All MIBs › GE-SINGLEUPS
Description: GE-SINGLEUPS module
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is GE-SINGLEUPS?
GE-SINGLEUPS is a GE Digital Energy proprietary MIB (enterprise OID 818) for single-unit uninterruptible power supplies, exposing UPS discovery and identity information. Its objects cover a bitmask of discovered UPS units, request/reply packet objects for a proprietary polling mechanism, and generic identity fields (manufacturer, model, UPS/agent software version, name, attached-device list, serial number). As a hardware-status/inventory MIB it lets an administrator confirm UPS identity and firmware version, complementing standard UPS-MIB monitoring. It is deployed on GE Digital Energy single-unit UPS systems. Engineers can download the GE-SINGLEUPS file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in GE-SINGLEUPS. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- GE Digital Energy single-unit UPS systems
Monitoring Examples
An administrator reads upsIdentModel-gen and upsIdentUPSSerialNumber-gen to confirm the exact UPS model and unit before cross-referencing a vendor service bulletin against a fleet of GE UPS units.
What Can Be Monitored
- UPS identity (manufacturer/model/serial/firmware)
This MIB depends on
Related MIBs
Imported Objects
From SNMPv2-SMI
| Counter32 | |
| Gauge32 | |
| Integer32 | |
| IpAddress | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-IDENTITY | |
| OBJECT-TYPE | |
| enterprises |
From SNMPv2-TC
| AutonomousType | |
| DisplayString | |
| TEXTUAL-CONVENTION | |
| TestAndIncr | |
| TimeInterval | |
| TimeStamp |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| imv | 1.3.6.1.4.1.818 | |||
| geHardware | 1.3.6.1.4.1.818.1 | |||
| geUPS | 1.3.6.1.4.1.818.1.1 | |||
| I32 geDiscoveredUPSsMask | 1.3.6.1.4.1.818.1.1.1 | Integer32 | read-only | Reading this variable returns bit mask indicating which UPSs in a parallel system are alive. Management software should poll only these UPSs on their snmp branches 11-18 as follows: 1 FirstUPS alive 2 SecondUPS alive 4 ThirdUPS alive 8 FourthUPS alive 16 FifthUPS alive 32 SixthUPS alive 64 SeventhUPS alive 128 EigthUPS alive Since the management software should always monitor the GenericUPS branch (10), this value has no meaning for single upses (which provide values on that snmp branch), and should be set to zero in that case. |
| STR geRequestPacket | 1.3.6.1.4.1.818.1.1.2 | DisplayString | read-write | Put the string, formatted as a IMV/CP4 packet, directly to internally RS485 bus. This OID could be used for accede directly to the internally RS485 bus from a remote place. |
| STR geReplyPacket | 1.3.6.1.4.1.818.1.1.3 | DisplayString | read-only | Contain the reply of the IMV/CP4 request packet sent using the OID geRequestPacket. Every time that a write command has be made at the OID ge RequestPacket, the value of this OID is erased. |
| geGenericUPS | 1.3.6.1.4.1.818.1.1.10 | |||
| upsIdent_gen | 1.3.6.1.4.1.818.1.1.10.1 | |||
| STR upsIdentManufacturer_gen | 1.3.6.1.4.1.818.1.1.10.1.1 | DisplayString | read-only | The name of the UPS manufacturer.(*) |
| STR upsIdentModel_gen | 1.3.6.1.4.1.818.1.1.10.1.2 | DisplayString | read-only | The UPS Model designation.(*) |
| STR upsIdentUPSSoftwareVersion_gen | 1.3.6.1.4.1.818.1.1.10.1.3 | DisplayString | read-only | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.(*) |
| STR upsIdentAgentSoftwareVersion_gen | 1.3.6.1.4.1.818.1.1.10.1.4 | DisplayString | read-only | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.(*) |
| STR upsIdentName_gen | 1.3.6.1.4.1.818.1.1.10.1.5 | DisplayString | read-write | A string identifying the UPS. This object should be set by the administrator.(*) |
| STR upsIdentAttachedDevices_gen | 1.3.6.1.4.1.818.1.1.10.1.6 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator.(*) |
| STR upsIdentUPSSerialNumber_gen | 1.3.6.1.4.1.818.1.1.10.1.7 | DisplayString | read-only | The UPS serial number |
| STR upsIdentComProtVersion_gen | 1.3.6.1.4.1.818.1.1.10.1.8 | DisplayString | read-only | The IMV communication protocol version |
| NUM upsIdentOperatingTime_gen | 1.3.6.1.4.1.818.1.1.10.1.9 | NonNegativeInteger32 | read-only | The present value of the operating time. total 'on' time since UPS manufactured |
| upsBattery_gen | 1.3.6.1.4.1.818.1.1.10.2 | |||
| INT upsBatteryStatus_gen | 1.3.6.1.4.1.818.1.1.10.2.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*) |
| NUM upsSecondsOnBattery_gen | 1.3.6.1.4.1.818.1.1.10.2.2 | NonNegativeInteger32 | read-only | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*) |
| NUM upsEstimatedMinutesRemaining_gen | 1.3.6.1.4.1.818.1.1.10.2.3 | PositiveInteger32 | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.(*) |
| I32 upsEstimatedChargeRemaining_gen | 1.3.6.1.4.1.818.1.1.10.2.4 | Integer32 | read-only | An estimate of the battery charge remaining expressed as a percent of full charge.(*) |
| NUM upsBatteryVoltage_gen | 1.3.6.1.4.1.818.1.1.10.2.5 | NonNegativeInteger32 | read-only | The magnitude of the present battery voltage.(*) |
| I32 upsBatteryCurrent_gen | 1.3.6.1.4.1.818.1.1.10.2.6 | Integer32 | read-only | The present battery current.(*) |
| I32 upsBatteryTemperature_gen | 1.3.6.1.4.1.818.1.1.10.2.7 | Integer32 | read-only | The ambient temperature at or near the UPS Battery casing.(*) |
| upsInput_gen | 1.3.6.1.4.1.818.1.1.10.3 | |||
| C32 upsInputLineBads_gen | 1.3.6.1.4.1.818.1.1.10.3.1 | Counter32 | read-only | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the input transitions from zero out-of-tolerance lines to one or more input lines out-of-tolerance.(*) |
| NUM upsInputNumLines_gen | 1.3.6.1.4.1.818.1.1.10.3.2 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This variable indicates the number of rows in the input table.(*) |
| upsInputTable_gen | 1.3.6.1.4.1.818.1.1.10.3.3 | not-accessible | A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*) | |
| upsInputEntry_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1 | not-accessible | An entry containing information applicable to a particular input line.(*) | |
| NUM upsInputLineIndex_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.1 | PositiveInteger32 | not-accessible | The input line identifier.(*) |
| NUM upsInputFrequency_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.2 | NonNegativeInteger32 | read-only | The present input frequency.(*) |
| NUM upsInputVoltage_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.3 | NonNegativeInteger32 | read-only | The magnitude of the present input voltage.(*) |
| NUM upsInputCurrent_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.4 | NonNegativeInteger32 | read-only | The magnitude of the present input current.(*) |
| NUM upsInputTruePower_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.5 | NonNegativeInteger32 | read-only | The magnitude of the present input true power.(*) |
| NUM upsInputVoltageMin_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.6 | NonNegativeInteger32 | read-only | The lowest magnitude of the input voltage since last read out. |
| NUM upsInputVoltageMax_gen | 1.3.6.1.4.1.818.1.1.10.3.3.1.7 | NonNegativeInteger32 | read-only | The highest magnitude of the input voltage since last read out. |
| upsOutput_gen | 1.3.6.1.4.1.818.1.1.10.4 | |||
| INT upsOutputSource_gen | 1.3.6.1.4.1.818.1.1.10.4.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*) |
| NUM upsOutputFrequency_gen | 1.3.6.1.4.1.818.1.1.10.4.2 | NonNegativeInteger32 | read-only | The present output frequency.(*) |
| NUM upsOutputNumLines_gen | 1.3.6.1.4.1.818.1.1.10.4.3 | NonNegativeInteger32 | read-only | The number of output lines utilized in this device. This variable indicates the number of rows in the output table.(*) |
| upsOutputTable_gen | 1.3.6.1.4.1.818.1.1.10.4.4 | not-accessible | A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*) | |
| upsOutputEntry_gen | 1.3.6.1.4.1.818.1.1.10.4.4.1 | not-accessible | An entry containing information applicable to a particular output line.(*) | |
| NUM upsOutputLineIndex_gen | 1.3.6.1.4.1.818.1.1.10.4.4.1.1 | PositiveInteger32 | not-accessible | The output line identifier.(*) |
| NUM upsOutputVoltage_gen | 1.3.6.1.4.1.818.1.1.10.4.4.1.2 | NonNegativeInteger32 | read-only | The present output voltage.(*) |
| NUM upsOutputCurrent_gen | 1.3.6.1.4.1.818.1.1.10.4.4.1.3 | NonNegativeInteger32 | read-only | The present output current.(*) |
| NUM upsOutputPower_gen | 1.3.6.1.4.1.818.1.1.10.4.4.1.4 | NonNegativeInteger32 | read-only | The present output true power.(*) |
| I32 upsOutputPercentLoad_gen | 1.3.6.1.4.1.818.1.1.10.4.4.1.5 | Integer32 | read-only | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
