayString | read-write | The user name of SMTP Authentication |
| STR pduEmailAuthPassword | 1.3.6.1.4.1.42610.1.4.4.1.5.7 | DisplayString | read-write | The password of SMTP Authentication |
| pduEmailReceiversTable | 1.3.6.1.4.1.42610.1.4.4.1.5.8 | not-accessible | A list of managers to send email notification to. | |
| pduEmailReceiversEntry | 1.3.6.1.4.1.42610.1.4.4.1.5.8.1 | not-accessible | The managers to send email notification to. | |
| INT mailRecvIndex | 1.3.6.1.4.1.42610.1.4.4.1.5.8.1.1 | INTEGER | read-only | The index to a email notification receiver entry. |
| STR mailRecvReceiverAddr | 1.3.6.1.4.1.42610.1.4.4.1.5.8.1.2 | DisplayString | read-write | The Email address of the manager to send a email notification to. |
| INT mailRecvEmailType | 1.3.6.1.4.1.42610.1.4.4.1.5.8.1.3 | INTEGER | read-write | The Email Type of email notification receivers. |
| INT mailRecvEventLevel | 1.3.6.1.4.1.42610.1.4.4.1.5.8.1.4 | INTEGER | read-write | The severity level of email notification to be received by this manager. |
| STR mailRecvDescription | 1.3.6.1.4.1.42610.1.4.4.1.5.8.1.5 | DisplayString | read-write | Description of email notification receivers |
| pduPwrMonitoring | 1.3.6.1.4.1.42610.1.4.4.1.6 | |||
| pduPwrMonitoringInlet | 1.3.6.1.4.1.42610.1.4.4.1.6.1 | |||
| INT pduPwrMonitoringInletNum | 1.3.6.1.4.1.42610.1.4.4.1.6.1.1 | INTEGER | read-only | The number of Inlet. |
| pduPwrMonitoringInletStatusTable | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2 | not-accessible | A list to display status of Inlet. | |
| pduPwrMonitoringInletStatusEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1 | not-accessible | A list to display status of Inlet. | |
| INT inletIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.1 | INTEGER | read-only | The index to Inlet status entry. |
| INT inletPowerAll | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.2 | INTEGER | read-only | The total power of inlet. |
| STR inletResetFrom | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.3 | DisplayString | read-only | The reset date of inlet. |
| INT inletEnergy | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.4 | INTEGER | read-only | The total energy of inlet. |
| INT inletStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.5 | INTEGER | read-only | The Status of inlet. |
| INT inletCurrPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.6 | INTEGER | read-only | The phase1 current of inlet. |
| INT inletCurrPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.7 | INTEGER | read-only | The phase2 current of inlet. |
| INT inletCurrPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.8 | INTEGER | read-only | The phase3 current of inlet. |
| INT inletVoltPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.9 | INTEGER | read-only | The phase1 voltage of inlet. |
| INT inletVoltPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.10 | INTEGER | read-only | The phase2 voltage of inlet. |
| INT inletVoltPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.11 | INTEGER | read-only | The phase3 voltage of inlet. |
| INT inletPwrFactorPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.12 | INTEGER | read-only | The phase1 power factor of inlet. |
| INT inletPwrFactorPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.13 | INTEGER | read-only | The phase2 power factor of inlet. |
| INT inletPwrFactorPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.14 | INTEGER | read-only | The phase3 power factor of inlet. |
| INT inletPowerPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.15 | INTEGER | read-only | The phase1 power of inlet. |
| INT inletPowerPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.16 | INTEGER | read-only | The phase2 power of inlet. |
| INT inletPowerPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.17 | INTEGER | read-only | The phase3 power of inlet. |
| INT inletStatusPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.18 | INTEGER | read-only | The phase1 status of inlet. |
| INT inletStatusPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.19 | INTEGER | read-only | The phase2 status of inlet. |
| INT inletStatusPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.2.1.20 | INTEGER | read-only | The phase3 status of inlet. |
| pduPwrMonitoringInletCfgTable | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3 | not-accessible | A list to configure thresholds of inlet. | |
| pduPwrMonitoringInletCfgEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1 | not-accessible | A list to configure thresholds of inlet. | |
| INT inletCfgIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.1 | INTEGER | read-only | The index to inlet configuration entry. |
| INT inletCfgLoadCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.2 | INTEGER | read-write | The Critical Threshold of inlet load. |
