All MIBs › RLE-FALCON-MIB
Category: Environmental Monitoring
Description: Manages RLE Technologies Falcon environmental monitor for temperature, humidity, and power status.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is RLE-FALCON-MIB?
RLE-FALCON-MIB is a vendor MIB from RLE Technologies for the Falcon series environmental monitoring unit, commonly deployed in data centers and telecom facilities to watch conditions inside equipment rooms and cabinets. It exposes identity information (manufacturer, model, software version), device clock settings, door alarm/bypass status, and keypad access codes/names used for physical security control. Its primary monitoring value is hardware/environmental status such as temperature, humidity, and power conditions reported by attached sensors, along with door alarm states that flag unauthorized physical access. It is a self-contained enterprise MIB with no strong dependency on other standard MIBs beyond generic SNMPv2-SMI conventions. It is typically deployed on Falcon environmental controller appliances mounted in server racks or telecom huts, usually after an administrator completes an RLE-FALCON-MIB download to load it into a MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in RLE-FALCON-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- RLE Technologies Falcon environmental monitoring unit
- data center/telecom rack environmental controllers
Monitoring Examples
An administrator would poll falconIdentModel and falconIdentSoftwareVersion to confirm the firmware level of a deployed Falcon unit, and monitor falconDoorAlarmBypass to detect whether a cabinet door sensor has been intentionally bypassed versus tripped unexpectedly. falconClock can be checked to ensure the unit's time source is synchronized for accurate alarm-event timestamping, while the falconKeypadCode/Name entries let an operator audit which access codes are assigned to which personnel for door entry.
What Can Be Monitored
- door alarm/bypass status
- keypad access codes and names
- device clock/time sync
- manufacturer/model identity
- software version
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Counter | |
| enterprises |
From RFC1213-MIB
| DisplayString |
From RFC1253-MIB
| PositiveInteger | |
| TruthValue |
From SNMPv2-SMI
| Gauge32 | |
| OBJECT-IDENTITY |
How to Use in IPNetwork Monitor
Example using falconAlarmsPresent OID:
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| rle | 1.3.6.1.4.1.3184 | |||
| products | 1.3.6.1.4.1.3184.1 | |||
| falcon | 1.3.6.1.4.1.3184.1.1 | |||
| falconMIB | 1.3.6.1.4.1.3184.1.1.1 | |||
| falconIdent | 1.3.6.1.4.1.3184.1.1.1.1 | |||
| STR falconIdentManufacturer | 1.3.6.1.4.1.3184.1.1.1.1.1 | DisplayString | read-only | The Monitor Control Unit manufacturer. |
| STR falconIdentModel | 1.3.6.1.4.1.3184.1.1.1.1.2 | DisplayString | read-only | The Monitor Control Unit Model designation. |
| STR falconIdentSoftwareVersion | 1.3.6.1.4.1.3184.1.1.1.1.3 | DisplayString | read-only | The falcon SNMP Agent software version. |
| OID falconIdentSpecific | 1.3.6.1.4.1.3184.1.1.1.1.4 | OBJECT IDENTIFIER | read-only | A reference to MIB definitions specific to the particular Monitor Unit being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value. |
| falconSystem | 1.3.6.1.4.1.3184.1.1.1.2 | |||
| STR falconClock | 1.3.6.1.4.1.3184.1.1.1.2.1 | DisplayString | read-write | The falcon internal clock settings. Displayed as MM/DD/YY HH:MM:SS |
| INT falconDoorAlarmBypass | 1.3.6.1.4.1.3184.1.1.1.2.2 | INTEGER | read-write | The falcon door alarm bypass switch. This allows the alarm to be bypassed upon valid keypad access. Zero disables this, or use 1 thru 8 for the corresponding falcon input. |
| falconKeypad | 1.3.6.1.4.1.3184.1.1.1.2.3 | |||
| STR falconKeypadCode1 | 1.3.6.1.4.1.3184.1.1.1.2.3.1 | DisplayString | read-write | The falcon keypad access code for user #1. This can be up to six numberic characters. |
| STR falconKeypadName1 | 1.3.6.1.4.1.3184.1.1.1.2.3.2 | DisplayString | read-write | The falcon keypad access name for user #1. This can be up to 20 characters. |
| STR falconKeypadCode2 | 1.3.6.1.4.1.3184.1.1.1.2.3.3 | DisplayString | read-write | The falcon keypad access code for user #2. This can be up to six numberic characters. |
| STR falconKeypadName2 | 1.3.6.1.4.1.3184.1.1.1.2.3.4 | DisplayString | read-write | The falcon keypad access name for user #2. This can be up to 20 characters. |
| STR falconKeypadCode3 | 1.3.6.1.4.1.3184.1.1.1.2.3.5 | DisplayString | read-write | The falcon keypad access code for user #3. This can be up to six numberic characters. |
| STR falconKeypadName3 | 1.3.6.1.4.1.3184.1.1.1.2.3.6 | DisplayString | read-write | The falcon keypad access name for user #3. This can be up to 20 characters. |
| STR falconKeypadCode4 | 1.3.6.1.4.1.3184.1.1.1.2.3.7 | DisplayString | read-write | The falcon keypad access code for user #4. This can be up to six numberic characters. |
| STR falconKeypadName4 | 1.3.6.1.4.1.3184.1.1.1.2.3.8 | DisplayString | read-write | The falcon keypad access name for user #4. This can be up to 20 characters. |
| STR falconKeypadCode5 | 1.3.6.1.4.1.3184.1.1.1.2.3.9 | DisplayString | read-write | The falcon keypad access code for user #5. This can be up to six numberic characters. |
| STR falconKeypadName5 | 1.3.6.1.4.1.3184.1.1.1.2.3.10 | DisplayString | read-write | The falcon keypad access name for user #5. This can be up to 20 characters. |
| STR falconKeypadCode6 | 1.3.6.1.4.1.3184.1.1.1.2.3.11 | DisplayString | read-write | The falcon keypad access code for user #6. This can be up to six numberic characters. |
| STR falconKeypadName6 | 1.3.6.1.4.1.3184.1.1.1.2.3.12 | DisplayString | read-write | The falcon keypad access name for user #6. This can be up to 20 characters. |
| STR falconKeypadCode7 | 1.3.6.1.4.1.3184.1.1.1.2.3.13 | DisplayString | read-write | The falcon keypad access code for user #7. This can be up to six numberic characters. |
| STR falconKeypadName7 | 1.3.6.1.4.1.3184.1.1.1.2.3.14 | DisplayString | read-write | The falcon keypad access name for user #7. This can be up to 20 characters. |
| STR falconKeypadCode8 | 1.3.6.1.4.1.3184.1.1.1.2.3.15 | DisplayString | read-write | The falcon keypad access code for user #8. This can be up to six numberic characters. |
| STR falconKeypadName8 | 1.3.6.1.4.1.3184.1.1.1.2.3.16 | DisplayString | read-write | The falcon keypad access name for user #8. This can be up to 20 characters. |
| STR falconKeypadCode9 | 1.3.6.1.4.1.3184.1.1.1.2.3.17 | DisplayString | read-write | The falcon keypad access code for user #9. This can be up to six numberic characters. |
| STR falconKeypadName9 | 1.3.6.1.4.1.3184.1.1.1.2.3.18 | DisplayString | read-write | The falcon keypad access name for user #9. This can be up to 20 characters. |
| STR falconKeypadCode10 | 1.3.6.1.4.1.3184.1.1.1.2.3.19 | DisplayString | read-write | The falcon keypad access code for user #10. This can be up to six numberic characters. |
| STR falconKeypadName10 | 1.3.6.1.4.1.3184.1.1.1.2.3.20 | DisplayString | read-write | The falcon keypad access name for user #10. This can be up to 20 characters. |
| STR falconKeypadCode11 | 1.3.6.1.4.1.3184.1.1.1.2.3.21 | DisplayString | read-write | The falcon keypad access code for user #11. This can be up to six numberic characters. |