| upsBypass_gen | 1.3.6.1.4.1.818.1.1.10.5 | |||
| NUM upsBypassFrequency_gen | 1.3.6.1.4.1.818.1.1.10.5.1 | NonNegativeInteger32 | read-only | The present bypass frequency.(*) |
| NUM upsBypassNumLines_gen | 1.3.6.1.4.1.818.1.1.10.5.2 | NonNegativeInteger32 | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.(*) |
| upsBypassTable_gen | 1.3.6.1.4.1.818.1.1.10.5.3 | not-accessible | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*) | |
| upsBypassEntry_gen | 1.3.6.1.4.1.818.1.1.10.5.3.1 | not-accessible | An entry containing information applicable to a particular bypass input.(*) | |
| NUM upsBypassLineIndex_gen | 1.3.6.1.4.1.818.1.1.10.5.3.1.1 | PositiveInteger32 | not-accessible | The bypass line identifier.(*) |
| NUM upsBypassVoltage_gen | 1.3.6.1.4.1.818.1.1.10.5.3.1.2 | NonNegativeInteger32 | read-only | The present bypass voltage.(*) |
| NUM upsBypassCurrent_gen | 1.3.6.1.4.1.818.1.1.10.5.3.1.3 | NonNegativeInteger32 | read-only | The present bypass current.(*) |
| NUM upsBypassPower_gen | 1.3.6.1.4.1.818.1.1.10.5.3.1.4 | NonNegativeInteger32 | read-only | The present true power conveyed by the bypass.(*) |
| upsAlarm_gen | 1.3.6.1.4.1.818.1.1.10.6 | |||
| G32 upsAlarmsPresent_gen | 1.3.6.1.4.1.818.1.1.10.6.1 | Gauge32 | read-only | The present number of active alarm conditions.(*) |
| upsAlarmTable_gen | 1.3.6.1.4.1.818.1.1.10.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an AutonomousType (OBJECT IDENTIFIER), upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent.(*) | |
| upsAlarmEntry_gen | 1.3.6.1.4.1.818.1.1.10.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm.(*) | |
| NUM upsAlarmId_gen | 1.3.6.1.4.1.818.1.1.10.6.2.1.1 | PositiveInteger32 | not-accessible | A unique identifier for an alarm condition. This value must remain constant.(*) |
| OID upsAlarmDescr_gen | 1.3.6.1.4.1.818.1.1.10.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
| TIM upsAlarmTime_gen | 1.3.6.1.4.1.818.1.1.10.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
| upsWellKnownAlarms_gen | 1.3.6.1.4.1.818.1.1.10.6.3 | |||
| upsAlarmBatteryBad_gen | 1.3.6.1.4.1.818.1.1.10.6.3.1 | One or more batteries have been determined to require replacement.(*) | ||
| upsAlarmOnBattery_gen | 1.3.6.1.4.1.818.1.1.10.6.3.2 | The UPS is drawing power from the batteries.(*) | ||
| upsAlarmLowBattery_gen | 1.3.6.1.4.1.818.1.1.10.6.3.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime.(*) | ||
| upsAlarmDepletedBattery_gen | 1.3.6.1.4.1.818.1.1.10.6.3.4 | The UPS will be unable to sustain the present load when and if the utility power is lost.(*) | ||
| upsAlarmTempBad_gen | 1.3.6.1.4.1.818.1.1.10.6.3.5 | A temperature is out of tolerance.(*) | ||
| upsAlarmInputBad_gen | 1.3.6.1.4.1.818.1.1.10.6.3.6 | An input condition is out of tolerance.(*) | ||
| upsAlarmOutputBad_gen | 1.3.6.1.4.1.818.1.1.10.6.3.7 | An output condition (other than OutputOverload) is out of tolerance.(*) | ||
| upsAlarmOutputOverload_gen | 1.3.6.1.4.1.818.1.1.10.6.3.8 | The output load exceeds the UPS output capacity.(*) | ||
| upsAlarmOnBypass_gen | 1.3.6.1.4.1.818.1.1.10.6.3.9 | The Bypass is presently engaged on the UPS.(*) | ||
| upsAlarmBypassBad_gen | 1.3.6.1.4.1.818.1.1.10.6.3.10 | The Bypass is out of tolerance.(*) | ||
| upsAlarmOutputOffAsRequested_gen | 1.3.6.1.4.1.818.1.1.10.6.3.11 | The UPS has shutdown as requested, i.e., the output is off.(*) | ||
| upsAlarmUpsOffAsRequested_gen | 1.3.6.1.4.1.818.1.1.10.6.3.12 | The entire UPS has shutdown as commanded.(*) | ||
| upsAlarmChargerFailed_gen | 1.3.6.1.4.1.818.1.1.10.6.3.13 | An uncorrected problem has been detected within the UPS charger subsystem.(*) | ||
| upsAlarmUpsOutputOff_gen | 1.3.6.1.4.1.818.1.1.10.6.3.14 | The output of the UPS is in the off state.(*) | ||
| upsAlarmUpsSystemOff_gen | 1.3.6.1.4.1.818.1.1.10.6.3.15 | The UPS system is in the off state.(*) | ||
| upsAlarmFanFailure_gen | 1.3.6.1.4.1.818.1.1.10.6.3.16 | The failure of one or more fans in the UPS has been detected.(*) | ||
| upsAlarmFuseFailure_gen | 1.3.6.1.4.1.818.1.1.10.6.3.17 | The failure of one or more fuses has been detected.(*) | ||
| upsAlarmGeneralFault_gen | 1.3.6.1.4.1.818.1.1.10.6.3.18 | A general fault in the UPS has been detected.(*) | ||
| upsAlarmDiagnosticTestFailed_gen | 1.3.6.1.4.1.818.1.1.10.6.3.19 | The result of the last diagnostic test indicates a failure.(*) | ||
| upsAlarmCommunicationsLost_gen | 1.3.6.1.4.1.818.1.1.10.6.3.20 | A problem has been encountered in the communications between the agent and the UPS.(*) | ||
| upsAlarmAwaitingPower_gen | 1.3.6.1.4.1.818.1.1.10.6.3.21 | The UPS output is off and the UPS is awaiting the return of input power.(*) | ||
| upsAlarmShutdownPending_gen | 1.3.6.1.4.1.818.1.1.10.6.3.22 | A upsShutdownAfterDelay countdown is underway.(*) | ||
| upsAlarmShutdownImminent_gen | 1.3.6.1.4.1.818.1.1.10.6.3.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.(*) | ||
| upsAlarmTestInProgress_gen | 1.3.6.1.4.1.818.1.1.10.6.3.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY.(*) | ||
| upsAlarmReceptacleOff_gen | 1.3.6.1.4.1.818.1.1.10.6.3.25 | The receptacle are switch off | ||
| NUM upsAlarmMaskA_gen | 1.3.6.1.4.1.818.1.1.10.6.4 | NonNegativeInteger32 | read-only | Specifies which alarm can be handled by the UPS. The 'Mask' parameter is a Long Integer32. The meaning of every bit is the same as for the 'upsAlarmGroupA' command. A bit having value=1 indicates that the corresponding alarm is handled by the UPS. |
| upsTest_gen | 1.3.6.1.4.1.818.1.1.10.7 | |||
| OID upsTestId_gen | 1.3.6.1.4.1.818.1.1.10.7.1 | OBJECT IDENTIFIER | read-write | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this document as well as those introduced by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. Setting this variable initiates the named test. Sets to this variable require the presence of upsTestSpinLock in the same SNMP message. The set request will be rejected with an appropriate error message if the requested test cannot be performed, including attempts to start a test when another test is already in progress. The status of the current or last test is maintained in upsTestResultsSummary. Tests in progress may be aborted by setting the upsTestId variable to upsTestAbortTestInProgress. Read operations return the value of the name of the test in progress if a test is in progress or the name of the last test performed if no test is in progress, unless no test has been run, in which case the well known value upsTestNoTestsInitiated is returned.(*) |
| TES upsTestSpinLock_gen | 1.3.6.1.4.1.818.1.1.10.7.2 | TestAndIncr | read-write | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress as follows: try-again: get (upsTestSpinLock) while (upsTestResultsSummary == inProgress) { /* loop while a test is running for another manager */ short delay get (upsTestSpinLock) } lock-value = upsTestSpinLock /* no test in progress, start the test */ set (upsTestSpinLock = lock-value, upsTestId = requested-test) if (error-index == 1) { /* (upsTestSpinLock failed) */ /* if problem is not access control, then some other manager slipped in ahead of us */ goto try-again } if (error-index == 2) { /* (upsTestId) */ /* cannot perform the test */ give up } /* test started ok */ /* wait for test completion by polling upsTestResultsSummary */ get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) while (upsTestResultsSummary == inProgress) { short delay get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail) } /* when test completes, retrieve any additional test results */ /* if upsTestSpinLock == lock-value + 1, then these are our test */ /* results (as opposed to another manager's */ The initial value of upsTestSpinLock at agent initialization shall be 1.(*) |
| INT upsTestResultsSummary_gen | 1.3.6.1.4.1.818.1.1.10.7.3 | INTEGER | read-only | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*) |
| STR upsTestResultsDetail_gen | 1.3.6.1.4.1.818.1.1.10.7.4 | DisplayString | read-only | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.(*) |
| TIM upsTestStartTime_gen | 1.3.6.1.4.1.818.1.1.10.7.5 | TimeStamp | read-only | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestStartTime has the value 0.(*) |
| NUM upsTestElapsedTime_gen | 1.3.6.1.4.1.818.1.1.10.7.6 | TimeInterval | read-only | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of upsTestResultsSummary is noTestsInitiated(6), upsTestElapsedTime has the value 0.(*) |
| upsWellKnownTests_gen | 1.3.6.1.4.1.818.1.1.10.7.7 | |||
| upsTestNoTestsInitiated_gen | 1.3.6.1.4.1.818.1.1.10.7.7.1 | No tests have been initiated and no test is in progress.(*) | ||
| upsTestAbortTestInProgress_gen | 1.3.6.1.4.1.818.1.1.10.7.7.2 | The test in progress is to be aborted / the test in progress was aborted.(*) | ||