| INT inletCfgLoadWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.3 | INTEGER | read-write | The Warning Threshold of inlet load. |
| INT inletCfgCurrCritPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.4 | INTEGER | read-write | The Critical Threshold of pahse1 current of inlet. |
| INT inletCfgCurrCritPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.5 | INTEGER | read-write | The Critical Threshold of pahse2 current of inlet. |
| INT inletCfgCurrCritPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.6 | INTEGER | read-write | The Critical Threshold of pahse3 current of inlet. |
| INT inletCfgCurrWarnPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.7 | INTEGER | read-write | The Warning Threshold of pahse1 current of inlet. |
| INT inletCfgCurrWarnPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.8 | INTEGER | read-write | The Warning Threshold of pahse2 current of inlet. |
| INT inletCfgCurrWarnPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.9 | INTEGER | read-write | The Warning Threshold of pahse3 current of inlet. |
| INT inletCfgVoltCritPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.10 | INTEGER | read-write | The Critical Threshold of pahse1 voltage of inlet. |
| INT inletCfgVoltCritPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.11 | INTEGER | read-write | The Critical Threshold of pahse2 voltage of inlet. |
| INT inletCfgVoltCritPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.12 | INTEGER | read-write | The Critical Threshold of pahse3 voltage of inlet. |
| INT inletCfgVoltWarnPhase1 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.13 | INTEGER | read-write | The Warning Threshold of pahse1 voltage of inlet. |
| INT inletCfgVoltWarnPhase2 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.14 | INTEGER | read-write | The Warning Threshold of pahse2 voltage of inlet. |
| INT inletCfgVoltWarnPhase3 | 1.3.6.1.4.1.42610.1.4.4.1.6.1.3.1.15 | INTEGER | read-write | The Warning Threshold of pahse3 voltage of inlet. |
| pduPwrMonitoringOutlet | 1.3.6.1.4.1.42610.1.4.4.1.6.2 | |||
| pduPwrMonitoringOutletPduA | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1 | |||
| INT pduPwrMonitoringOutletNumPduA | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.1 | INTEGER | read-only | The number of PduA Outlet. |
| pduPwrMonitoringOutletStatusTablePduA | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2 | not-accessible | A list to display status of PduA outlet. | |
| pduPwrMonitoringOutletStatusPduAEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1 | not-accessible | A list to display status of PduA outlet. | |
| INT outletPduAIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.1 | INTEGER | read-only | The index to outlet status of PduA. |
| INT outletPduAState | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.2 | INTEGER | read-only | The state of PduA outlet. |
| INT outletPduACurrent | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.3 | INTEGER | read-only | The current of PduA outlet. |
| INT outletPduAPwrFactor | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.4 | INTEGER | read-only | The power factor of PduA outlet. |
| INT outletPduAPower | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.5 | INTEGER | read-only | The power of PduA outlet. |
| INT outletPduAEnergy | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.6 | INTEGER | read-only | The energy of PduA outlet. |
| STR outletPduAResetFrom | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.7 | DisplayString | read-only | The reset date of PduA outlet. |
| INT outletPduAStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.2.1.8 | INTEGER | read-only | The status of PduA outlet. |
| pduPwrMonitoringOutletCfgTablePduA | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3 | not-accessible | A list to display configuration of PduA outlet. | |
| pduPwrMonitoringOutletCfgPduAEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1 | not-accessible | A list to display configuration of PduA outlet. | |
| INT outletCfgPduAIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.1 | INTEGER | read-only | The index to outlet configuration of PduA. |
| STR outletCfgPduAName | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.2 | DisplayString | read-write | The name for outlet of PduA. |
| INT outletCfgPduADelayOnStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.3 | INTEGER | read-write | The Delay On status of PduA outlet. |
| INT outletCfgPduADelayOnTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.4 | INTEGER | read-write | The Delay On time of PduA outlet. |
| INT outletCfgPduADelayOffStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.5 | INTEGER | read-write | The Delay Off status of PduA outlet. |
| INT outletCfgPduADelayOffTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.6 | INTEGER | read-write | The Delay Off time of PduA outlet. |