| STR falconKeypadName11 | 1.3.6.1.4.1.3184.1.1.1.2.3.22 | DisplayString | read-write | The falcon keypad access name for user #11. This can be up to 20 characters. |
| STR falconKeypadCode12 | 1.3.6.1.4.1.3184.1.1.1.2.3.23 | DisplayString | read-write | The falcon keypad access code for user #12. This can be up to six numberic characters. |
| STR falconKeypadName12 | 1.3.6.1.4.1.3184.1.1.1.2.3.24 | DisplayString | read-write | The falcon keypad access name for user #12. This can be up to 20 characters. |
| STR falconKeypadCode13 | 1.3.6.1.4.1.3184.1.1.1.2.3.25 | DisplayString | read-write | The falcon keypad access code for user #13. This can be up to six numberic characters. |
| STR falconKeypadName13 | 1.3.6.1.4.1.3184.1.1.1.2.3.26 | DisplayString | read-write | The falcon keypad access name for user #13. This can be up to 20 characters. |
| STR falconKeypadCode14 | 1.3.6.1.4.1.3184.1.1.1.2.3.27 | DisplayString | read-write | The falcon keypad access code for user #14. This can be up to six numberic characters. |
| STR falconKeypadName14 | 1.3.6.1.4.1.3184.1.1.1.2.3.28 | DisplayString | read-write | The falcon keypad access name for user #14. This can be up to 20 characters. |
| STR falconKeypadCode15 | 1.3.6.1.4.1.3184.1.1.1.2.3.29 | DisplayString | read-write | The falcon keypad access code for user #15. This can be up to six numberic characters. |
| STR falconKeypadName15 | 1.3.6.1.4.1.3184.1.1.1.2.3.30 | DisplayString | read-write | The falcon keypad access name for user #15. This can be up to 20 characters. |
| STR falconKeypadCode16 | 1.3.6.1.4.1.3184.1.1.1.2.3.31 | DisplayString | read-write | The falcon keypad access code for user #16. This can be up to six numberic characters. |
| STR falconKeypadName16 | 1.3.6.1.4.1.3184.1.1.1.2.3.32 | DisplayString | read-write | The falcon keypad access name for user #16. This can be up to 20 characters. |
| STR falconKeypadCode17 | 1.3.6.1.4.1.3184.1.1.1.2.3.33 | DisplayString | read-write | The falcon keypad access code for user #17. This can be up to six numberic characters. |
| STR falconKeypadName17 | 1.3.6.1.4.1.3184.1.1.1.2.3.34 | DisplayString | read-write | The falcon keypad access name for user #17. This can be up to 20 characters. |
| STR falconKeypadCode18 | 1.3.6.1.4.1.3184.1.1.1.2.3.35 | DisplayString | read-write | The falcon keypad access code for user #18. This can be up to six numberic characters. |
| STR falconKeypadName18 | 1.3.6.1.4.1.3184.1.1.1.2.3.36 | DisplayString | read-write | The falcon keypad access name for user #18. This can be up to 20 characters. |
| STR falconKeypadCode19 | 1.3.6.1.4.1.3184.1.1.1.2.3.37 | DisplayString | read-write | The falcon keypad access code for user #19. This can be up to six numberic characters. |
| STR falconKeypadName19 | 1.3.6.1.4.1.3184.1.1.1.2.3.38 | DisplayString | read-write | The falcon keypad access name for user #19. This can be up to 20 characters. |
| STR falconKeypadCode20 | 1.3.6.1.4.1.3184.1.1.1.2.3.39 | DisplayString | read-write | The falcon keypad access code for user #20. This can be up to six numberic characters. |
| STR falconKeypadName20 | 1.3.6.1.4.1.3184.1.1.1.2.3.40 | DisplayString | read-write | The falcon keypad access name for user #20. This can be up to 20 characters. |
| INT falconInputVoltage | 1.3.6.1.4.1.3184.1.1.1.2.4 | INTEGER | read-only | The falcon input voltage (DC Power). |
| INT falconOnBattery | 1.3.6.1.4.1.3184.1.1.1.2.5 | INTEGER | read-write | The state of use of the On Battery Alarm. When the State is set to installed(1), the On Battery and Low Battery alarms are enabled. This variable is stored in non-volatile memory. |
| INT falconLowBatteryThreshold | 1.3.6.1.4.1.3184.1.1.1.2.6 | INTEGER | read-write | The low voltage trip point for the low battery alarm. When the input voltage goes below this voltage, the Low Battery alarm is set. This variable is stored in non-volatile memory. |
| INT falconAnalogAverage | 1.3.6.1.4.1.3184.1.1.1.2.7 | INTEGER | read-write | This is the analog averaging duration in seconds. The analog input readings are averaged for this time period before updating. This value must be set to 1,2,3,4,5,6,10,15,20,30 or 60 seconds. This variable is stored in non-volatile memory. |
| falconInputs | 1.3.6.1.4.1.3184.1.1.1.3 | |||
| falconInput1 | 1.3.6.1.4.1.3184.1.1.1.3.1 | |||
| INT falconInput1State | 1.3.6.1.4.1.3184.1.1.1.3.1.1 | INTEGER | read-write | The state of use of Input Number 1. When a sensor is connected to Input 1 set State to installed(2) to indicate that the value of falconReading1 is valid. When no sensor is connected to Input 1 set State to notInstalled(1) to indicate that the value of falconReading1 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput1Reading | 1.3.6.1.4.1.3184.1.1.1.3.1.2 | INTEGER | read-only | The reading for sensor 1. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput1Gain | 1.3.6.1.4.1.3184.1.1.1.3.1.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 1 to obtain the value of the Input1 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput1Offset | 1.3.6.1.4.1.3184.1.1.1.3.1.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 1 to obtain the value of the Input1 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput1Label | 1.3.6.1.4.1.3184.1.1.1.3.1.5 | DisplayString | read-write | A user-defined text string associated with Input Number 1. The text string is stored in non-volatile memory. |
| STR falconInput1UOM | 1.3.6.1.4.1.3184.1.1.1.3.1.6 | DisplayString | read-write | A user-defined text string associated with Input Number 1. The text string is stored in non-volatile memory. |
| INT falconInput1HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.1.7 | INTEGER | read-write | When input 1 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 1. The HighLimit2 variable is stored in non-volatile memory. |
| INT falconInput1HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.1.8 | INTEGER | read-write | When input 1 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 1. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput1LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.1.9 | INTEGER | read-write | When input 1 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 1. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput1LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.1.10 | INTEGER | read-write | When input 1 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 1. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput1RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.1.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput1Delay | 1.3.6.1.4.1.3184.1.1.1.3.1.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput1Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.1.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput2 | 1.3.6.1.4.1.3184.1.1.1.3.2 | |||