| upsTestGeneralSystemsTest_gen | 1.3.6.1.4.1.818.1.1.10.7.7.3 | The manufacturer's standard test of UPS device systems.(*) | ||
| upsTestQuickBatteryTest_gen | 1.3.6.1.4.1.818.1.1.10.7.7.4 | A test that is sufficient to determine if the battery needs replacement.(*) | ||
| upsTestDeepBatteryCalibration_gen | 1.3.6.1.4.1.818.1.1.10.7.7.5 | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high degree of confidence. WARNING: this test will leave the battery in a low charge state and will require time for recharging to a level sufficient to provide normal battery duration for the protected load.(*) | ||
| upsControl_gen | 1.3.6.1.4.1.818.1.1.10.8 | |||
| INT upsShutdownType_gen | 1.3.6.1.4.1.818.1.1.10.8.1 | INTEGER | read-write | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reaches zero. Setting this object to output(1) indicates that shutdown requests should cause only the output of the UPS to turn off. Setting this object to system(2) indicates that shutdown requests will cause the entire UPS system to turn off.(*) |
| I32 upsShutdownAfterDelay_gen | 1.3.6.1.4.1.818.1.1.10.8.2 | Integer32 | read-write | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) after the indicated number of seconds, or less if the UPS batteries become depleted. Setting this object to 0 will cause the shutdown to occur immediately. Setting this object to -1 will abort the countdown. If the system is already in the desired state at the time the countdown reaches 0, then nothing will happen. That is, there is no additional action at that time if upsShutdownType = system and the system is already off. Similarly, there is no additional action at that time if upsShutdownType = output and the output is already off. When read, upsShutdownAfterDelay will return the number of seconds remaining until shutdown, or -1 if no shutdown countdown is in effect. On some systems, if the agent is restarted while a shutdown countdown is in effect, the countdown may be aborted. Sets to this object override any upsShutdownAfterDelay already in effect.(*) |
| I32 upsStartupAfterDelay_gen | 1.3.6.1.4.1.818.1.1.10.8.3 | Integer32 | read-write | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will abort the countdown. If the output is already on at the time the countdown reaches 0, then nothing will happen. Sets to this object override the effect of any upsStartupAfterDelay countdown or upsRebootWithDuration countdown in progress. When read, upsStartupAfterDelay will return the number of seconds until startup, or -1 if no startup countdown is in effect. If the countdown expires during a utility failure, the startup shall not occur until the utility power is restored. On some systems, if the agent is restarted while a startup countdown is in effect, the countdown is aborted.(*) |
| I32 upsRebootWithDuration_gen | 1.3.6.1.4.1.818.1.1.10.8.4 | Integer32 | read-write | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*) |
| INT upsAutoRestart_gen | 1.3.6.1.4.1.818.1.1.10.8.5 | INTEGER | read-write | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutdownAfterDelay or an internal battery depleted condition. Setting this object to 'off' will prevent the UPS system from restarting after a shutdown until an operator manually or remotely explicitly restarts it. If the UPS is in a startup or reboot countdown, then the UPS will not restart until that delay has been satisfied.(*) |
| NUM upsReceptaclesNum_gen | 1.3.6.1.4.1.818.1.1.10.8.6 | NonNegativeInteger32 | read-only | The number of receptacles utilized in this device. This entry indicates the number of rows in the receptacle table. |
| upsReceptacleTable_gen | 1.3.6.1.4.1.818.1.1.10.8.7 | not-accessible | A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum. | |
| upsReceptacleEntry_gen | 1.3.6.1.4.1.818.1.1.10.8.7.1 | not-accessible | An entry containing information applicable to a particular receptacle. | |
| NUM upsReceptacleLineIndex_gen | 1.3.6.1.4.1.818.1.1.10.8.7.1.1 | PositiveInteger32 | not-accessible | The receptacle line identifier. |
| INT upsReceptacleOnOff_gen | 1.3.6.1.4.1.818.1.1.10.8.7.1.2 | INTEGER | read-write | The present state of the receptacle. Setting this object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state nothing will happen. After an autorestart (see upsAutoRestart) the receptacle will be on. |
| INT upsUPSMode_gen | 1.3.6.1.4.1.818.1.1.10.8.8 | INTEGER | read-write | The operation mode off the UPS. Off-line indicates a mode in which the input power is transferred to the output directly or via a step-up or step-down transformer. On-line mode indicates a mode in which the output power is regenerated through some convertor. the operating mode of the UPS may be fixed, or may be selectable (e.g. an on-line UPS with ecomode) |
| INT upsRectifierOnOff_gen | 1.3.6.1.4.1.818.1.1.10.8.9 | INTEGER | read-write | The present state of the rectifier. Setting this object to 'on' will cause the rectifier to be turned on. Setting this object to 'off' will turn the rectifier off. If the rectifier is already in the desired state nothing will happen. |
| INT upsBatteryChargeMethod_gen | 1.3.6.1.4.1.818.1.1.10.8.10 | INTEGER | read-write | The present state of the charge method. Setting this object to 'Normal charge' will cause the battery to be charged using the normal method. Setting this object to 'Boost charge' will charge the battery in boost mode. If the charge method is already in the desired state nothing will happen. |
| INT upsInverterOnOff_gen | 1.3.6.1.4.1.818.1.1.10.8.11 | INTEGER | read-write | The present state of the inverter. Setting this object to 'on' will cause the inverter to be turned on. Setting this object to 'off' will turn the inverter off. If the inverter is already in the desired state nothing will happen. |
| INT upsBypassOnOff_gen | 1.3.6.1.4.1.818.1.1.10.8.12 | INTEGER | read-write | The present state of the bypass. Setting this object to 'on' will cause the bypass to be activated. Setting this object to 'off' will deactivate the bypass. If the UPS is already in the desired state nothing will happen. |
| INT upsLoadSource_gen | 1.3.6.1.4.1.818.1.1.10.8.13 | INTEGER | read-write | The present source of the load. Setting this object to 'On bypass' will cause the load to be supplied by the bypass. Setting this object to 'On inverter' will cause the load to be supplied by the inverter. If the load is already supplied by the desired source nothing will happen. |
| upsConfig_gen | 1.3.6.1.4.1.818.1.1.10.9 | |||
| NUM upsConfigInputVoltage_gen | 1.3.6.1.4.1.818.1.1.10.9.1 | NonNegativeInteger32 | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigInputFreq_gen | 1.3.6.1.4.1.818.1.1.10.9.2 | NonNegativeInteger32 | read-write | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVoltage_gen | 1.3.6.1.4.1.818.1.1.10.9.3 | NonNegativeInteger32 | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputFreq_gen | 1.3.6.1.4.1.818.1.1.10.9.4 | NonNegativeInteger32 | read-write | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2.(*) |
| NUM upsConfigOutputVA_gen | 1.3.6.1.4.1.818.1.1.10.9.5 | NonNegativeInteger32 | read-only | The magnitude of the nominal Volt-Amp rating.(*) |
| NUM upsConfigOutputPower_gen | 1.3.6.1.4.1.818.1.1.10.9.6 | NonNegativeInteger32 | read-only | The magnitude of the nominal true power rating.(*) |
| NUM upsConfigLowBattTime_gen | 1.3.6.1.4.1.818.1.1.10.9.7 | NonNegativeInteger32 | read-write | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the agent shall round up to the next supported value. If the requested value is larger than the largest supported value, then the largest supported value shall be selected.(*) |
| INT upsConfigAudibleStatus_gen | 1.3.6.1.4.1.818.1.1.10.9.8 | INTEGER | read-write | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*) |
| NUM upsConfigLowVoltageTransferPoint_gen | 1.3.6.1.4.1.818.1.1.10.9.9 | NonNegativeInteger32 | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigHighVoltageTransferPoint_gen | 1.3.6.1.4.1.818.1.1.10.9.10 | NonNegativeInteger32 | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup.(*) |
| NUM upsConfigBatteryCapacity_gen | 1.3.6.1.4.1.818.1.1.10.9.11 | NonNegativeInteger32 | read-write | The installed battery capacity. This value is the 'factory'-value, not the value after calibration. |
| NUM upsConfigBatteryChargeCurrent_gen | 1.3.6.1.4.1.818.1.1.10.9.12 | NonNegativeInteger32 | read-write | The maximum battery charge current, including external chargers. |
| INT upsConfigNoLoadShutdown_gen | 1.3.6.1.4.1.818.1.1.10.9.13 | INTEGER | read-write | Dis- or enable 'no load' shutdown from the contact interface. |