| INT outletCfgPduAReboot | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.7 | INTEGER | read-write | The Delay On reboot duration of PduA outlet. |
| INT outletCfgPduAOverCurrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.8 | INTEGER | read-write | The Critical Threshold of current of PduA outlet. |
| INT outletCfgPduAOverCurrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.9 | INTEGER | read-write | The Warning Threshold of current of PduA outlet. |
| INT outletCfgPduAOverPwrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.10 | INTEGER | read-write | The Critical Threshold of power of PduA outlet. |
| INT outletCfgPduAOverPwrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.3.1.11 | INTEGER | read-write | The Warning Threshold of power of PduA outlet. |
| pduPwrMonitoringOutletCtlTablePduA | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4 | not-accessible | A list to display control of PduA outlet. | |
| pduPwrMonitoringOutletCtlPduAEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4.1 | not-accessible | A list to display control of PduA outlet. | |
| INT outletCtlPduAIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4.1.1 | INTEGER | read-only | The index to outlet control of PduA. |
| INT outletCtlPduAControl | 1.3.6.1.4.1.42610.1.4.4.1.6.2.1.4.1.2 | INTEGER | read-write | The control-type of PduA outlet. |
| pduPwrMonitoringOutletPduB | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2 | |||
| INT pduPwrMonitoringOutletNumPduB | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.1 | INTEGER | read-only | The number of PduB Outlet. |
| pduPwrMonitoringOutletStatusTablePduB | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2 | not-accessible | A list to display status of PduB outlet. | |
| pduPwrMonitoringOutletStatusPduBEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1 | not-accessible | A list to display status of PduB outlet. | |
| INT outletPduBIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.1 | INTEGER | read-only | The index to outlet status of PduB. |
| INT outletPduBState | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.2 | INTEGER | read-only | The state of PduB outlet. |
| INT outletPduBCurrent | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.3 | INTEGER | read-only | The current of PduB outlet. |
| INT outletPduBPwrFactor | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.4 | INTEGER | read-only | The power factor of PduB outlet. |
| INT outletPduBPower | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.5 | INTEGER | read-only | The power of PduB outlet. |
| INT outletPduBEnergy | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.6 | INTEGER | read-only | The energy of PduB outlet. |
| STR outletPduBResetFrom | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.7 | DisplayString | read-only | The reset date of PduB outlet. |
| INT outletPduBStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.2.1.8 | INTEGER | read-only | The status of PduB outlet. |
| pduPwrMonitoringOutletCfgTablePduB | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3 | not-accessible | A list to display configuration of PduB outlet. | |
| pduPwrMonitoringOutletCfgPduBEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1 | not-accessible | A list to display configuration of PduB outlet. | |
| INT outletCfgPduBIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.1 | INTEGER | read-only | The index to outlet configuration of PduB. |
| STR outletCfgPduBName | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.2 | DisplayString | read-write | The name for outlet of PduB. |
| INT outletCfgPduBDelayOnStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.3 | INTEGER | read-write | The Delay On status of PduB outlet. |
| INT outletCfgPduBDelayOnTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.4 | INTEGER | read-write | The Delay On time of PduB outlet. |
| INT outletCfgPduBDelayOffStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.5 | INTEGER | read-write | The Delay Off status of PduB outlet. |
| INT outletCfgPduBDelayOffTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.6 | INTEGER | read-write | The Delay Off time of PduB outlet. |
| INT outletCfgPduBReboot | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.7 | INTEGER | read-write | The Delay On reboot duration of PduB outlet. |
| INT outletCfgPduBOverCurrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.8 | INTEGER | read-write | The Critical Threshold of current of PduB outlet. |
| INT outletCfgPduBOverCurrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.9 | INTEGER | read-write | The Warning Threshold of current of PduB outlet. |
| INT outletCfgPduBOverPwrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.10 | INTEGER | read-write | The Critical Threshold of power of PduB outlet. |
| INT outletCfgPduBOverPwrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.3.1.11 | INTEGER | read-write | The Warning Threshold of power of PduB outlet. |
| pduPwrMonitoringOutletCtlTablePduB | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4 | not-accessible | A list to display control of PduB outlet. | |
| pduPwrMonitoringOutletCtlPduBEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4.1 | not-accessible | A list to display control of PduB outlet. | |
| INT outletCtlPduBIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4.1.1 | INTEGER | read-only | The index to outlet control of PduB. |
| INT outletCtlPduBControl | 1.3.6.1.4.1.42610.1.4.4.1.6.2.2.4.1.2 | INTEGER | read-write | The control-type of PduB outlet. |
| pduPwrMonitoringOutletPduC | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3 | |||
| INT pduPwrMonitoringOutletNumPduC | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.1 | INTEGER | read-only | The number of PduC Outlet. |
| pduPwrMonitoringOutletStatusTablePduC | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2 | not-accessible | A list to display status of PduC outlet. | |
| pduPwrMonitoringOutletStatusPduCEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1 | not-accessible | A list to display status of PduC outlet. | |
| INT outletPduCIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.1 | INTEGER | read-only | The index to outlet status of PduC. |
| INT outletPduCState | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.2 | INTEGER | read-only | The state of PduC outlet. |
| INT outletPduCCurrent | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.3 | INTEGER | read-only | The current of PduC outlet. |
| INT outletPduCPwrFactor | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.4 | INTEGER | read-only | The power factor of PduC outlet. |
| INT outletPduCPower | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.5 | INTEGER | read-only | The power of PduC outlet. |
| INT outletPduCEnergy | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.6 | INTEGER | read-only | The energy of PduC outlet. |
| STR outletPduCResetFrom | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.7 | DisplayString | read-only | The reset date of PduC outlet. |
| INT outletPduCStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.8 | INTEGER | read-only | The status of PduC outlet. |
| pduPwrMonitoringOutletCfgTablePduC | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3 | not-accessible | A list to display configuration of PduC outlet. | |
| pduPwrMonitoringOutletCfgPduCEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1 | not-accessible | A list to display configuration of PduC outlet. | |
| INT outletCfgPduCIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.1 | INTEGER | read-only | The index to outlet configuration of PduC. |
| STR outletCfgPduCName | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.2 | DisplayString | read-write | The name for outlet of PduC. |
| INT outletCfgPduCDelayOnStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.3 | INTEGER | read-write | The Delay On status of PduC outlet. |
| INT outletCfgPduCDelayOnTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.4 | INTEGER | read-write | The Delay On time of PduC outlet. |
| INT outletCfgPduCDelayOffStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.5 | INTEGER | read-write | The Delay Off status of PduC outlet. |
| INT outletCfgPduCDelayOffTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.6 | INTEGER | read-write | The Delay Off time of PduC outlet. |
| INT outletCfgPduCReboot | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.7 | INTEGER | read-write | The Delay On reboot duration of PduC outlet. |
| INT outletCfgPduCOverCurrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.8 | INTEGER | read-write | The Critical Threshold of current of PduC outlet. |
| INT outletCfgPduCOverCurrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.9 | INTEGER | read-write | The Warning Threshold of current of PduC outlet. |
| INT outletCfgPduCOverPwrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.10 | INTEGER | read-write | The Critical Threshold of power of PduC outlet. |
| INT outletCfgPduCOverPwrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.3.1.11 | INTEGER | read-write | The Warning Threshold of power of PduC outlet. |
| pduPwrMonitoringOutletCtlTablePduC | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4 | not-accessible | A list to display control of PduC outlet. | |
| pduPwrMonitoringOutletCtlPduCEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4.1 | not-accessible | A list to display control of PduC outlet. | |
| INT outletCtlPduCIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4.1.1 | INTEGER | read-only | The index to outlet control of PduC. |