| INT falconInput2State | 1.3.6.1.4.1.3184.1.1.1.3.2.1 | INTEGER | read-write | The state of use of Input Number 2. When a sensor is connected to Input 2 set State to installed(2) to indicate that the value of falconReading2 is valid. When no sensor is connected to Input 2 set State to notInstalled(1) to indicate that the value of falconReading2 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput2Reading | 1.3.6.1.4.1.3184.1.1.1.3.2.2 | INTEGER | read-only | The reading for sensor 2. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput2Gain | 1.3.6.1.4.1.3184.1.1.1.3.2.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 2 to obtain the value of the Input2 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput2Offset | 1.3.6.1.4.1.3184.1.1.1.3.2.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 2 to obtain the value of the Input2 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput2Label | 1.3.6.1.4.1.3184.1.1.1.3.2.5 | DisplayString | read-write | A user-defined text string associated with Input Number 2. The text string is stored in non-volatile memory. |
| STR falconInput2UOM | 1.3.6.1.4.1.3184.1.1.1.3.2.6 | DisplayString | read-write | A user-defined text string associated with Input Number 2. The text string is stored in non-volatile memory. |
| INT falconInput2HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.2.7 | INTEGER | read-write | When input 2 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 2. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput2HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.2.8 | INTEGER | read-write | When input 2 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 2. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput2LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.2.9 | INTEGER | read-write | When input 2 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 2. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput2LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.2.10 | INTEGER | read-write | When input 2 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 2. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput2RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.2.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput2Delay | 1.3.6.1.4.1.3184.1.1.1.3.2.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput2Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.2.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput3 | 1.3.6.1.4.1.3184.1.1.1.3.3 | |||
| INT falconInput3State | 1.3.6.1.4.1.3184.1.1.1.3.3.1 | INTEGER | read-write | The state of use of Input Number 3. When a sensor is connected to Input 3 set State to installed(2) to indicate that the value of falconReading3 is valid. When no sensor is connected to Input 3 set State to notInstalled(1) to indicate that the value of falconReading3 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput3Reading | 1.3.6.1.4.1.3184.1.1.1.3.3.2 | INTEGER | read-only | The reading for sensor 3. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput3Gain | 1.3.6.1.4.1.3184.1.1.1.3.3.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 3 to obtain the value of the Input3 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput3Offset | 1.3.6.1.4.1.3184.1.1.1.3.3.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 3 to obtain the value of the Input3 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput3Label | 1.3.6.1.4.1.3184.1.1.1.3.3.5 | DisplayString | read-write | A user-defined text string associated with Input Number 3. The text string is stored in non-volatile memory. |
| STR falconInput3UOM | 1.3.6.1.4.1.3184.1.1.1.3.3.6 | DisplayString | read-write | A user-defined text string associated with Input Number 3. The text string is stored in non-volatile memory. |
| INT falconInput3HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.3.7 | INTEGER | read-write | When input 3 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 3. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput3HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.3.8 | INTEGER | read-write | When input 3 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 3. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput3LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.3.9 | INTEGER | read-write | When input 3 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 3. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput3LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.3.10 | INTEGER | read-write | When input 3 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 3. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput3RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.3.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput3Delay | 1.3.6.1.4.1.3184.1.1.1.3.3.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput3Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.3.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput4 | 1.3.6.1.4.1.3184.1.1.1.3.4 | |||
| INT falconInput4State | 1.3.6.1.4.1.3184.1.1.1.3.4.1 | INTEGER | read-write | The state of use of Input Number 4. When a sensor is connected to Input 4 set State to installed(2) to indicate that the value of falconReading4 is valid. When no sensor is connected to Input 4 set State to notInstalled(1) to indicate that the value of falconReading4 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput4Reading | 1.3.6.1.4.1.3184.1.1.1.3.4.2 | INTEGER | read-only | The reading for sensor 4. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput4Gain | 1.3.6.1.4.1.3184.1.1.1.3.4.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 4 to obtain the value of the Input4 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput4Offset | 1.3.6.1.4.1.3184.1.1.1.3.4.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 4 to obtain the value of the Input4 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput4Label | 1.3.6.1.4.1.3184.1.1.1.3.4.5 | DisplayString | read-write | A user-defined text string associated with Input Number 4. The text string is stored in non-volatile memory. |
| STR falconInput4UOM | 1.3.6.1.4.1.3184.1.1.1.3.4.6 | DisplayString | read-write | A user-defined text string associated with Input Number 4. The text string is stored in non-volatile memory. |
| INT falconInput4HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.4.7 | INTEGER | read-write | When input 4 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 4. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput4HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.4.8 | INTEGER | read-write | When input 4 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 4. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput4LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.4.9 | INTEGER | read-write | When input 4 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 4. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput4LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.4.10 | INTEGER | read-write | When input 4 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 4. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput4RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.4.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput4Delay | 1.3.6.1.4.1.3184.1.1.1.3.4.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput4Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.4.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput5 | 1.3.6.1.4.1.3184.1.1.1.3.5 | |||