| NUM upsConfigStartDelay_gen | 1.3.6.1.4.1.818.1.1.10.9.14 | PositiveInteger32 | read-write | Minimum required autonomy time before the UPS may perform an autorestart. |
| upsGetSet_gen | 1.3.6.1.4.1.818.1.1.10.10 | |||
| NUM upsEventGetNext_gen | 1.3.6.1.4.1.818.1.1.10.10.1 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventSetStartingTimeStamp will be used as the start value of the table with the lowest index number. |
| NUM upsEventGetPrevious_gen | 1.3.6.1.4.1.818.1.1.10.10.2 | PositiveInteger32 | read-write | The number of events to retreive from the UPS event buffer. When this object is set the EventTable will be filled with the requested number of entries. The value upsEventLastTime will be used as the last value of the table with the highest index number. Returns SNMP-NOSUCHNAME for UPSs that don't support this command. |
| NUM upsEventSetStartingTimeStamp_gen | 1.3.6.1.4.1.818.1.1.10.10.3 | NonNegativeInteger32 | read-write | The timestamp which is used as starting point for downloading events from the UPS event buffer |
| NUM upsEventRetreiveCurrentTimeStamp_gen | 1.3.6.1.4.1.818.1.1.10.10.4 | NonNegativeInteger32 | read-only | The current timestamp is retreived from the UPS |
| NUM upsEventTableSize_gen | 1.3.6.1.4.1.818.1.1.10.10.5 | NonNegativeInteger32 | read-only | The number of entries in the event table. This object indicates the number of rows in the event table. |
| upsEventTable_gen | 1.3.6.1.4.1.818.1.1.10.10.6 | not-accessible | A list of event table entries. The number of entries is always 10, and the value of upsEventTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..10)): PDU-SET upsSetStartingTimeStamp PDU-SET upsEventGetNext PDU-GET upsEventTableSize PDU-GET upsEventCode,upsEventStatus,upsEventTime 1 PDU-GET upsEventCode,upsEventStatus,upsEventTime 2 .. PDU-GET upsEventCode,upsEventStatus,upsEventTime The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsEventTableSize. | |
| upsEventEntry_gen | 1.3.6.1.4.1.818.1.1.10.10.6.1 | not-accessible | An entry containing information applicable to a particular event. | |
| NUM upsEventLineIndex_gen | 1.3.6.1.4.1.818.1.1.10.10.6.1.1 | PositiveInteger32 | not-accessible | The event line identifier. |
| NUM upsEventCode_gen | 1.3.6.1.4.1.818.1.1.10.10.6.1.2 | NonNegativeInteger32 | read-only | The event code in numerical format. |
| NUM upsEventStatus_gen | 1.3.6.1.4.1.818.1.1.10.10.6.1.3 | NonNegativeInteger32 | read-only | The status of the UPS at the moment that the event was generated. The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMP-NOSUCHNAME is returned. |
| NUM upsEventTime_gen | 1.3.6.1.4.1.818.1.1.10.10.6.1.4 | NonNegativeInteger32 | read-only | The timestamp of the moment the event was generated. |
| NUM upsParametersRead_gen | 1.3.6.1.4.1.818.1.1.10.10.7 | PositiveInteger32 | read-write | The number of parameters to retreive from the UPS. When this object is set the ParameterTable will be filled with the requested number of entries. The value upsParametersStartAddress will be used as the start value of the table with the lowest index number. |
| NUM upsParametersWrite_gen | 1.3.6.1.4.1.818.1.1.10.10.8 | PositiveInteger32 | read-write | The number of parameters to write to the UPS. When this object is set the ParameterTable will be send to the ups. The value upsParametersStartAddress will be used for the first value of the table with the lowest index number. |
| NUM upsParametersStartAddress_gen | 1.3.6.1.4.1.818.1.1.10.10.9 | NonNegativeInteger32 | read-write | The address which is used as starting point for downloading parameters from the UPS |
| NUM upsParameterTableSize_gen | 1.3.6.1.4.1.818.1.1.10.10.10 | NonNegativeInteger32 | read-only | The number of entries in the parameter table. This object indicates the number of rows in the parameter table. |
| upsParameterTable_gen | 1.3.6.1.4.1.818.1.1.10.10.11 | not-accessible | A list of parameter entries. The number of entries is always 16, and the value of upsParameterTableSize gives the number of valid entries from the begging of the table. Invalid entries return 0. To prevent problems with simultaneous queries from several agents, these values MUST be accessed using several PDUs in the same SNMP message ( is (1..16)): Read sequence: PDU-SET upsSetStartingAddress PDU-SET upsParametersRead PDU-GET upsParameterTableSize PDU-GET upsParameterValue 1 PDU-GET upsParameterValue 2 .. PDU-GET upsParameterValue The table is read up to requested number of events and the management software afterwards decides which entries are valid, as indicated by the upsParameterTableSize. Write sequence: PDU-SET upsSetStartingAddress PDU-SET upsParameterValue 1 PDU-SET upsParameterValue 2 .. PDU-SET upsParameterValue PDU-SET upsParametersWrite | |
| upsParameterEntry_gen | 1.3.6.1.4.1.818.1.1.10.10.11.1 | not-accessible | An entry containing information applicable to a particular parameter. | |
| NUM upsParameterLineIndex_gen | 1.3.6.1.4.1.818.1.1.10.10.11.1.1 | PositiveInteger32 | not-accessible | The parameter line identifier. |
| I32 upsParameterValue_gen | 1.3.6.1.4.1.818.1.1.10.10.11.1.2 | Integer32 | read-write | The parameter value in numerical format. |
| NUM upsStatus_gen | 1.3.6.1.4.1.818.1.1.10.10.12 | NonNegativeInteger32 | read-only | The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMP-NOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0001h upsStatusEcomodeIsOn 2 0002h upsStatusBatteryIsCharging 4 0004h upsStatusBatteryIsDischarging 8 0008h upsStatusAlarmIsActive 16 0010h upsStatusRectifierIsOn 32 0020h upsStatusLowBattery 64 0040h upsStatusOnBypass 128 0080h upsStatusMainsBypassOK 256 0100h upsStatusMainsRectifierOK 512 0200h upsStatusDetourIsOn 1024 0400h upsStatusAcousticAlarmIsOn 2048 0800h - (not used.) 4096 1000h upsStatusInverterIsOn 8192 2000h upsStatusNotInParallel (Q1 open) 16384 4000h upsStatusResetLoadOff 32768 8000h upsStatusLoadOff |
| NUM upsMainsStatisticsMBfail_gen | 1.3.6.1.4.1.818.1.1.10.10.13 | NonNegativeInteger32 | read-only | Count of main bypass failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsMRfail_gen | 1.3.6.1.4.1.818.1.1.10.10.14 | NonNegativeInteger32 | read-only | Count of mains rectifier failures (>200 ms), since UPS installation. |
| NUM upsMainsStatisticsB2_gen | 1.3.6.1.4.1.818.1.1.10.10.15 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (0..2 ms), during the last 7 days. |
| NUM upsMainsStatisticsB5_gen | 1.3.6.1.4.1.818.1.1.10.10.16 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (2..5 ms), during the last 7 days. |
| NUM upsMainsStatisticsB10_gen | 1.3.6.1.4.1.818.1.1.10.10.17 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (5..10 ms), during the last 7 days. |
| NUM upsMainsStatisticsB200_gen | 1.3.6.1.4.1.818.1.1.10.10.18 | NonNegativeInteger32 | read-only | Count of transients on the mains bypass (10..200 ms), during the last 7 days. |
| NUM upsMainsStatisticsBypRel_gen | 1.3.6.1.4.1.818.1.1.10.10.19 | NonNegativeInteger32 | read-only | Bypass reliability degree [0..100%;255]. The value NOSUCHNAME means 'not available'. |
| NUM upsTime_gen | 1.3.6.1.4.1.818.1.1.10.10.20 | NonNegativeInteger32 | read-write | The current timestamp (or real-time) of the UPS. For the format, see 'Timestamp' specifications. The write-command has to comply with the correct timestamp format expected by the UPS (counter value or real-time-clock value). Missing to doing so will result in a SNMP-genERROR, meaning 'command not supported'. It is possible to know which is the timestamp format supported by the UPS, by issuing a read-command or by reading events, which includes timestamps. |
| STR upsRequestPermission_gen | 1.3.6.1.4.1.818.1.1.10.10.21 | DisplayString | write-only | An encrypted code is send to enable use of restricted write objects during a limited period of time. |
| I32 upsEventGetCode_gen | 1.3.6.1.4.1.818.1.1.10.10.22 | Integer32 | write-only | The code which is used as starting point to downloading the events from the UPS event buffer. |
| TES upsEventSpinLock_gen | 1.3.6.1.4.1.818.1.1.10.10.23 | TestAndIncr | read-write | A spin lock on the event subsystem. |
| TES upsParameterSpinLock_gen | 1.3.6.1.4.1.818.1.1.10.10.24 | TestAndIncr | read-write | A spin lock on the parameters subsystem. |
| geUPSTraps_gen | 1.3.6.1.4.1.818.1.1.10.11 | |||
| NTF upsAlarmBatteryBadTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.1 | One or more batteries have been determined to require replacement. | ||
| NTF upsAlarmOnBatteryTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.2 | An On Battery condition is restored. | ||
| NTF upsAlarmLowBatteryTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.3 | The remaining battery run-time is less than or equal to upsConfigLowBattTime. | ||
| NTF upsAlarmDepletedBatteryTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.4 | The UPS will be unable to sustain the present load when and if the utility power is lost) | ||
| NTF upsAlarmTempBadTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.5 | A temperature is out of tolerance. | ||
| NTF upsAlarmInputBadTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.6 | An input condition is out of tolerance. | ||
| NTF upsAlarmOutputBadTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.7 | An output condition (other than OutputOverload) is out of tolerance. | ||
| NTF upsAlarmOutputOverloadTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.8 | The output load exceeds the UPS output capacity. | ||
| NTF upsAlarmOnBypassTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.9 | The Bypass is presently engaged on the UPS. | ||
| NTF upsAlarmBypassBadTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.10 | The Bypass is out of tolerance. | ||
| NTF upsAlarmOutputOffAsRequestedTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.11 | The UPS has shutdown as requested, i.e., the output is off. | ||
| NTF upsAlarmUpsOffAsRequestedTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.12 | The entire UPS has shutdown as commanded. | ||
| NTF upsAlarmChargerFailedTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.13 | An uncorrected problem has been detected within the UPS charger subsystem. | ||
| NTF upsAlarmUpsOutputOffTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.14 | The output of the UPS is in the off state. | ||
| NTF upsAlarmUpsSystemOffTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.15 | The UPS system is in the off state. | ||
| NTF upsAlarmFanFailureTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.16 | The failure of one or more fans in the UPS has been detected. | ||
| NTF upsAlarmFuseFailureTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.17 | The failure of one or more fuses has been detected. | ||
| NTF upsAlarmGeneralFaultTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.18 | A general fault in the UPS has been detected. | ||
| NTF upsAlarmDiagnosticTestFailedTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.19 | The result of the last diagnostic test indicates a failure. | ||
| NTF upsAlarmCommunicationsLostTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.20 | A problem has been encountered in the communication between the agent and the UPS. | ||
| NTF upsAlarmAwaitingPowerTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.21 | The UPS output is off and the UPS is awaiting the return of the input power (*). | ||
| NTF upsAlarmShutdownPendingTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.22 | A upsShutdownAfterDelay countdown is underway. | ||
| NTF upsAlarmShutdownImminentTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.23 | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. | ||
| NTF upsAlarmTestInProgressTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.24 | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of the testing in the alarm table, if desired, via a OBJECT-IDENTITY macro in the MIB document specific to that implementation and are outside the scope of this OBJECT-IDENTITY. | ||
| NTF upsAlarmReceptacleOffTrap_gen | 1.3.6.1.4.1.818.1.1.10.11.0.25 | A receptacle has been switched off. | ||
| NTF upsAlarmBatteryBadRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.33 | A Battery bad condition is restored. | ||
| NTF upsAlarmOnBatteryRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.34 | The UPS is drawing power from mains again. | ||
| NTF upsAlarmLowBatteryRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.35 | A Low Battery condition is restored. | ||
| NTF upsAlarmDepletedBatteryRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.36 | A Depleted Battery condition is restored. | ||
| NTF upsAlarmTempBadRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.37 | A bad temperature condition is restored. | ||
| NTF upsAlarmInputBadRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.38 | An input bad condition is restored. | ||
| NTF upsAlarmOutputBadRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.39 | An output bad condition is restored. | ||
| NTF upsAlarmOutputOverloadRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.40 | An output overload condition is restored. | ||
| NTF upsAlarmOnBypassRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.41 | An On Bypass condition is restored. | ||
| NTF upsAlarmBypassBadRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.42 | A Bypass bad condition is restored. | ||
| NTF upsAlarmOutputOffAsRequestedRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.43 | A request shutdown has been restored. | ||
| NTF upsAlarmUpsOffAsRequestedRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.44 | A entire UPS command has been restored. | ||
| NTF upsAlarmChargerFailedRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.45 | A Charger Failer condition is restored. | ||
| NTF upsAlarmUpsOutputOn_gen | 1.3.6.1.4.1.818.1.1.10.11.0.46 | The output of the UPS switched in the on state. | ||
| NTF upsAlarmUpsSystemOn_gen | 1.3.6.1.4.1.818.1.1.10.11.0.47 | The UPS system is switched in the on state. | ||
| NTF upsAlarmFanFailureRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.48 | A Fan failure condition is restored. | ||
| NTF upsAlarmFuseFailureRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.49 | A Fuse failure condition is restored. | ||
| NTF upsAlarmGeneralFaultRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.50 | A general fault is restored. | ||
| NTF upsAlarmDiagnosticTestFailedRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.51 | A last diagnostic test indicates a failure is restored. | ||
| NTF upsAlarmCommunicationsLostRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.52 | A problem in the communication between the agent and the UPS is restored. | ||
| NTF upsAlarmAwaitingPowerRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.53 | A awaiting power condition is restored (*). | ||
| NTF upsAlarmShutdownPendingRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.54 | A upsShutdownAfterDelay countdown is restored. | ||
| NTF upsAlarmShutdownImminentRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.55 | A shutdown imminent condition is restored. | ||
| NTF upsAlarmTestInProgressRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.56 | The test is in progress is terminated. | ||
| NTF upsAlarmReceptacleOn_gen | 1.3.6.1.4.1.818.1.1.10.11.0.57 | A receptacle has been switched on. | ||
| NTF upsAlarmValueLow_gen | 1.3.6.1.4.1.818.1.1.10.11.0.129 | A measurement value reached a value below its low-level threshold. | ||
| NTF upsAlarmValueHigh_gen | 1.3.6.1.4.1.818.1.1.10.11.0.130 | A measurement value reached a value higher than its high-level threshold. | ||
| NTF upsAlarmValueLowRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.133 | A ValueLow alarm condition is restored. | ||
| NTF upsAlarmValueHighRestored_gen | 1.3.6.1.4.1.818.1.1.10.11.0.134 | A ValueHigh alarm condition is restored. | ||
| geEnvironmental | 1.3.6.1.4.1.818.1.2 | |||
| ioInterface_First | 1.3.6.1.4.1.818.1.2.1 | |||
| ioInterfaceInputLine_First | 1.3.6.1.4.1.818.1.2.1.1 | |||
| NUM ioInterfaceNumInputs_First | 1.3.6.1.4.1.818.1.2.1.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_First | 1.3.6.1.4.1.818.1.2.1.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_First | 1.3.6.1.4.1.818.1.2.1.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_First | 1.3.6.1.4.1.818.1.2.1.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_First | 1.3.6.1.4.1.818.1.2.1.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_First | 1.3.6.1.4.1.818.1.2.1.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_First | 1.3.6.1.4.1.818.1.2.1.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_First | 1.3.6.1.4.1.818.1.2.1.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_First | 1.3.6.1.4.1.818.1.2.1.1.3 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_First | 1.3.6.1.4.1.818.1.2.1.2 | |||
| NUM ioInterfaceNumOutput_First | 1.3.6.1.4.1.818.1.2.1.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_First | 1.3.6.1.4.1.818.1.2.1.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_First | 1.3.6.1.4.1.818.1.2.1.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_First | 1.3.6.1.4.1.818.1.2.1.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_First | 1.3.6.1.4.1.818.1.2.1.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_First | 1.3.6.1.4.1.818.1.2.1.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_First | 1.3.6.1.4.1.818.1.2.1.3 | |||