| INT outletCtlPduCControl | 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.4.1.2 | INTEGER | read-write | The control-type of PduC outlet. |
| pduPwrMonitoringOutletPduD | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4 | |||
| INT pduPwrMonitoringOutletNumPduD | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.1 | INTEGER | read-only | The number of PduD Outlet. |
| pduPwrMonitoringOutletStatusTablePduD | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2 | not-accessible | A list to display status of PduD outlet. | |
| pduPwrMonitoringOutletStatusPduDEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1 | not-accessible | A list to display status of PduD outlet. | |
| INT outletPduDIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.1 | INTEGER | read-only | The index to outlet status of PduD. |
| INT outletPduDState | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.2 | INTEGER | read-only | The state of PduD outlet. |
| INT outletPduDCurrent | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.3 | INTEGER | read-only | The current of PduD outlet. |
| INT outletPduDPwrFactor | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.4 | INTEGER | read-only | The power factor of PduD outlet. |
| INT outletPduDPower | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.5 | INTEGER | read-only | The power of PduD outlet. |
| INT outletPduDEnergy | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.6 | INTEGER | read-only | The energy of PduD outlet. |
| STR outletPduDResetFrom | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.7 | DisplayString | read-only | The reset date of PduD outlet. |
| INT outletPduDStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.2.1.8 | INTEGER | read-only | The status of PduD outlet. |
| pduPwrMonitoringOutletCfgTablePduD | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3 | not-accessible | A list to display configuration of PduD outlet. | |
| pduPwrMonitoringOutletCfgPduDEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1 | not-accessible | A list to display configuration of PduD outlet. | |
| INT outletCfgPduDIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.1 | INTEGER | read-only | The index to outlet configuration of PduD. |
| STR outletCfgPduDName | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.2 | DisplayString | read-write | The name for outlet of PduD. |
| INT outletCfgPduDDelayOnStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.3 | INTEGER | read-write | The Delay On status of PduD outlet. |
| INT outletCfgPduDDelayOnTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.4 | INTEGER | read-write | The Delay On time of PduD outlet. |
| INT outletCfgPduDDelayOffStatus | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.5 | INTEGER | read-write | The Delay Off status of PduD outlet. |
| INT outletCfgPduDDelayOffTime | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.6 | INTEGER | read-write | The Delay Off time of PduD outlet. |
| INT outletCfgPduDReboot | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.7 | INTEGER | read-write | The Delay On reboot duration of PduD outlet. |
| INT outletCfgPduDOverCurrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.8 | INTEGER | read-write | The Critical Threshold of current of PduD outlet. |
| INT outletCfgPduDOverCurrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.9 | INTEGER | read-write | The Warning Threshold of current of PduD outlet. |
| INT outletCfgPduDOverPwrCritical | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.10 | INTEGER | read-write | The Critical Threshold of power of PduD outlet. |
| INT outletCfgPduDOverPwrWarning | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.3.1.11 | INTEGER | read-write | The Warning Threshold of power of PduD outlet. |
| pduPwrMonitoringOutletCtlTablePduD | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4 | not-accessible | A list to display control of PduD outlet. | |
| pduPwrMonitoringOutletCtlPduDEntry | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4.1 | not-accessible | A list to display control of PduD outlet. | |
| INT outletCtlPduDIndex | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4.1.1 | INTEGER | read-only | The index to outlet control of PduD. |
| INT outletCtlPduDControl | 1.3.6.1.4.1.42610.1.4.4.1.6.2.4.4.1.2 | INTEGER | read-write | The control-type of PduD outlet. |
| pduEnvMonitoring | 1.3.6.1.4.1.42610.1.4.4.1.7 | |||
| pduEnvMonitoringStatus | 1.3.6.1.4.1.42610.1.4.4.1.7.1 | |||
| INT pduEnvMonitoringTemp | 1.3.6.1.4.1.42610.1.4.4.1.7.1.1 | INTEGER | read-only | The temperature of EMD. |
| INT pduEnvMonitoringHumi | 1.3.6.1.4.1.42610.1.4.4.1.7.1.2 | INTEGER | read-only | The humidity of EMD. |
| INT pduEnvMonitoringTempAlarm | 1.3.6.1.4.1.42610.1.4.4.1.7.1.3 | INTEGER | read-only | The temperature status of EMD. |