| INT falconInput5State | 1.3.6.1.4.1.3184.1.1.1.3.5.1 | INTEGER | read-write | The state of use of Input Number 5. When a sensor is connected to Input 5 set State to installed(2) to indicate that the value of falconReading4 is valid. When no sensor is connected to Input 5 set State to notInstalled(1) to indicate that the value of falconReading5 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput5Reading | 1.3.6.1.4.1.3184.1.1.1.3.5.2 | INTEGER | read-only | The reading for sensor 5. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput5Gain | 1.3.6.1.4.1.3184.1.1.1.3.5.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 5 to obtain the value of the Input5 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput5Offset | 1.3.6.1.4.1.3184.1.1.1.3.5.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 5 to obtain the value of the Input5 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput5Label | 1.3.6.1.4.1.3184.1.1.1.3.5.5 | DisplayString | read-write | A user-defined text string associated with Input Number 5. The text string is stored in non-volatile memory. |
| STR falconInput5UOM | 1.3.6.1.4.1.3184.1.1.1.3.5.6 | DisplayString | read-write | A user-defined text string associated with Input Number 5. The text string is stored in non-volatile memory. |
| INT falconInput5HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.5.7 | INTEGER | read-write | When input 5 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 5. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput5HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.5.8 | INTEGER | read-write | When input 5 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 5. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput5LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.5.9 | INTEGER | read-write | When input 5 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 5. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput5LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.5.10 | INTEGER | read-write | When input 5 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 5. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput5RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.5.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput5Delay | 1.3.6.1.4.1.3184.1.1.1.3.5.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput5Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.5.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput6 | 1.3.6.1.4.1.3184.1.1.1.3.6 | |||
| INT falconInput6State | 1.3.6.1.4.1.3184.1.1.1.3.6.1 | INTEGER | read-write | The state of use of Input Number 6. When a sensor is connected to Input 6 set State to installed(2) to indicate that the value of falconReading6 is valid. When no sensor is connected to Input 6 set State to notInstalled(1) to indicate that the value of falconReading6 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput6Reading | 1.3.6.1.4.1.3184.1.1.1.3.6.2 | INTEGER | read-only | The reading for sensor 6. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput6Gain | 1.3.6.1.4.1.3184.1.1.1.3.6.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 6 to obtain the value of the Input6 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput6Offset | 1.3.6.1.4.1.3184.1.1.1.3.6.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 6 to obtain the value of the Input6 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput6Label | 1.3.6.1.4.1.3184.1.1.1.3.6.5 | DisplayString | read-write | A user-defined text string associated with Input Number 6. The text string is stored in non-volatile memory. |
| STR falconInput6UOM | 1.3.6.1.4.1.3184.1.1.1.3.6.6 | DisplayString | read-write | A user-defined text string associated with Input Number 6. The text string is stored in non-volatile memory. |
| INT falconInput6HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.6.7 | INTEGER | read-write | When input 6 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 6. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput6HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.6.8 | INTEGER | read-write | When input 6 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 6. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput6LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.6.9 | INTEGER | read-write | When input 6 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 6. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput6LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.6.10 | INTEGER | read-write | When input 6 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 6. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput6RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.6.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput6Delay | 1.3.6.1.4.1.3184.1.1.1.3.6.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput6Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.6.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput7 | 1.3.6.1.4.1.3184.1.1.1.3.7 | |||
| INT falconInput7State | 1.3.6.1.4.1.3184.1.1.1.3.7.1 | INTEGER | read-write | The state of use of Input Number 7. When a sensor is connected to Input 7 set State to installed(2) to indicate that the value of falconReading4 is valid. When no sensor is connected to Input 7 set State to notInstalled(1) to indicate that the value of falconReading7 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput7Reading | 1.3.6.1.4.1.3184.1.1.1.3.7.2 | INTEGER | read-only | The reading for sensor 7. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput7Gain | 1.3.6.1.4.1.3184.1.1.1.3.7.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 7 to obtain the value of the Input7 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput7Offset | 1.3.6.1.4.1.3184.1.1.1.3.7.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 7 to obtain the value of the Input7 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput7Label | 1.3.6.1.4.1.3184.1.1.1.3.7.5 | DisplayString | read-write | A user-defined text string associated with Input Number 7. The text string is stored in non-volatile memory. |
| STR falconInput7UOM | 1.3.6.1.4.1.3184.1.1.1.3.7.6 | DisplayString | read-write | A user-defined text string associated with Input Number 7. The text string is stored in non-volatile memory. |
| INT falconInput7HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.7.7 | INTEGER | read-write | When input 7 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 7. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput7HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.7.8 | INTEGER | read-write | When input 7 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 7. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput7LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.7.9 | INTEGER | read-write | When input 7 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 7. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput7LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.7.10 | INTEGER | read-write | When input 7 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 7. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput7RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.7.11 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput7Delay | 1.3.6.1.4.1.3184.1.1.1.3.7.12 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput7Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.7.13 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput8 | 1.3.6.1.4.1.3184.1.1.1.3.8 | |||