| NUM ioInterfaceNumAnalogue_First | 1.3.6.1.4.1.818.1.2.1.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_First | 1.3.6.1.4.1.818.1.2.1.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_First | 1.3.6.1.4.1.818.1.2.1.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_First | 1.3.6.1.4.1.818.1.2.1.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_First | 1.3.6.1.4.1.818.1.2.1.4 | |||
| NTF ioAlarmGenericChange_First | 1.3.6.1.4.1.818.1.2.1.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Second | 1.3.6.1.4.1.818.1.2.2 | |||
| ioInterfaceInputLine_Second | 1.3.6.1.4.1.818.1.2.2.1 | |||
| NUM ioInterfaceNumInputs_Second | 1.3.6.1.4.1.818.1.2.2.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Second | 1.3.6.1.4.1.818.1.2.2.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Second | 1.3.6.1.4.1.818.1.2.2.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Second | 1.3.6.1.4.1.818.1.2.2.2 | |||
| NUM ioInterfaceNumOutput_Second | 1.3.6.1.4.1.818.1.2.2.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Second | 1.3.6.1.4.1.818.1.2.2.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Second | 1.3.6.1.4.1.818.1.2.2.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Second | 1.3.6.1.4.1.818.1.2.2.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Second | 1.3.6.1.4.1.818.1.2.2.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Second | 1.3.6.1.4.1.818.1.2.2.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Second | 1.3.6.1.4.1.818.1.2.2.3 | |||
| NUM ioInterfaceNumAnalogue_Second | 1.3.6.1.4.1.818.1.2.2.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Second | 1.3.6.1.4.1.818.1.2.2.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Second | 1.3.6.1.4.1.818.1.2.2.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Second | 1.3.6.1.4.1.818.1.2.2.4 | |||
| NTF ioAlarmGenericChange_Second | 1.3.6.1.4.1.818.1.2.2.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Third | 1.3.6.1.4.1.818.1.2.3 | |||
| ioInterfaceInputLine_Third | 1.3.6.1.4.1.818.1.2.3.1 | |||
| NUM ioInterfaceNumInputs_Third | 1.3.6.1.4.1.818.1.2.3.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Third | 1.3.6.1.4.1.818.1.2.3.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Third | 1.3.6.1.4.1.818.1.2.3.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Third | 1.3.6.1.4.1.818.1.2.3.2 | |||
| NUM ioInterfaceNumOutput_Third | 1.3.6.1.4.1.818.1.2.3.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Third | 1.3.6.1.4.1.818.1.2.3.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Third | 1.3.6.1.4.1.818.1.2.3.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Third | 1.3.6.1.4.1.818.1.2.3.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Third | 1.3.6.1.4.1.818.1.2.3.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Third | 1.3.6.1.4.1.818.1.2.3.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Third | 1.3.6.1.4.1.818.1.2.3.3 | |||
| NUM ioInterfaceNumAnalogue_Third | 1.3.6.1.4.1.818.1.2.3.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Third | 1.3.6.1.4.1.818.1.2.3.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Third | 1.3.6.1.4.1.818.1.2.3.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Third | 1.3.6.1.4.1.818.1.2.3.4 | |||
| NTF ioAlarmGenericChange_Third | 1.3.6.1.4.1.818.1.2.3.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Fourth | 1.3.6.1.4.1.818.1.2.4 | |||
| ioInterfaceInputLine_Fourth | 1.3.6.1.4.1.818.1.2.4.1 | |||
| NUM ioInterfaceNumInputs_Fourth | 1.3.6.1.4.1.818.1.2.4.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Fourth | 1.3.6.1.4.1.818.1.2.4.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Fourth | 1.3.6.1.4.1.818.1.2.4.2 | |||
| NUM ioInterfaceNumOutput_Fourth | 1.3.6.1.4.1.818.1.2.4.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Fourth | 1.3.6.1.4.1.818.1.2.4.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Fourth | 1.3.6.1.4.1.818.1.2.4.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Fourth | 1.3.6.1.4.1.818.1.2.4.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Fourth | 1.3.6.1.4.1.818.1.2.4.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Fourth | 1.3.6.1.4.1.818.1.2.4.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Fourth | 1.3.6.1.4.1.818.1.2.4.3 | |||
| NUM ioInterfaceNumAnalogue_Fourth | 1.3.6.1.4.1.818.1.2.4.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Fourth | 1.3.6.1.4.1.818.1.2.4.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Fourth | 1.3.6.1.4.1.818.1.2.4.4 | |||
| NTF ioAlarmGenericChange_Fourth | 1.3.6.1.4.1.818.1.2.4.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Fifth | 1.3.6.1.4.1.818.1.2.5 | |||
| ioInterfaceInputLine_Fifth | 1.3.6.1.4.1.818.1.2.5.1 | |||
| NUM ioInterfaceNumInputs_Fifth | 1.3.6.1.4.1.818.1.2.5.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Fifth | 1.3.6.1.4.1.818.1.2.5.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Fifth | 1.3.6.1.4.1.818.1.2.5.2 | |||
| NUM ioInterfaceNumOutput_Fifth | 1.3.6.1.4.1.818.1.2.5.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Fifth | 1.3.6.1.4.1.818.1.2.5.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Fifth | 1.3.6.1.4.1.818.1.2.5.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Fifth | 1.3.6.1.4.1.818.1.2.5.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Fifth | 1.3.6.1.4.1.818.1.2.5.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Fifth | 1.3.6.1.4.1.818.1.2.5.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Fifth | 1.3.6.1.4.1.818.1.2.5.3 | |||
| NUM ioInterfaceNumAnalogue_Fifth | 1.3.6.1.4.1.818.1.2.5.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Fifth | 1.3.6.1.4.1.818.1.2.5.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Fifth | 1.3.6.1.4.1.818.1.2.5.4 | |||
| NTF ioAlarmGenericChange_Fifth | 1.3.6.1.4.1.818.1.2.5.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Sixth | 1.3.6.1.4.1.818.1.2.6 | |||
| ioInterfaceInputLine_Sixth | 1.3.6.1.4.1.818.1.2.6.1 | |||
| NUM ioInterfaceNumInputs_Sixth | 1.3.6.1.4.1.818.1.2.6.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Sixth | 1.3.6.1.4.1.818.1.2.6.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Sixth | 1.3.6.1.4.1.818.1.2.6.2 | |||
| NUM ioInterfaceNumOutput_Sixth | 1.3.6.1.4.1.818.1.2.6.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Sixth | 1.3.6.1.4.1.818.1.2.6.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Sixth | 1.3.6.1.4.1.818.1.2.6.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Sixth | 1.3.6.1.4.1.818.1.2.6.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Sixth | 1.3.6.1.4.1.818.1.2.6.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Sixth | 1.3.6.1.4.1.818.1.2.6.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Sixth | 1.3.6.1.4.1.818.1.2.6.3 | |||
| NUM ioInterfaceNumAnalogue_Sixth | 1.3.6.1.4.1.818.1.2.6.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Sixth | 1.3.6.1.4.1.818.1.2.6.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Sixth | 1.3.6.1.4.1.818.1.2.6.4 | |||
| NTF ioAlarmGenericChange_Sixth | 1.3.6.1.4.1.818.1.2.6.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Seventh | 1.3.6.1.4.1.818.1.2.7 | |||
| ioInterfaceInputLine_Seventh | 1.3.6.1.4.1.818.1.2.7.1 | |||
| NUM ioInterfaceNumInputs_Seventh | 1.3.6.1.4.1.818.1.2.7.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Seventh | 1.3.6.1.4.1.818.1.2.7.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Seventh | 1.3.6.1.4.1.818.1.2.7.2 | |||
| NUM ioInterfaceNumOutput_Seventh | 1.3.6.1.4.1.818.1.2.7.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Seventh | 1.3.6.1.4.1.818.1.2.7.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Seventh | 1.3.6.1.4.1.818.1.2.7.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Seventh | 1.3.6.1.4.1.818.1.2.7.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Seventh | 1.3.6.1.4.1.818.1.2.7.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Seventh | 1.3.6.1.4.1.818.1.2.7.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Seventh | 1.3.6.1.4.1.818.1.2.7.3 | |||
| NUM ioInterfaceNumAnalogue_Seventh | 1.3.6.1.4.1.818.1.2.7.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Seventh | 1.3.6.1.4.1.818.1.2.7.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Seventh | 1.3.6.1.4.1.818.1.2.7.4 | |||
| NTF ioAlarmGenericChange_Seventh | 1.3.6.1.4.1.818.1.2.7.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| ioInterface_Eighth | 1.3.6.1.4.1.818.1.2.8 | |||
| ioInterfaceInputLine_Eighth | 1.3.6.1.4.1.818.1.2.8.1 | |||
| NUM ioInterfaceNumInputs_Eighth | 1.3.6.1.4.1.818.1.2.8.1.1 | NonNegativeInteger32 | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| ioInterfaceInputTable_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2 | not-accessible | A list of input line table entries. The number of entries is given by the value of ioInterfaceNumInputs. | |
