All MIBs › ROOMALERT24E-MIB
Category: Environmental Monitoring
Description: Manages AVTECH Room Alert 24E rack environment monitor sensors, thresholds, and alert states.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is ROOMALERT24E-MIB?
ROOMALERT24E-MIB is an AVTECH Software (enterprise OID 20916, Room Alert environmental-monitoring line) proprietary MIB for the Room Alert 24E sensor appliance. Its objects cover internal temperature (Fahrenheit/Celsius, scaled x100), internal humidity, heat-index (F/C), and up to four digital sensor ports each supporting five sensor-reading slots. As a performance MIB it lets an administrator watch data-center/room temperature, humidity, and heat index alongside up to twenty attached digital sensors (door, water, motion, etc.) on a Room Alert 24E unit. It is deployed on the AVTECH Room Alert 24E environmental-monitoring appliance. Engineers can download the ROOMALERT24E-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in ROOMALERT24E-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- AVTECH Room Alert 24E environmental-monitoring appliance
Monitoring Examples
An administrator monitors internal-tempf and internal-humidity to catch a data-center cooling failure via a Room Alert 24E environmental-monitoring appliance.
What Can Be Monitored
- temperature, humidity, heat index, and digital sensor readings
This MIB depends on
Related MIBs
Imported Objects
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| avtech | 1.3.6.1.4.1.20916 | |||
| products | 1.3.6.1.4.1.20916.1 | |||
| roomalert24e | 1.3.6.1.4.1.20916.1.5 | |||
| NTF tempalarm1_24e | 1.3.6.1.4.1.20916.1.5.0.1 | A tempalarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold. | ||
| NTF room_alert_24e_snmp_trap | 1.3.6.1.4.1.20916.1.5.0.2 | A room-alert-24e-snmp-trap indicates that an alarm condition has occurred on the sensor indicated by the alarmmessage variable. | ||
| NTF tempalarm2_24e | 1.3.6.1.4.1.20916.1.5.0.3 | A tempalarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold. | ||
| NTF tempclear2_24e | 1.3.6.1.4.1.20916.1.5.0.4 | A tempclear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshold. | ||
| NTF tempalarm3_24e | 1.3.6.1.4.1.20916.1.5.0.5 | A tempalarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold. | ||
| NTF tempclear3_24e | 1.3.6.1.4.1.20916.1.5.0.6 | A tempclear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshold. | ||
| NTF humidityalarm1_24e | 1.3.6.1.4.1.20916.1.5.0.7 | A humidityalarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold. | ||
| NTF humidityclear1_24e | 1.3.6.1.4.1.20916.1.5.0.8 | A humidityclear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low threshold. | ||
| NTF humidityalarm2_24e | 1.3.6.1.4.1.20916.1.5.0.9 | A humidityalarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold. | ||
| NTF humidityclear2_24e | 1.3.6.1.4.1.20916.1.5.0.10 | A humidityclear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low threshold. | ||
| NTF humidityalarm3_24e | 1.3.6.1.4.1.20916.1.5.0.11 | A humidityalarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold. | ||
| NTF humidityclear3_24e | 1.3.6.1.4.1.20916.1.5.0.12 | A humidityclear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low threshold. | ||
| NTF switchalarm1_24e | 1.3.6.1.4.1.20916.1.5.0.13 | A switchalarm1 trap signifies that switch sensor 1 is in an alarm state. | ||
| NTF switchclear1_24e | 1.3.6.1.4.1.20916.1.5.0.14 | A switchclear1 trap signifies that the switch sensor 1 has returned to a normal state. | ||
| NTF switchalarm2_24e | 1.3.6.1.4.1.20916.1.5.0.15 | A switchalarm2 trap signifies that switch sensor 2 is in an alarm state. | ||
| NTF switchclear2_24e | 1.3.6.1.4.1.20916.1.5.0.16 | A switchclear2 trap signifies that the switch sensor 2 has returned to a normal state. | ||
| NTF switchalarm3_24e | 1.3.6.1.4.1.20916.1.5.0.17 | A switchalarm1 trap signifies that switch sensor 1 is in an alarm state. | ||
| NTF switchclear3_24e | 1.3.6.1.4.1.20916.1.5.0.18 | A switchclear3 trap signifies that the switch sensor 3 has returned to a normal state. | ||
| NTF switchalarm4_24e | 1.3.6.1.4.1.20916.1.5.0.19 | A switchalarm4 trap signifies that switch sensor 4 is in an alarm state. | ||
| NTF switchclear4_24e | 1.3.6.1.4.1.20916.1.5.0.20 | A switchclear4 trap signifies that the switch sensor 4 has returned to a normal state. | ||