| INT falconInput8State | 1.3.6.1.4.1.3184.1.1.1.3.8.1 | INTEGER | read-write | The state of use of Input Number 8. When a sensor is connected to Input 8 set State to installed(2) to indicate that the value of falconReading8 is valid. When no sensor is connected to Input 8 set State to notInstalled(1) to indicate that the value of falconReading8 may not be valid. This variable is stored in non-volatile memory. |
| INT falconInput8Reading | 1.3.6.1.4.1.3184.1.1.1.3.8.2 | INTEGER | read-only | The reading for sensor 8. If the input is digital, the reading will be 1 (active) or 0 (inactive) |
| INT falconInput8Gain | 1.3.6.1.4.1.3184.1.1.1.3.8.3 | INTEGER | read-write | A correction gain associated with the sensor variable. The value of gain is multiplied by the value from Input Sensor Number 8 to obtain the value of the Input8 variable. The gain variable is stored in non-volatile memory. |
| INT falconInput8Offset | 1.3.6.1.4.1.3184.1.1.1.3.8.4 | INTEGER | read-write | A correction Offset associated with the sensor variable. The value of Offset is added to the value from Input Sensor Number 8 to obtain the value of the Input8 variable. The Offset variable is stored in non-volatile memory. |
| STR falconInput8Label | 1.3.6.1.4.1.3184.1.1.1.3.8.5 | DisplayString | read-write | A user-defined text string associated with Input Number 8. The text string is stored in non-volatile memory. |
| STR falconInput8UOM | 1.3.6.1.4.1.3184.1.1.1.3.8.6 | DisplayString | read-write | A user-defined text string associated with Input Number 8. The text string is stored in non-volatile memory. |
| INT falconInput8HighLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.8.7 | INTEGER | read-write | When input 8 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 8. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput8HighLimit | 1.3.6.1.4.1.3184.1.1.1.3.8.8 | INTEGER | read-write | When input 8 reaches or exceeds this value a trap will be generated signifying a high alarm condition at sensor 8. The HighLimit variable is stored in non-volatile memory. |
| INT falconInput8LowLimit | 1.3.6.1.4.1.3184.1.1.1.3.8.9 | INTEGER | read-write | When input 8 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 8. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput8RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.8.9 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput8Delay | 1.3.6.1.4.1.3184.1.1.1.3.8.10 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| INT falconInput8LowLimit2 | 1.3.6.1.4.1.3184.1.1.1.3.8.10 | INTEGER | read-write | When input 8 reaches or goes below this value a trap will be generated signifying a low alarm condition at sensor 8. The LowLimit variable is stored in non-volatile memory. |
| INT falconInput8Hysteresis | 1.3.6.1.4.1.3184.1.1.1.3.8.11 | INTEGER | read-write | The value of alarm hysteresis for this input. The input reading must decrease or increase by this value before the alarm will clear. This variable is stored in non-volatile memory. |
| falconInput9 | 1.3.6.1.4.1.3184.1.1.1.3.25 | |||
| INT falconInput9State | 1.3.6.1.4.1.3184.1.1.1.3.25.1 | INTEGER | read-write | The state of use of Input Number 9. This variable is stored in non-volatile memory. |
| INT falconInput9Reading | 1.3.6.1.4.1.3184.1.1.1.3.25.2 | INTEGER | read-only | The reading for input 9. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput9Label | 1.3.6.1.4.1.3184.1.1.1.3.25.3 | DisplayString | read-write | A user-defined text string associated with Input Number 9. The text string is stored in non-volatile memory. |
| INT falconInput9RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.25.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput9Delay | 1.3.6.1.4.1.3184.1.1.1.3.25.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput10 | 1.3.6.1.4.1.3184.1.1.1.3.26 | |||
| INT falconInput10State | 1.3.6.1.4.1.3184.1.1.1.3.26.1 | INTEGER | read-write | The state of use of Input Number 10. This variable is stored in non-volatile memory. |
| INT falconInput10Reading | 1.3.6.1.4.1.3184.1.1.1.3.26.2 | INTEGER | read-only | The reading for input 10. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput10Label | 1.3.6.1.4.1.3184.1.1.1.3.26.3 | DisplayString | read-write | A user-defined text string associated with Input Number 10. The text string is stored in non-volatile memory. |
| INT falconInput10RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.26.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput10Delay | 1.3.6.1.4.1.3184.1.1.1.3.26.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput11 | 1.3.6.1.4.1.3184.1.1.1.3.27 | |||
| INT falconInput11State | 1.3.6.1.4.1.3184.1.1.1.3.27.1 | INTEGER | read-write | The state of use of Input Number 11. This variable is stored in non-volatile memory. |
| INT falconInput11Reading | 1.3.6.1.4.1.3184.1.1.1.3.27.2 | INTEGER | read-only | The reading for input 11. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput11Label | 1.3.6.1.4.1.3184.1.1.1.3.27.3 | DisplayString | read-write | A user-defined text string associated with Input Number 11. The text string is stored in non-volatile memory. |
| INT falconInput11RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.27.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput11Delay | 1.3.6.1.4.1.3184.1.1.1.3.27.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput12 | 1.3.6.1.4.1.3184.1.1.1.3.28 | |||
| INT falconInput12State | 1.3.6.1.4.1.3184.1.1.1.3.28.1 | INTEGER | read-write | The state of use of Input Number 12. This variable is stored in non-volatile memory. |
| INT falconInput12Reading | 1.3.6.1.4.1.3184.1.1.1.3.28.2 | INTEGER | read-only | The reading for input 12. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput12Label | 1.3.6.1.4.1.3184.1.1.1.3.28.3 | DisplayString | read-write | A user-defined text string associated with Input Number 12. The text string is stored in non-volatile memory. |
| INT falconInput12RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.28.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput12Delay | 1.3.6.1.4.1.3184.1.1.1.3.28.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput13 | 1.3.6.1.4.1.3184.1.1.1.3.29 | |||
| INT falconInput13State | 1.3.6.1.4.1.3184.1.1.1.3.29.1 | INTEGER | read-write | The state of use of Input Number 13. This variable is stored in non-volatile memory. |
| INT falconInput13Reading | 1.3.6.1.4.1.3184.1.1.1.3.29.2 | INTEGER | read-only | The reading for input 13. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput13Label | 1.3.6.1.4.1.3184.1.1.1.3.29.3 | DisplayString | read-write | A user-defined text string associated with Input Number 13. The text string is stored in non-volatile memory. |
| INT falconInput13RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.29.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput13Delay | 1.3.6.1.4.1.3184.1.1.1.3.29.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput14 | 1.3.6.1.4.1.3184.1.1.1.3.30 | |||
| INT falconInput14State | 1.3.6.1.4.1.3184.1.1.1.3.30.1 | INTEGER | read-write | The state of use of Input Number 14. This variable is stored in non-volatile memory. |