| ioInterfaceInputEntry_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1 | not-accessible | An entry containing information applicable to a particular input line. | |
| NUM ioInterfaceInputLineIndex_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1.1 | PositiveInteger32 | not-accessible | The input line identifier. |
| STR ioInterfaceInputDescription_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this input line. |
| INT ioInterfaceInputStatus_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1.3 | INTEGER | read-only | The status of the input lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| INT ioInterfaceEdgeMode_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1.4 | INTEGER | read-write | Edge mode for input lines. This object specifies if the corresponding input line should be recognised immediately as active (edge mode on), or only when the state remains stable for at least the time specified by ioInterfaceAlarmDelay (edge mode off). EdgeMode is only meaningful when the object ioInterfaceAlarmMask is active. |
| INT ioInterfaceAlarmMask_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1.5 | INTEGER | read-write | Alarm functionality for the input line can be set active or inactive. |
| NUM ioInterfaceAlarmDelay_Eighth | 1.3.6.1.4.1.818.1.2.8.1.2.1.6 | NonNegativeInteger32 | read-write | Time delay during which an active input line has to be stable, prior to issue an alarm. Effective only when EdgeMode=off for the corresponding line. |
| ioInterfaceOutputLine_Eighth | 1.3.6.1.4.1.818.1.2.8.2 | |||
| NUM ioInterfaceNumOutput_Eighth | 1.3.6.1.4.1.818.1.2.8.2.1 | NonNegativeInteger32 | read-only | The number of output lines utilized by this device. This entry indicates the number of rows in the output line table. |
| ioInterfaceOutputTable_Eighth | 1.3.6.1.4.1.818.1.2.8.2.2 | not-accessible | A list of output line table entries. The number of entries is given by the value of ioInterfaceNumOutputs. | |
| ioInterfaceOutputEntry_Eighth | 1.3.6.1.4.1.818.1.2.8.2.2.1 | not-accessible | An entry containing information applicable to a particular output line. | |
| NUM ioInterfaceOutputLineIndex_Eighth | 1.3.6.1.4.1.818.1.2.8.2.2.1.1 | PositiveInteger32 | not-accessible | The output line identifier. |
| STR ioInterfaceOutputDescription_Eighth | 1.3.6.1.4.1.818.1.2.8.2.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this output line. |
| INT ioInterfaceOutputStatus_Eighth | 1.3.6.1.4.1.818.1.2.8.2.2.1.3 | INTEGER | read-write | The status of the output lines controlled by the device. When a bit is high (1), the associated line is 'active' |
| ioInterfaceAnalogueLine_Eighth | 1.3.6.1.4.1.818.1.2.8.3 | |||
| NUM ioInterfaceNumAnalogue_Eighth | 1.3.6.1.4.1.818.1.2.8.3.1 | NonNegativeInteger32 | read-only | The number of analogue lines utilized by this device. This entry indicates the number of rows in the analogue line table. |
| ioInterfaceAnalogueTable_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2 | not-accessible | A list of analogue line table entries. The number of entries is given by the value of ioInterfaceNumAnalogue. | |
| ioInterfaceAnalogueEntry_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1 | not-accessible | An entry containing information applicable to a particular analogue line. | |
| NUM ioInterfaceAnalogueLineIndex_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.1 | PositiveInteger32 | not-accessible | The analogue line identifier. |
| STR ioInterfaceAnalogueDescription_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.2 | DisplayString | read-write | A description of the alarm monitored by this analogue line. |
| I32 ioInterfaceAnalogueStatus_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.3 | Integer32 | read-only | Read analogue value 1, when the board support such functionality |
| I32 ioInterfaceAnalogueLowThreshold_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.4 | Integer32 | read-write | Low limit for the analogical value. When the analogical measurement comes under this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueHighThreshold_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.5 | Integer32 | read-write | High limit for the analogical value. When the analogical measurement comes higher than this limit, an alarm is issued. The limit can be disabled specifying the special floating point value which means 'not available'. |
| I32 ioInterfaceAnalogueResetLowThreshold_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.6 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the low alarm condition (hysteresis) |
| I32 ioInterfaceAnalogueResetHighThreshold_Eighth | 1.3.6.1.4.1.818.1.2.8.3.2.1.7 | Integer32 | read-write | After an alarm, value which has to be crossed by the analogue input, in order to remove the high alarm condition (hysteresis) |
| ioInterfaceTraps_Eighth | 1.3.6.1.4.1.818.1.2.8.4 | |||
| NTF ioAlarmGenericChange_Eighth | 1.3.6.1.4.1.818.1.2.8.4.0.1 | An generic change of a digital input/digital output/analog input has become active. | ||
| geModem | 1.3.6.1.4.1.818.1.3 | |||
| NUM geModemStatus | 1.3.6.1.4.1.818.1.3.1 | NonNegativeInteger32 | read-only | The status of the modem, controlled by the addressed device. The status word is a collection of bits, as specified below. The SNMP value NOSUCHNAME means 'status not (yet) available'. 1 modemStatOnline. There is a valid online connection. 2 modemStatError. The last operation has failed. The device will clear this bit when a new modem command is received. 4 unused (should be defined = 0). 8 unused (should be defined = 0). 16 modemStatDialling. The dialling procedure is pending. 32 modemStatBusy. The device is performing some operation, and can not be accessed, temporarily. 64 unused (should be defined = 0). 128 modemStatNoModem. The modem is not connected or not responding. 256 modemStatDCD. The DCD line status signal is on. 512 modemStatRing. The RING line status signal is on. 1024 modemStatCTS. The CTS line status signal is on. 2048 modemStatDSR. The DSR line status signal is on. 4096 unused (should be defined = 0). 8192 unused (should be defined = 0). 16384 unused (should be defined = 0). 32768 unused (should be defined = 0). |
| NUM geModemNumInitString | 1.3.6.1.4.1.818.1.3.2 | NonNegativeInteger32 | read-only | The number of modem init strings utilized by this ups. This entry indicates the number of rows in the init string table. |
| geModemInitStringTable | 1.3.6.1.4.1.818.1.3.3 | not-accessible | A list of init string table entries. The number of entries is given by the value of geModemNumInitString. | |
| geModemInitStringEntry | 1.3.6.1.4.1.818.1.3.3.1 | not-accessible | An entry containing information applicable to a particular Init string. | |
| NUM geModemInitStringLineIndex | 1.3.6.1.4.1.818.1.3.3.1.1 | PositiveInteger32 | not-accessible | The Init string line identifier. |
| STR geModemInitstring | 1.3.6.1.4.1.818.1.3.3.1.2 | DisplayString | read-write | A modem Init string. |
| NUM geModemNumPhoneNumber | 1.3.6.1.4.1.818.1.3.4 | NonNegativeInteger32 | read-only | The number of modem phone numbers utilized by this ups. This entry indicates the number of rows in the table. |
| geModemPhoneNumberTable | 1.3.6.1.4.1.818.1.3.5 | not-accessible | A list of phone number table entries. The number of entries is given by the value of geModemNumPhoneNumber. | |
| geModemPhoneNumberEntry | 1.3.6.1.4.1.818.1.3.5.1 | not-accessible | An entry containing information applicable to a particular phone number. | |
| NUM geModemPhoneNumberLineIndex | 1.3.6.1.4.1.818.1.3.5.1.1 | PositiveInteger32 | not-accessible | The phone number line identifier. |
| STR geModemPhoneNumber | 1.3.6.1.4.1.818.1.3.5.1.2 | DisplayString | read-write | A phone number. |
| geDevices | 1.3.6.1.4.1.818.1.100 | |||
| geDevicesDescriptions | 1.3.6.1.4.1.818.1.100.1 | |||
| advSNMPWebIntCard | 1.3.6.1.4.1.818.1.100.1.1 | |||
| snmpWebIntCard | 1.3.6.1.4.1.818.1.100.1.2 | |||
| snmpWebIntBox | 1.3.6.1.4.1.818.1.100.1.3 | |||
| snmpSWPFAgent | 1.3.6.1.4.1.818.1.100.1.4 | |||
| snmpSWJUMPAgent | 1.3.6.1.4.1.818.1.100.1.5 | |||
| geSoftware | 1.3.6.1.4.1.818.2 | |||
| geClient | 1.3.6.1.4.1.818.2.1 | |||
| STR geClientProcessor | 1.3.6.1.4.1.818.2.1.1 | DisplayString | read-only | The processor used by the clients machine. |
| STR geClientOperatingSystem | 1.3.6.1.4.1.818.2.1.2 | DisplayString | read-only | Operating system on which the client runs. |
| STR geClientJavaRuntimeVersion | 1.3.6.1.4.1.818.2.1.3 | DisplayString | read-only | JavaRuntimeVersion of the client machine. |