| NTF switchalarm5_24e | 1.3.6.1.4.1.20916.1.5.0.21 | A switchalarm5 trap signifies that switch sensor 5 is in an alarm state. | ||
| NTF switchclear5_24e | 1.3.6.1.4.1.20916.1.5.0.22 | A switchclear5 trap signifies that the switch sensor 5 has returned to a normal state. | ||
| NTF switchalarm6_24e | 1.3.6.1.4.1.20916.1.5.0.23 | A switchalarm6 trap signifies that switch sensor 6 is in an alarm state. | ||
| NTF switchclear6_24e | 1.3.6.1.4.1.20916.1.5.0.24 | A switchclear6 trap signifies that the switch sensor 6 has returned to a normal state. | ||
| NTF switchalarm7_24e | 1.3.6.1.4.1.20916.1.5.0.25 | A switchalarm7 trap signifies that switch sensor 7 is in an alarm state. | ||
| NTF switchclear7_24e | 1.3.6.1.4.1.20916.1.5.0.26 | A switchclear7 trap signifies that the switch sensor 7 has returned to a normal state. | ||
| NTF switchalarm8_24e | 1.3.6.1.4.1.20916.1.5.0.27 | A switchalarm8 trap signifies that switch sensor 8 is in an alarm state. | ||
| NTF switchclear8_24e | 1.3.6.1.4.1.20916.1.5.0.28 | A switchclear8 trap signifies that the switch sensor 8 has returned to a normal state. | ||
| sensors | 1.3.6.1.4.1.20916.1.5.1 | |||
| internal | 1.3.6.1.4.1.20916.1.5.1.1 | |||
| temperature | 1.3.6.1.4.1.20916.1.5.1.1.1 | |||
| INT internal_tempf | 1.3.6.1.4.1.20916.1.5.1.1.1.1 | INTEGER | read-only | The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. |
| INT internal_tempc | 1.3.6.1.4.1.20916.1.5.1.1.1.2 | INTEGER | read-only | The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. |
| humidity | 1.3.6.1.4.1.20916.1.5.1.1.2 | |||
| INT internal_humidity | 1.3.6.1.4.1.20916.1.5.1.1.2.1 | INTEGER | read-only | The internal relative humidity reading in %RH. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. |
| heat_index | 1.3.6.1.4.1.20916.1.5.1.1.3 | |||
| INT internal_heat_index | 1.3.6.1.4.1.20916.1.5.1.1.3.1 | INTEGER | read-only | The internal heat index reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. |
| INT internal_heat_indexc | 1.3.6.1.4.1.20916.1.5.1.1.3.2 | INTEGER | read-only | The internal heat index reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided by 100 to get the actual value. |
| digital | 1.3.6.1.4.1.20916.1.5.1.2 | |||
| digital_sen1 | 1.3.6.1.4.1.20916.1.5.1.2.1 | |||
| INT digital_sen1_1 | 1.3.6.1.4.1.20916.1.5.1.2.1.1 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. |
| INT digital_sen1_2 | 1.3.6.1.4.1.20916.1.5.1.2.1.2 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. |
| INT digital_sen1_3 | 1.3.6.1.4.1.20916.1.5.1.2.1.3 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. |
| INT digital_sen1_4 | 1.3.6.1.4.1.20916.1.5.1.2.1.4 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. |
| INT digital_sen1_5 | 1.3.6.1.4.1.20916.1.5.1.2.1.5 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| digital_sen2 | 1.3.6.1.4.1.20916.1.5.1.2.2 | |||
| INT digital_sen2_1 | 1.3.6.1.4.1.20916.1.5.1.2.2.1 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. |
| INT digital_sen2_2 | 1.3.6.1.4.1.20916.1.5.1.2.2.2 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. |
| INT digital_sen2_3 | 1.3.6.1.4.1.20916.1.5.1.2.2.3 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. |
| INT digital_sen2_4 | 1.3.6.1.4.1.20916.1.5.1.2.2.4 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. |
| INT digital_sen2_5 | 1.3.6.1.4.1.20916.1.5.1.2.2.5 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| digital_sen3 | 1.3.6.1.4.1.20916.1.5.1.2.3 | |||
| INT digital_sen3_1 | 1.3.6.1.4.1.20916.1.5.1.2.3.1 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. |
| INT digital_sen3_2 | 1.3.6.1.4.1.20916.1.5.1.2.3.2 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. |
| INT digital_sen3_3 | 1.3.6.1.4.1.20916.1.5.1.2.3.3 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. |
| INT digital_sen3_4 | 1.3.6.1.4.1.20916.1.5.1.2.3.4 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. |
| INT digital_sen3_5 | 1.3.6.1.4.1.20916.1.5.1.2.3.5 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| digital_sen4 | 1.3.6.1.4.1.20916.1.5.1.2.4 | |||
| INT digital_sen4_1 | 1.3.6.1.4.1.20916.1.5.1.2.4.1 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. |