| INT falconInput14Reading | 1.3.6.1.4.1.3184.1.1.1.3.30.2 | INTEGER | read-only | The reading for input 14. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput14Label | 1.3.6.1.4.1.3184.1.1.1.3.30.3 | DisplayString | read-write | A user-defined text string associated with Input Number 14. The text string is stored in non-volatile memory. |
| INT falconInput14RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.30.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput14Delay | 1.3.6.1.4.1.3184.1.1.1.3.30.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput15 | 1.3.6.1.4.1.3184.1.1.1.3.31 | |||
| INT falconInput15State | 1.3.6.1.4.1.3184.1.1.1.3.31.1 | INTEGER | read-write | The state of use of Input Number 15. This variable is stored in non-volatile memory. |
| INT falconInput15Reading | 1.3.6.1.4.1.3184.1.1.1.3.31.2 | INTEGER | read-only | The reading for input 15. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput15Label | 1.3.6.1.4.1.3184.1.1.1.3.31.3 | DisplayString | read-write | A user-defined text string associated with Input Number 15. The text string is stored in non-volatile memory. |
| INT falconInput15RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.31.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput15Delay | 1.3.6.1.4.1.3184.1.1.1.3.31.50 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput16 | 1.3.6.1.4.1.3184.1.1.1.3.32 | |||
| INT falconInput16State | 1.3.6.1.4.1.3184.1.1.1.3.32.1 | INTEGER | read-write | The state of use of Input Number 16. This variable is stored in non-volatile memory. |
| INT falconInput16Reading | 1.3.6.1.4.1.3184.1.1.1.3.32.2 | INTEGER | read-only | The reading for input 16. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput16Label | 1.3.6.1.4.1.3184.1.1.1.3.32.3 | DisplayString | read-write | A user-defined text string associated with Input Number 16. The text string is stored in non-volatile memory. |
| INT falconInput16RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.32.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput16Delay | 1.3.6.1.4.1.3184.1.1.1.3.32.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput17 | 1.3.6.1.4.1.3184.1.1.1.3.33 | |||
| INT falconInput17State | 1.3.6.1.4.1.3184.1.1.1.3.33.1 | INTEGER | read-write | The state of use of Input Number 17. This variable is stored in non-volatile memory. |
| INT falconInput17Reading | 1.3.6.1.4.1.3184.1.1.1.3.33.2 | INTEGER | read-only | The reading for input 17. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput17Label | 1.3.6.1.4.1.3184.1.1.1.3.33.3 | DisplayString | read-write | A user-defined text string associated with Input Number 17. The text string is stored in non-volatile memory. |
| INT falconInput17RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.33.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput17Delay | 1.3.6.1.4.1.3184.1.1.1.3.33.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput18 | 1.3.6.1.4.1.3184.1.1.1.3.34 | |||
| INT falconInput18State | 1.3.6.1.4.1.3184.1.1.1.3.34.1 | INTEGER | read-write | The state of use of Input Number 18. This variable is stored in non-volatile memory. |
| INT falconInput18Reading | 1.3.6.1.4.1.3184.1.1.1.3.34.2 | INTEGER | read-only | The reading for input 18. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput18Label | 1.3.6.1.4.1.3184.1.1.1.3.34.3 | DisplayString | read-write | A user-defined text string associated with Input Number 18. The text string is stored in non-volatile memory. |
| INT falconInput18RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.34.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput18Delay | 1.3.6.1.4.1.3184.1.1.1.3.34.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput19 | 1.3.6.1.4.1.3184.1.1.1.3.35 | |||
| INT falconInput19State | 1.3.6.1.4.1.3184.1.1.1.3.35.1 | INTEGER | read-write | The state of use of Input Number 19. This variable is stored in non-volatile memory. |
| INT falconInput19Reading | 1.3.6.1.4.1.3184.1.1.1.3.35.2 | INTEGER | read-only | The reading for input 19. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput19Label | 1.3.6.1.4.1.3184.1.1.1.3.35.3 | DisplayString | read-write | A user-defined text string associated with Input Number 19. The text string is stored in non-volatile memory. |
| INT falconInput19RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.35.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput19Delay | 1.3.6.1.4.1.3184.1.1.1.3.35.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconInput20 | 1.3.6.1.4.1.3184.1.1.1.3.36 | |||
| INT falconInput20State | 1.3.6.1.4.1.3184.1.1.1.3.36.1 | INTEGER | read-write | The state of use of Input Number 20. This variable is stored in non-volatile memory. |
| INT falconInput20Reading | 1.3.6.1.4.1.3184.1.1.1.3.36.2 | INTEGER | read-only | The reading for input 20. The reading will be 1 (active) or 0 (inactive) |
| STR falconInput20Label | 1.3.6.1.4.1.3184.1.1.1.3.36.3 | DisplayString | read-write | A user-defined text string associated with Input Number 20. The text string is stored in non-volatile memory. |
| INT falconInput20RlyControl | 1.3.6.1.4.1.3184.1.1.1.3.36.4 | INTEGER | read-write | The control of the output relays. This is a binary setting with each bit representing an alarm state. To set K1 on a high alarm, set the 1st bit (1). To set K2 on a high alarm, set the 2nd bit (2). To set K1 on a low alarm, set the 3rd bit (4). To set K2 on a low alarm, set the 4th bit (8). To set K1 on a digital alarm, set the 1st bit (1). To set K2 on a digital alarm, set the 2nd bit (2). For no action. set this value to 0. The range of this setting is 0..15. This variable is stored in non-volatile memory. |
| INT falconInput20Delay | 1.3.6.1.4.1.3184.1.1.1.3.36.5 | INTEGER | read-write | The number of seconds an alarm for this input must be present before annunication. The range of this setting is 0..600. This variable is stored in non-volatile memory. |
| falconOutputs | 1.3.6.1.4.1.3184.1.1.1.4 | |||
| falconRelay1 | 1.3.6.1.4.1.3184.1.1.1.4.1 | |||
| INT falconRelay1State | 1.3.6.1.4.1.3184.1.1.1.4.1.1 | INTEGER | read-write | The state of use of Relay Number 1. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypad. This variable is stored in non-volatile memory. |
| INT falconRelay1Status | 1.3.6.1.4.1.3184.1.1.1.4.1.2 | INTEGER | read-only | The current status for relay 1. |
| STR falconRelay1Label | 1.3.6.1.4.1.3184.1.1.1.4.1.3 | DisplayString | read-write | A user-defined text string associated with Relay Number 1. The text string is stored in non-volatile memory. |
| INT falconRelay1Time | 1.3.6.1.4.1.3184.1.1.1.4.1.4 | INTEGER | read-write | The number of seconds the relay will be activated. Set this to -1 for indefinitely. |
| falconRelay2 | 1.3.6.1.4.1.3184.1.1.1.4.2 | |||
| INT falconRelay2State | 1.3.6.1.4.1.3184.1.1.1.4.2.1 | INTEGER | read-write | The state of use of Relay Number 2. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypad. This variable is stored in non-volatile memory. |
| INT falconRelay2Status | 1.3.6.1.4.1.3184.1.1.1.4.2.2 | INTEGER | read-only | The current status for relay 2. |
| STR falconRelay2Label | 1.3.6.1.4.1.3184.1.1.1.4.2.3 | DisplayString | read-write | A user-defined text string associated with Relay Number 2. The text string is stored in non-volatile memory. |
| INT falconRelay2Time | 1.3.6.1.4.1.3184.1.1.1.4.2.4 | INTEGER | read-write | The number of seconds the relay will be activated. Set this to -1 for indefinitely. |
