SPSv1-MIB :: outletPduCPower

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › SPSv1-MIB › outletPduCPower

outletPduCPower

Module: SPSv1-MIB

OID (symbolic): SPSv1-MIB::outletPduCPower

OID (numeric): 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.5

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The power of PduC outlet.

What is outletPduCPower?

This read-only integer, in units of 0.1W, reports the real power draw of a specific PduC outlet, the C-bank counterpart to outletPduAPower/outletPduBPower.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.5
snmpwalk -v2c -c public <target> SPSv1-MIB::outletPduCPower

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.5.1
snmpget -v2c -c public <target> SPSv1-MIB::outletPduCPower.1

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> outletPduCPower.1

Start monitoring Powertek/SPS-series rack PDU (firmware version/network configuration status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SPSv1-MIB::outletPduCPower OID value, configure state conditions and alerts, and monitor any Powertek/SPS-series rack PDU (firmware version/network configuration status) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.42610powertekSPSv1-MIB
1.3.6.1.4.1.42610.1productSPSv1-MIB
1.3.6.1.4.1.42610.1.4pduSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4spsSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1pduObjectsSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1.6pduPwrMonitoringSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1.6.2pduPwrMonitoringOutletSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1.6.2.3pduPwrMonitoringOutletPduCSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2pduPwrMonitoringOutletStatusTablePduCSPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1pduPwrMonitoringOutletStatusPduCEntrySPSv1-MIB
1.3.6.1.4.1.42610.1.4.4.1.6.2.3.2.1.5outletPduCPowerSPSv1-MIB