| INT pduEnvMonitoringHumiAlarm | 1.3.6.1.4.1.42610.1.4.4.1.7.1.4 | INTEGER | read-only | The humidity status of EMD. |
| pduEnvMonitoringCfg | 1.3.6.1.4.1.42610.1.4.4.1.7.2 | |||
| INT pduEnvMonitoringControl | 1.3.6.1.4.1.42610.1.4.4.1.7.2.1 | INTEGER | read-write | Enable/disable the EMD. |
| INT pduEnvMonitoringTempHighCritical | 1.3.6.1.4.1.42610.1.4.4.1.7.2.2 | INTEGER | read-write | The High Critical Threshold of temperature of EMD. |
| INT pduEnvMonitoringTempHighWarning | 1.3.6.1.4.1.42610.1.4.4.1.7.2.3 | INTEGER | read-write | The High Warning Threshold of temperature of EMD. |
| INT pduEnvMonitoringTempLowCritical | 1.3.6.1.4.1.42610.1.4.4.1.7.2.4 | INTEGER | read-write | The Low Critical Threshold of temperature of EMD. |
| INT pduEnvMonitoringTempLowWarning | 1.3.6.1.4.1.42610.1.4.4.1.7.2.5 | INTEGER | read-write | The Low Warning Threshold of temperature of EMD. |
| INT pduEnvMonitoringTempHystersis | 1.3.6.1.4.1.42610.1.4.4.1.7.2.6 | INTEGER | read-write | The Hystersis of Temperature of EMD. |
| INT pduEnvMonitoringTempOffset | 1.3.6.1.4.1.42610.1.4.4.1.7.2.7 | INTEGER | read-write | The Offset of Temperature of EMD. |
| INT pduEnvMonitoringHumiHighCritical | 1.3.6.1.4.1.42610.1.4.4.1.7.2.8 | INTEGER | read-write | The High Crtitcal Threshold of humidity of EMD. |
| INT pduEnvMonitoringHumiHighWarning | 1.3.6.1.4.1.42610.1.4.4.1.7.2.9 | INTEGER | read-write | The High Warning Threshold of humidity of EMD. |
| INT pduEnvMonitoringHumiLowCritical | 1.3.6.1.4.1.42610.1.4.4.1.7.2.10 | INTEGER | read-write | The Low Crtitcal Threshold of humidity of EMD. |
| INT pduEnvMonitoringHumiLowWarning | 1.3.6.1.4.1.42610.1.4.4.1.7.2.11 | INTEGER | read-write | The Low Warning Threshold of humidity of EMD. |
| INT pduEnvMonitoringHumiHystersis | 1.3.6.1.4.1.42610.1.4.4.1.7.2.12 | INTEGER | read-write | The Hystersis of Humidity of EMD. |
| INT pduEnvMonitoringHumiOffset | 1.3.6.1.4.1.42610.1.4.4.1.7.2.13 | INTEGER | read-write | The Ofset of Humidity of EMD. |
| pduTraps | 1.3.6.1.4.1.42610.1.4.4.2 | |||
| NTF pduSystemColdBoot | 1.3.6.1.4.1.42610.1.4.4.2.0.1 | Informational: Cold boot. | ||
| NTF pduSystemWarmBoot | 1.3.6.1.4.1.42610.1.4.4.2.0.2 | Informational: Warm boot. | ||
| NTF pduSystemRestart | 1.3.6.1.4.1.42610.1.4.4.2.0.3 | Informational: System restart. | ||
| NTF pduResetToDefault | 1.3.6.1.4.1.42610.1.4.4.2.0.4 | Informational: Parameters reset to default. | ||
| NTF pduFirmUpgrade | 1.3.6.1.4.1.42610.1.4.4.2.0.5 | Informational: Firmware upgrade. | ||
| NTF pduSystemLogClear | 1.3.6.1.4.1.42610.1.4.4.2.0.6 | Informational: System log cleared. | ||
| NTF pduEventlogClear | 1.3.6.1.4.1.42610.1.4.4.2.0.7 | Informational: Event log cleared. | ||
| NTF pduInletHistoryClear | 1.3.6.1.4.1.42610.1.4.4.2.0.8 | Informational: Inlet history log cleared. | ||
| NTF pduOutletHistoryClear | 1.3.6.1.4.1.42610.1.4.4.2.0.9 | Informational: Outlet history log cleared. | ||
| NTF pduSystemTimeChangeUser | 1.3.6.1.4.1.42610.1.4.4.2.0.10 | Informational: Time changed by user. | ||
| NTF pduSystemTimeChangeNtp | 1.3.6.1.4.1.42610.1.4.4.2.0.11 | Informational: Time synced with NTP server. | ||
| NTF pduSystemTimeChangeRtc | 1.3.6.1.4.1.42610.1.4.4.2.0.12 | Informational: Time changed by RTC. | ||
| NTF pduMailTestPass | 1.3.6.1.4.1.42610.1.4.4.2.0.13 | Informational: Test mail pass. | ||
| NTF pduMailTestFail | 1.3.6.1.4.1.42610.1.4.4.2.0.14 | Informational: Test mail failed. | ||
| NTF pduMailSentPass | 1.3.6.1.4.1.42610.1.4.4.2.0.15 | Informational: Mail sent successfully. | ||
| NTF pduMailSentFail | 1.3.6.1.4.1.42610.1.4.4.2.0.16 | Informational: Mail sent failed. | ||
| NTF pduSystemCfgChange | 1.3.6.1.4.1.42610.1.4.4.2.0.17 | Informational: Parameter changed. | ||
| NTF pduSystemParamImport | 1.3.6.1.4.1.42610.1.4.4.2.0.18 | Informational: Import XML configuration. | ||
| NTF pduInletCommLost | 1.3.6.1.4.1.42610.1.4.4.2.0.19 | Informational: Inlet communication lost. | ||
| NTF pduInletCommRestore | 1.3.6.1.4.1.42610.1.4.4.2.0.20 | Informational: Inlet communication restore. | ||
| NTF pduOutletCommLost | 1.3.6.1.4.1.42610.1.4.4.2.0.21 | Informational: Outlet communication lost. | ||
| NTF pduOutletCommRestore | 1.3.6.1.4.1.42610.1.4.4.2.0.22 | Informational: Outlet communication restore | ||
| NTF pduOutletOnUser | 1.3.6.1.4.1.42610.1.4.4.2.0.23 | Informational: Outlet turned on by user. | ||
| NTF pduOutletOnSchedule | 1.3.6.1.4.1.42610.1.4.4.2.0.24 | Informational: Outlet turned on by schedule. | ||
| NTF pduOutletOffUser | 1.3.6.1.4.1.42610.1.4.4.2.0.25 | Informational: Outlet turned off by user. | ||
| NTF pduOutletOffSchedule | 1.3.6.1.4.1.42610.1.4.4.2.0.26 | Informational: Outlet turned off by schedule. | ||
| NTF pduOutletRebootUser | 1.3.6.1.4.1.42610.1.4.4.2.0.27 | Informational: Outlet reboot by user. | ||
| NTF pduOutletRebootSchedule | 1.3.6.1.4.1.42610.1.4.4.2.0.28 | Informational: Outlet reboot by schedule. | ||