| falconRelay3 | 1.3.6.1.4.1.3184.1.1.1.4.3 | |||
| INT falconRelay3State | 1.3.6.1.4.1.3184.1.1.1.4.3.1 | INTEGER | read-write | The state of use of Relay Number 3. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypad. This variable is stored in non-volatile memory. |
| INT falconRelay3Status | 1.3.6.1.4.1.3184.1.1.1.4.3.2 | INTEGER | read-only | The current status for relay 3. |
| STR falconRelay3Label | 1.3.6.1.4.1.3184.1.1.1.4.3.3 | DisplayString | read-write | A user-defined text string associated with Relay Number 3. The text string is stored in non-volatile memory. |
| INT falconRelay3Time | 1.3.6.1.4.1.3184.1.1.1.4.3.4 | INTEGER | read-write | The number of seconds the relay will be activated. Set this to -1 for indefinitely. |
| falconRelay4 | 1.3.6.1.4.1.3184.1.1.1.4.4 | |||
| INT falconRelay4State | 1.3.6.1.4.1.3184.1.1.1.4.4.1 | INTEGER | read-write | The state of use of Relay Number 4. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypad. This variable is stored in non-volatile memory. |
| INT falconRelay4Status | 1.3.6.1.4.1.3184.1.1.1.4.4.2 | INTEGER | read-only | The current status for relay 4. |
| STR falconRelay4Label | 1.3.6.1.4.1.3184.1.1.1.4.4.3 | DisplayString | read-write | A user-defined text string associated with Relay Number 4. The text string is stored in non-volatile memory. |
| INT falconRelay4Time | 1.3.6.1.4.1.3184.1.1.1.4.4.4 | INTEGER | read-write | The number of seconds the relay will be activated. Set this to -1 for indefinitely. |
| falconRelay5 | 1.3.6.1.4.1.3184.1.1.1.4.5 | |||
| INT falconRelay5State | 1.3.6.1.4.1.3184.1.1.1.4.5.1 | INTEGER | read-write | The state of use of Relay Number 5. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypad. This variable is stored in non-volatile memory. |
| INT falconRelay5Status | 1.3.6.1.4.1.3184.1.1.1.4.5.2 | INTEGER | read-only | The current status for relay 5. |
| STR falconRelay5Label | 1.3.6.1.4.1.3184.1.1.1.4.5.3 | DisplayString | read-write | A user-defined text string associated with Relay Number 5. The text string is stored in non-volatile memory. |
| INT falconRelay5Time | 1.3.6.1.4.1.3184.1.1.1.4.5.4 | INTEGER | read-write | The number of seconds the relay will be activated. Set this to -1 for indefinitely. |
| falconRelay6 | 1.3.6.1.4.1.3184.1.1.1.4.6 | |||
| INT falconRelay6State | 1.3.6.1.4.1.3184.1.1.1.4.6.1 | INTEGER | read-write | The state of use of Relay Number 6. The relay can be set for normally open or closed. The relay can be forced to an on or off condition, or controlled by the keypad. This variable is stored in non-volatile memory. |
| INT falconRelay6Status | 1.3.6.1.4.1.3184.1.1.1.4.6.2 | INTEGER | read-only | The current status for relay 6. |
| STR falconRelay6Label | 1.3.6.1.4.1.3184.1.1.1.4.6.3 | DisplayString | read-write | A user-defined text string associated with Relay Number 6. The text string is stored in non-volatile memory. |
| INT falconRelay6Time | 1.3.6.1.4.1.3184.1.1.1.4.6.4 | INTEGER | read-write | The number of seconds the relay will be activated. Set this to -1 for indefinitely. |
| falconAlarms | 1.3.6.1.4.1.3184.1.1.1.5 | |||
| G32 falconAlarmsPresentEx | 1.3.6.1.4.1.3184.1.1.1.5.1 | Gauge32 | read-only | The present number of active alarm conditions. |
| falconAlarmTable | 1.3.6.1.4.1.3184.1.1.1.5.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with falconAlarmId equal to 1, and increments the value of falconAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of falconAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because falconAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), falconAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of falconAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of falconAlarmsPresent. | |
| falconAlarmEntry | 1.3.6.1.4.1.3184.1.1.1.5.2.1 | not-accessible | An entry containing information applicable to a particular alarm. | |
| NUM falconAlarmId | 1.3.6.1.4.1.3184.1.1.1.5.2.1.1 | PositiveInteger | not-accessible | A unique identifier for an alarm condition. This value must remain constant. |
| OID falconAlarmDescr | 1.3.6.1.4.1.3184.1.1.1.5.2.1.2 | OBJECT IDENTIFIER | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
| falconWellKnownAlarms | 1.3.6.1.4.1.3184.1.1.1.5.3 | |||
| falconInput1HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.1 | The reading for sensor 1 has reached the high limit value. | ||
| falconInput1LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.2 | The reading for sensor 1 has reached the low limit value. | ||
| falconInput1High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.3 | The reading for sensor 1 has reached the high limit value. | ||
| falconInput1Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.4 | The reading for sensor 1 has reached the low limit value. | ||
| falconInput2HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.5 | The reading for sensor 2 has reached the high limit value. | ||
| falconInput2LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.6 | The reading for sensor 2 has reached the low limit value. | ||
| falconInput2High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.7 | The reading for sensor 2 has reached the high limit value. | ||
| falconInput2Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.8 | The reading for sensor 2 has reached the low limit value. | ||
| falconInput3HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.9 | The reading for sensor 3 has reached the high limit value. | ||
| falconInput3LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.10 | The reading for sensor 3 has reached the low limit value. | ||
| falconInput3High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.11 | The reading for sensor 3 has reached the high limit value. | ||
| falconInput3Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.12 | The reading for sensor 3 has reached the low limit value. | ||
| falconInput4HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.13 | The reading for sensor 4 has reached the high limit value. | ||
| falconInput4LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.14 | The reading for sensor 4 has reached the low limit value. | ||
| falconInput4High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.15 | The reading for sensor 4 has reached the high limit value. | ||
| falconInput4Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.16 | The reading for sensor 4 has reached the low limit value. | ||
| falconInput5HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.17 | The reading for sensor 5 has reached the high limit value. | ||
| falconInput5LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.18 | The reading for sensor 5 has reached the low limit value. | ||
| falconInput5High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.19 | The reading for sensor 5 has reached the high limit value. | ||
| falconInput5Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.20 | The reading for sensor 5 has reached the low limit value. | ||
| falconInput6HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.21 | The reading for sensor 6 has reached the high limit value. | ||
| falconInput6LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.22 | The reading for sensor 6 has reached the low limit value. | ||