| NUM geClientMaxSizeOfLogfiles | 1.3.6.1.4.1.818.2.1.4 | NonNegativeInteger32 | read-write | The max. size of the logfiles in Kb. |
| STR geClientLanguageSelection | 1.3.6.1.4.1.818.2.1.5 | DisplayString | read-only | Shows the currently activated language of the client. |
| NUM geClientInternalCommunicationPort | 1.3.6.1.4.1.818.2.1.6 | NonNegativeInteger32 | read-write | UDP port used between server and client part. |
| INT geClientReboot | 1.3.6.1.4.1.818.2.1.7 | INTEGER | write-only | setting this object causes the protection client to reboot and activate new settings. |
| NUM geClientNumUPS | 1.3.6.1.4.1.818.2.1.8 | NonNegativeInteger32 | read-only | The number of UPSs utilized by this client. This entry indicates the number of rows in the table. |
| geClientUPSTable | 1.3.6.1.4.1.818.2.1.9 | not-accessible | A list of UPS table entries. The number of entries is given by the value of geClientNumUPS. | |
| geClientUPSEntry | 1.3.6.1.4.1.818.2.1.9.1 | not-accessible | An entry containing information applicable to a particular UPS. | |
| NUM geClientUPSLineIndex | 1.3.6.1.4.1.818.2.1.9.1.1 | PositiveInteger32 | not-accessible | The UPS line identifier. |
| STR geClientUPSName | 1.3.6.1.4.1.818.2.1.9.1.2 | DisplayString | read-write | The administrative name of the UPS. |
| INT geClientUPSCommunicationType | 1.3.6.1.4.1.818.2.1.9.1.3 | INTEGER | read-write | The method of communication. |
| STR geClientUPSCommunicationPort | 1.3.6.1.4.1.818.2.1.9.1.4 | DisplayString | read-write | The communication port. |
| STR geClientUPSReadCommName | 1.3.6.1.4.1.818.2.1.9.1.5 | DisplayString | read-write | The Read community string. Used when communication method is SNMP. |
| STR geClientUPSWriteCommName | 1.3.6.1.4.1.818.2.1.9.1.6 | DisplayString | read-write | The Write community string. Used when communication method is SNMP. |
| NUM geClientUPSCommRetries | 1.3.6.1.4.1.818.2.1.9.1.7 | NonNegativeInteger32 | read-write | Number of retries in case an answer times out. When the max. number of retries is reached a lost communication alarm will be raised. |
| INT geClientAlarmManagement | 1.3.6.1.4.1.818.2.1.9.1.8 | INTEGER | read-write | Alarm Management enabled or disabled. |
| NUM geClientPreDelay | 1.3.6.1.4.1.818.2.1.9.1.9 | NonNegativeInteger32 | read-only | The number of second an alarm needs to be active before action is taken. |
| INT geClientSystemShutdown | 1.3.6.1.4.1.818.2.1.9.1.10 | INTEGER | read-only | Specifies whether the client should shutdown the machine when an alarm situation occurs. |
| NUM geClientRuntime | 1.3.6.1.4.1.818.2.1.9.1.11 | NonNegativeInteger32 | read-only | The user defined preferable runtime. |
| INT geClientUPSShutdown | 1.3.6.1.4.1.818.2.1.9.1.12 | INTEGER | read-only | Defines whether the UPS will be shut down after an Operating System shutdown. |
| NUM geClientMaxScriptExecutionTime | 1.3.6.1.4.1.818.2.1.9.1.13 | NonNegativeInteger32 | read-only | The max. number of seconds the script file is allowed to run. |
| NUM geClientGraceperiod | 1.3.6.1.4.1.818.2.1.9.1.14 | NonNegativeInteger32 | read-only | The time between start of the Operating System shutdown and the UPS shutdown. |
| NUM geClientNumTests | 1.3.6.1.4.1.818.2.1.20 | NonNegativeInteger32 | read-only | The number of scheduled tests. This entry indicates the number of rows in the table. |
| geClientTestTable | 1.3.6.1.4.1.818.2.1.21 | not-accessible | A list of test table entries. The number of entries is given by the value of geClientNumTests. | |
| geClientTestEntry | 1.3.6.1.4.1.818.2.1.21.1 | not-accessible | An entry containing information applicable to a particular Test. | |
| NUM geClientTestLineIndex | 1.3.6.1.4.1.818.2.1.21.1.1 | PositiveInteger32 | not-accessible | The test line identifier. |
| I32 geClientTestId | 1.3.6.1.4.1.818.2.1.21.1.2 | Integer32 | read-write | The test Id. |
| I32 geClientTestDayTime | 1.3.6.1.4.1.818.2.1.21.1.3 | Integer32 | read-write | The time on which the test is due to be performed. |
| I32 geClientTestWeekDay | 1.3.6.1.4.1.818.2.1.21.1.4 | Integer32 | read-write | The day in the week on which the test will be performed. |
| I32 geClientTestMonthDay | 1.3.6.1.4.1.818.2.1.21.1.5 | Integer32 | read-write | The month day on which the test will be performed. |
| NUM geClientNumShutdowns | 1.3.6.1.4.1.818.2.1.30 | NonNegativeInteger32 | read-only | The number of scheduled Shutdowns. This entry indicates the number of rows in the table. |
| geClientShutdownTable | 1.3.6.1.4.1.818.2.1.31 | not-accessible | A list of Shutdown table entries. The number of entries is given by the value of geClientNumShutdowns. | |
| geClientShutdownEntry | 1.3.6.1.4.1.818.2.1.31.1 | not-accessible | An entry containing information applicable to a particular Shutdown. | |
| NUM geClientShutdownLineIndex | 1.3.6.1.4.1.818.2.1.31.1.1 | PositiveInteger32 | not-accessible | The Shutdown line identifier. |
| I32 geClientShutdownDelay | 1.3.6.1.4.1.818.2.1.31.1.2 | Integer32 | read-write | The delay before start of the Shutdown. |
| I32 geClientShutdownDuration | 1.3.6.1.4.1.818.2.1.31.1.3 | Integer32 | read-write | The duration of the Shutdown. |
| I32 geClientShutdownDayTime | 1.3.6.1.4.1.818.2.1.31.1.4 | Integer32 | read-write | The time on which the Shutdown is due to be performed. |
| I32 geClientShutdownWeekDay | 1.3.6.1.4.1.818.2.1.31.1.5 | Integer32 | read-write | The day in the week on which the Shutdown will be performed. |
| I32 geClientShutdownMonthDay | 1.3.6.1.4.1.818.2.1.31.1.6 | Integer32 | read-write | The month day on which the Shutdown will be performed. |
| I32 geClientShutdownPreWarnTime | 1.3.6.1.4.1.818.2.1.31.1.7 | Integer32 | read-write | The number of seconds before start of the shutdown a pre warning will be raised. |
| geAgent | 1.3.6.1.4.1.818.3 | |||
| geAgentConfig | 1.3.6.1.4.1.818.3.1 | |||
| NUM geAgentUDPPort | 1.3.6.1.4.1.818.3.1.1 | NonNegativeInteger32 | read-write | The UDP port number used by agent. |
| NUM geAgentWebServerPort | 1.3.6.1.4.1.818.3.1.2 | NonNegativeInteger32 | read-write | The UDP port number used by the HTTP server. |
| STR geAgentComPort | 1.3.6.1.4.1.818.3.1.3 | DisplayString | read-write | The COM port used by the agent. |
| NUM geAgentComTimeout | 1.3.6.1.4.1.818.3.1.4 | NonNegativeInteger32 | read-write | The Timeout delay in seconds of the serial communication. |
| NUM geAgentComRetries | 1.3.6.1.4.1.818.3.1.5 | NonNegativeInteger32 | read-write | The number of retries when serial communication fails. |
| STR geAgentReadCommunity | 1.3.6.1.4.1.818.3.1.6 | DisplayString | read-write | The read community string of the agent. |
| STR geAgentWriteCommunity | 1.3.6.1.4.1.818.3.1.7 | DisplayString | read-write | The write community string of the agent. |
| STR geAgentResponsibleEmailAddress | 1.3.6.1.4.1.818.3.1.8 | DisplayString | read-write | The email address of the responsible person for this agent. |
| INT geRFCTrapsToSend | 1.3.6.1.4.1.818.3.1.9 | INTEGER | read-write | This object defines whether RFC traps need to be send. The bit value 1 indicates that the traps needs to be send, while value 0 does not result in a trap to send. |
| NUM geIMVTrapsToSend | 1.3.6.1.4.1.818.3.1.10 | NonNegativeInteger32 | read-write | This object defines for which device(s) IMV traps need to be send. The bit value 1 indicates that the trap needs to be send, while value 0 does not result in a trap to send. The value presents the devices as a mask: 1 GenericUPS 2 FirstUPS 4 SecondUPS 8 ThirdUPS 16 FourthUPS 32 FifthUPS 64 SixthUPS 128 SeventhUPS 256 EigthUPS 512 IOInterface |
| geAgentTraps | 1.3.6.1.4.1.818.3.2 | |||
| NUM geAgentNumTraps | 1.3.6.1.4.1.818.3.2.1 | NonNegativeInteger32 | read-only | The number of configured traps. This entry indicates the number of rows in the table. |
| geAgentTrapTable | 1.3.6.1.4.1.818.3.2.2 | not-accessible | A list of trap table entries. The number of entries is given by the value of geAgentNumTraps. | |
| geAgentTrapEntry | 1.3.6.1.4.1.818.3.2.2.1 | not-accessible | An entry containing information applicable to a particular trap target. | |
| NUM geAgentTrapLineIndex | 1.3.6.1.4.1.818.3.2.2.1.1 | PositiveInteger32 | not-accessible | The Trap line identifier. |
| STR geAgentTrapAddress | 1.3.6.1.4.1.818.3.2.2.1.2 | DisplayString | read-write | The destination IP-address of the trap. |
| STR geAgentTrapCommunity | 1.3.6.1.4.1.818.3.2.2.1.3 | DisplayString | read-write | The communication string used by the trap. |
| I32 geAgentTrapPort | 1.3.6.1.4.1.818.3.2.2.1.4 | Integer32 | read-write | The UDP port on the receiving side. |
RFC description
Manages UPS systems for GE hardware including battery, input, output, and alarm monitoring.