| INT digital_sen4_2 | 1.3.6.1.4.1.20916.1.5.1.2.4.2 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. |
| INT digital_sen4_3 | 1.3.6.1.4.1.20916.1.5.1.2.4.3 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. |
| INT digital_sen4_4 | 1.3.6.1.4.1.20916.1.5.1.2.4.4 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. |
| INT digital_sen4_5 | 1.3.6.1.4.1.20916.1.5.1.2.4.5 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| digital_sen5 | 1.3.6.1.4.1.20916.1.5.1.2.5 | |||
| INT digital_sen5_1 | 1.3.6.1.4.1.20916.1.5.1.2.5.1 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. |
| INT digital_sen5_2 | 1.3.6.1.4.1.20916.1.5.1.2.5.2 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. |
| INT digital_sen5_3 | 1.3.6.1.4.1.20916.1.5.1.2.5.3 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. |
| INT digital_sen5_4 | 1.3.6.1.4.1.20916.1.5.1.2.5.4 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. |
| INT digital_sen5_5 | 1.3.6.1.4.1.20916.1.5.1.2.5.5 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| digital_sen6 | 1.3.6.1.4.1.20916.1.5.1.2.6 | |||
| INT digital_sen6_1 | 1.3.6.1.4.1.20916.1.5.1.2.6.1 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage. |
| INT digital_sen6_2 | 1.3.6.1.4.1.20916.1.5.1.2.6.2 | INTEGER | read-only | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts. |
| INT digital_sen6_3 | 1.3.6.1.4.1.20916.1.5.1.2.6.3 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts. |
| INT digital_sen6_4 | 1.3.6.1.4.1.20916.1.5.1.2.6.4 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts. |
| INT digital_sen6_5 | 1.3.6.1.4.1.20916.1.5.1.2.6.5 | INTEGER | read-only | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| switch | 1.3.6.1.4.1.20916.1.5.1.3 | |||
| INT switch_sen1 | 1.3.6.1.4.1.20916.1.5.1.3.1 | INTEGER | read-only | The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen2 | 1.3.6.1.4.1.20916.1.5.1.3.2 | INTEGER | read-only | The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen3 | 1.3.6.1.4.1.20916.1.5.1.3.3 | INTEGER | read-only | The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen4 | 1.3.6.1.4.1.20916.1.5.1.3.4 | INTEGER | read-only | The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen5 | 1.3.6.1.4.1.20916.1.5.1.3.5 | INTEGER | read-only | The reading for switch sensor 5 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen6 | 1.3.6.1.4.1.20916.1.5.1.3.6 | INTEGER | read-only | The reading for switch sensor 6 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen7 | 1.3.6.1.4.1.20916.1.5.1.3.7 | INTEGER | read-only | The reading for switch sensor 7 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen8 | 1.3.6.1.4.1.20916.1.5.1.3.8 | INTEGER | read-only | The reading for switch sensor 8 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen9 | 1.3.6.1.4.1.20916.1.5.1.3.9 | INTEGER | read-only | The reading for switch sensor 9 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen10 | 1.3.6.1.4.1.20916.1.5.1.3.10 | INTEGER | read-only | The reading for switch sensor 10 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen11 | 1.3.6.1.4.1.20916.1.5.1.3.11 | INTEGER | read-only | The reading for switch sensor 11 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen12 | 1.3.6.1.4.1.20916.1.5.1.3.12 | INTEGER | read-only | The reading for switch sensor 12 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen13 | 1.3.6.1.4.1.20916.1.5.1.3.13 | INTEGER | read-only | The reading for switch sensor 13 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen14 | 1.3.6.1.4.1.20916.1.5.1.3.14 | INTEGER | read-only | The reading for switch sensor 14 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen15 | 1.3.6.1.4.1.20916.1.5.1.3.15 | INTEGER | read-only | The reading for switch sensor 15 (0 = OPEN, 1 = CLOSED). |
| INT switch_sen16 | 1.3.6.1.4.1.20916.1.5.1.3.16 | INTEGER | read-only | The reading for switch sensor 16 (0 = OPEN, 1 = CLOSED). |
| traps | 1.3.6.1.4.1.20916.1.5.2 | |||
| OCT alarmmessage | 1.3.6.1.4.1.20916.1.5.2.1 | OCTET STRING | read-only | Last Alarm Message |
RFC description
AVTECH Room Alert 24E environmental monitoring for temperature, humidity, heat index, and digital sensors.
Start monitoring AVTECH Room Alert 24E environmental-monitoring appliance (temperature/humidity/heat-index/digital sensors) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.