| NTF pduInletEnergyReset | 1.3.6.1.4.1.42610.1.4.4.2.0.29 | Informational: Inlet energy reset. | ||
| NTF pduOutletEnergyReset | 1.3.6.1.4.1.42610.1.4.4.2.0.30 | Informational: Outlet energy reset. | ||
| NTF pduSetUser | 1.3.6.1.4.1.42610.1.4.4.2.0.31 | Informational: Assign outlet to user. | ||
| NTF pduDeletUser | 1.3.6.1.4.1.42610.1.4.4.2.0.32 | Informational: Delete user. | ||
| NTF pduUpgradeInletSuccess | 1.3.6.1.4.1.42610.1.4.4.2.0.33 | Informational: Inlet upgrade successfully. | ||
| NTF pduUpgradeInletFail | 1.3.6.1.4.1.42610.1.4.4.2.0.34 | Informational: Inlet upgrade fail. | ||
| NTF pduUpgradeOutletSuccess | 1.3.6.1.4.1.42610.1.4.4.2.0.35 | Informational: Outlet upgrade successfully. | ||
| NTF pduUpgradeOutletFail | 1.3.6.1.4.1.42610.1.4.4.2.0.36 | Informational: Outlet upgrade fail. | ||
| NTF pduEmdTempHighWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.101 | Informational: Temperature had returned from high warning to normal. | ||
| NTF pduEmdTempHighWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.102 | Warning: Temperature was higher than high warning set point. | ||
| NTF pduEmdTempLowWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.103 | Informational: Temperature had returned from low warning to normal. | ||
| NTF pduEmdTempLowWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.104 | Warning: Temperature was lower than low warning set point. | ||
| NTF pduEmdTempHighCritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.105 | Informational: Temperature had returned from high critical to high warning. | ||
| NTF pduEmdTempHighCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.106 | Critical: Temperature was higher than high critical set point. | ||
| NTF pduEmdTempLowCritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.107 | Informational: Temperature had returned from low critical to low warning. | ||
| NTF pduEmdTempLowCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.108 | Critical: Temperature was lower than low critical set point. | ||
| NTF pduEmdHumiHighWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.109 | Informational: Humidity had returned from high warning to normal. | ||
| NTF pduEmdHumiHighWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.110 | Warning: Humidity was higher than high warning set point. | ||
| NTF pduEmdHumiLowWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.111 | Informational: Humidity had returned from low warning to normal. | ||
| NTF pduEmdHumiLowWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.112 | Warning: Humidity was lower than low warning set point. | ||
| NTF pduEmdHumiHighCritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.113 | Informational: Humidity had returned from high critical to high warning. | ||
| NTF pduEmdHumiHighCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.114 | Critical: Humidity was higher than high critical set point. | ||
| NTF pduEmdHumiLowCritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.115 | Informational: Humidity had returned from low critical to low warning. | ||
| NTF pduEmdHumiLowCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.116 | Critical: Humidity was lower than low critical set point. | ||
| NTF pduEmdAlarm1NotActive | 1.3.6.1.4.1.42610.1.4.4.2.0.117 | Informational: Alarm-1 became inactive. | ||
| NTF pduEmdAlarm1Active | 1.3.6.1.4.1.42610.1.4.4.2.0.118 | Warning: Alarm-1 became active. | ||
| NTF pduEmdAlarm2NotActive | 1.3.6.1.4.1.42610.1.4.4.2.0.119 | Informational: Alarm-2 became inactive. | ||
| NTF pduEmdAlarm2Active | 1.3.6.1.4.1.42610.1.4.4.2.0.120 | Warning: Alarm-2 became active. | ||
| NTF pduRs485Online | 1.3.6.1.4.1.42610.1.4.4.2.0.121 | Informational: RS485 Sensor was online. | ||
| NTF pduRs485Offline | 1.3.6.1.4.1.42610.1.4.4.2.0.122 | Warning: RS485 Sensor was offline. | ||
| NTF pduInletLoadCritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.123 | Informational: Inlet load had returned from critical to warning. | ||
| NTF pduInletLoadCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.124 | Critical: Inlet load was higher than critical set point. | ||
| NTF pduInletLoadWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.125 | Informational: Inlet load had returned from warning to normal. | ||
| NTF pduInletLoadWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.126 | Warning: Inlet load was higher than warning set point. | ||
| NTF pduInletCurrPhase1CritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.127 | Informational: Inlet phase1 current had returned from critical to warning. | ||
| NTF pduInletCurrPhase1Critical | 1.3.6.1.4.1.42610.1.4.4.2.0.128 | Critical: Inlet phase1 current was higher than critical set point. | ||
| NTF pduInletCurrPhase1WarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.129 | Informational: Inlet phase1 current had returned from warning to normal. | ||