| falconInput6High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.23 | The reading for sensor 6 has reached the high limit value. | ||
| falconInput6Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.24 | The reading for sensor 6 has reached the low limit value. | ||
| falconInput7HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.25 | The reading for sensor 7 has reached the high limit value. | ||
| falconInput7LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.26 | The reading for sensor 7 has reached the low limit value. | ||
| falconInput7High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.27 | The reading for sensor 7 has reached the high limit value. | ||
| falconInput7Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.28 | The reading for sensor 7 has reached the low limit value. | ||
| falconInput8HighAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.29 | The reading for sensor 8 has reached the high limit value. | ||
| falconInput8LowAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.30 | The reading for sensor 8 has reached the low limit value. | ||
| falconInput8High2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.31 | The reading for sensor 8 has reached the high limit value. | ||
| falconInput8Low2Alarm | 1.3.6.1.4.1.3184.1.1.1.5.3.32 | The reading for sensor 8 has reached the low limit value. | ||
| falconInput1DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.81 | The digital input 1 has been activated. | ||
| falconInput2DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.82 | The digital input 2 has been activated. | ||
| falconInput3DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.83 | The digital input 3 has been activated. | ||
| falconInput4DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.84 | The digital input 4 has been activated. | ||
| falconInput5DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.85 | The digital input 5 has been activated. | ||
| falconInput6DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.86 | The digital input 6 has been activated. | ||
| falconInput7DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.87 | The digital input 7 has been activated. | ||
| falconInput8DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.88 | The digital input 8 has been activated. | ||
| falconInput9DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.89 | The digital input 9 has been activated. | ||
| falconInput10DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.90 | The digital input 10 has been activated. | ||
| falconInput11DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.91 | The digital input 11 has been activated. | ||
| falconInput12DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.92 | The digital input 12 has been activated. | ||
| falconInput13DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.93 | The digital input 13 has been activated. | ||
| falconInput14DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.94 | The digital input 14 has been activated. | ||
| falconInput15DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.95 | The digital input 15 has been activated. | ||
| falconInput16DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.96 | The digital input 16 has been activated. | ||
| falconInput17DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.97 | The digital input 17 has been activated. | ||
| falconInput18DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.98 | The digital input 18 has been activated. | ||
| falconInput19DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.99 | The digital input 19 has been activated. | ||
| falconInput20DigAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.100 | The digital input 20 has been activated. | ||
| falconOnBatteryAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.102 | The On Battery input has been activated. | ||
| falconLowBatteryAlarm | 1.3.6.1.4.1.3184.1.1.1.5.3.103 | The Faclon has detected a low battery condition. | ||
| falconTraps | 1.3.6.1.4.1.3184.1.1.1.6 | |||
| NTF falconAlarmEntryAdded | 1.3.6.1.4.1.3184.1.1.1.6.0.1 | An AlarmEntryAdded Trap signifies that the a sensor reading has reached a high or low limit value. | ||
| NTF falconAlarmEntryRemoved | 1.3.6.1.4.1.3184.1.1.1.6.0.2 | An AlarmEntryAdded Trap signifies that the a sensor reading has gone below the high limit value or above the low limit value. | ||
| NTF falconAccessGranted | 1.3.6.1.4.1.3184.1.1.1.6.0.3 | An falconAccessGranted Trap signifies that a valid key code sequence was processed by the falcon. | ||
| NTF falconAccessDenied | 1.3.6.1.4.1.3184.1.1.1.6.0.4 | An falconAccessedDenied Trap signifies that an invalid key code sequence was processed by the falcon. | ||
| falconAlarmHistory | 1.3.6.1.4.1.3184.1.1.1.7 | |||
| G32 falconAlarmHistoryEntries | 1.3.6.1.4.1.3184.1.1.1.7.1 | Gauge32 | read-only | The present number of entries in the alarm history. |
| INT falconAlarmHistoryClear | 1.3.6.1.4.1.3184.1.1.1.7.2 | INTEGER | read-write | Setting this value to ClearBuffer(1) will clear the alarm history buffer. |
| falconAlarmHistoryTable | 1.3.6.1.4.1.3184.1.1.1.7.3 | not-accessible | A list of alarm history table entries stored in the in the non-volatile memory. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The falcon creates a row in the table each time a new alarm is detected. The falcon creates the first row with falconAlarmHistoryId equal to 1, and increments the value of falconAlarmHistoryId each time a new row is created, up to a maximum of 100. After 100 entries are created, the falcon will overwrite the earliest entry with the latest alarm. The number of rows in the table at any given time is reflected by the value of falconAlarmHistoryEntries. | |
| falconAlarmHistoryEntry | 1.3.6.1.4.1.3184.1.1.1.7.3.1 | not-accessible | An entry containing information applicable to a particular alarm history entry. | |
| NUM falconAlarmHistoryId | 1.3.6.1.4.1.3184.1.1.1.7.3.1.1 | PositiveInteger | not-accessible | A unique identifier for an alarm condition. This value must remain constant. |
| STR falconAlarmHistoryText | 1.3.6.1.4.1.3184.1.1.1.7.3.1.2 | DisplayString | read-only | A text desciption of the alarm history entry. Each of the strings will have the following format, AHxxx-id-type-timestamp label xxx = number entry in the table id = Alarm ID type = HIGH, LOW, ALM or RTN timestamp = MM/DD/YY HH:MM:SS Label = The label associated with the input channel These alarms are stored in non-volatile memory. |
| falconTrapSettings | 1.3.6.1.4.1.3184.1.1.1.8 | |||
| INT falconPersistantTraps | 1.3.6.1.4.1.3184.1.1.1.8.1 | INTEGER | read-write | The number of minutes between persistant traps. Set this to 0 to turn off persistant traps. This value is stored in non-volatile memory. |
| INT falconAlarmAcknowledge | 1.3.6.1.4.1.3184.1.1.1.8.2 | INTEGER | read-write | Setting this value to AcknowledgeAlarms(1) will stop the falcon from sending persistant traps and dial out sequences. |
| falcon8124 | 1.3.6.1.4.1.3184.1.1.3 |
RFC description
RLE Falcon monitor control unit management MIB for SNMP agent configuration and hardware monitoring.
Start monitoring RLE Technologies Falcon environmental monitoring unit, data center/telecom rack controllers with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.