| NTF pduInletCurrPhase1Warn | 1.3.6.1.4.1.42610.1.4.4.2.0.130 | Warning: Inlet phase1 current was higher than warning set point. | ||
| NTF pduInletCurrPhase2CritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.131 | Informational: Inlet phase2 current had returned from critical to warning. | ||
| NTF pduInletCurrPhase2Critical | 1.3.6.1.4.1.42610.1.4.4.2.0.132 | Critical: Inlet phase2 current was higher than critical set point. | ||
| NTF pduInletCurrPhase2WarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.133 | Informational: Inlet phase2 current had returned from warning to normal. | ||
| NTF pduInletCurrPhase2Warn | 1.3.6.1.4.1.42610.1.4.4.2.0.134 | Warning: Inlet phase2 current was higher than warning set point. | ||
| NTF pduInletCurrPhase3CritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.135 | Informational: Inlet phase3 current had returned from critical to warning. | ||
| NTF pduInletCurrPhase3Critical | 1.3.6.1.4.1.42610.1.4.4.2.0.136 | Critical: Inlet phase3 current was higher than critical set point. | ||
| NTF pduInletCurrPhase3WarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.137 | Informational: Inlet phase3 current had returned from warning to normal. | ||
| NTF pduInletCurrPhase3Warn | 1.3.6.1.4.1.42610.1.4.4.2.0.138 | Warning: Inlet phase3 current had returned from critical to warning. | ||
| NTF pduInletVoltPhase1CritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.139 | Informational: Inlet phase1 voltage had returned from critical to warning. | ||
| NTF pduInletVoltPhase1Critical | 1.3.6.1.4.1.42610.1.4.4.2.0.140 | Critical: Inlet phase1 voltage was higher than critical set point. | ||
| NTF pduInletVoltPhase1WarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.141 | Informational: Inlet phase1 voltage had returned from warning to normal. | ||
| NTF pduInletVoltPhase1Warn | 1.3.6.1.4.1.42610.1.4.4.2.0.142 | Warning: Inlet phase1 voltage was higher than warning set point. | ||
| NTF pduInletVoltPhase2CritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.143 | Informational: Inlet phase2 voltage had returned from critical to warning. | ||
| NTF pduInletVoltPhase2Critical | 1.3.6.1.4.1.42610.1.4.4.2.0.144 | Critical: Inlet phase2 voltage was higher than critical set point. | ||
| NTF pduInletVoltPhase2WarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.145 | Informational: Inlet phase2 voltage had returned from warning to normal. | ||
| NTF pduInletVoltPhase2Warn | 1.3.6.1.4.1.42610.1.4.4.2.0.146 | Warning: Inlet phase2 voltage was higher than warning set point. | ||
| NTF pduInletVoltPhase3CritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.147 | Informational: Inlet phase3 voltage had returned from critical to warning. | ||
| NTF pduInletVoltPhase3Critical | 1.3.6.1.4.1.42610.1.4.4.2.0.148 | Critical: Inlet phase3 voltage was higher than critical set point. | ||
| NTF pduInletVoltPhase3WarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.149 | Informational: Inlet phase3 voltage had returned from warning to normal. | ||
| NTF pduInletVoltPhase3Warn | 1.3.6.1.4.1.42610.1.4.4.2.0.150 | Warning: Inlet phase3 voltage was higher than warning set point. | ||
| NTF pduOutletCurrCritToWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.151 | Informational: Outlet current had returned from critical to warning. | ||
| NTF pduOutletCurrCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.152 | Critical: Outlet current was higher than critical set point. | ||
| NTF pduOutletCurrWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.153 | Informational: Outlet current had returned from warning to normal. | ||
| NTF pduOutletCurrWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.154 | Warning: Outlet current was higher than warning set point. | ||
| NTF pduOutletPwrCritTOWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.155 | Informational: Outlet power had returned from critical to warning. | ||
| NTF pduOutletPwrCritical | 1.3.6.1.4.1.42610.1.4.4.2.0.156 | Critical: Outlet power was higher than critical set point. | ||
| NTF pduOutletPwrWarnToNormal | 1.3.6.1.4.1.42610.1.4.4.2.0.157 | Informational: Outlet power had returned from warning to normal. | ||
| NTF pduOutletPwrWarn | 1.3.6.1.4.1.42610.1.4.4.2.0.158 | Warning: Outlet power was higher than warning set point. | ||
| NTF pduAlarm1Disabled | 1.3.6.1.4.1.42610.1.4.4.2.0.159 | Informational: Alarm-1 became disabled. | ||
| NTF pduAlarm2Disabled | 1.3.6.1.4.1.42610.1.4.4.2.0.160 | Informational: Alarm-2 became disabled. |
RFC description
Monitors system identification, network, power, environment, and SNMP configuration of Powertek single-phase PDU.
Start monitoring Powertek/SPS-series rack PDU (firmware version/network configuration status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.