All MIBs › ELTEK-DISTRIBUTED-MIB
Organization: ELTEK dcSystem MIB Working Group
Last Updated: 2011--0-6-
Category: Domain: Power/UPS, Vendor: Eltek
Description: Eltek distributed power management MIB for monitoring distributed rectifier systems and their individual components.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is ELTEK-DISTRIBUTED-MIB?
This is an Eltek private enterprise MIB for the company's distributed DC power/rectifier systems (SmartPack/WebPower controller family, spanning multiple hardware branches like AL175, AL6000, and Aeongold), used in telecom power plants. It exposes system-level configuration (trap repeat rate, refresh interval, control-unit enumeration) alongside a control-unit table and configurable digital/analog inputs used to monitor individual rectifier or battery-plant components. Its monitoring focus is hardware status of power infrastructure: tracking system time synchronization, the number and identity of distributed control units, per-unit input states, and trap notification behavior, all of which reveal whether a distributed rectifier/battery plant component has failed or gone out of sync. It defines its own branch-versioned OID structure (branches 1 through 9+ for different product generations) rather than relying on external standard MIBs. It's typically deployed in telecom central-office or cell-site DC power plant monitoring via SNMP. Engineers can download the ELTEK-DISTRIBUTED-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in ELTEK-DISTRIBUTED-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Eltek SmartPack/WebPower DC power rectifier system
Monitoring Examples
An operator would poll systemControlUnitTable (indexed by systemControlUnitIndex, keyed to inputControlUnitID) to enumerate all distributed control units in a power plant and detect if one has dropped off the poll. systemTimeTime confirms the plant controller's clock is synchronized, important for correlating alarm timestamps across units. The inputUserConfigurable1/2/3 objects expose site-specific analog/digital inputs (e.g., a door sensor or auxiliary alarm) that an admin would map to specific hardware conditions per deployment, and systemSendOffTrap combined with systemTrapRepeatRate governs how aggressively the unit re-sends unacknowledged alarms.
What Can Be Monitored
- control unit count/identity
- system time sync
- trap repeat rate
- user-configurable input status
- alarm/trap send state
This MIB depends on
Related MIBs
Imported Objects
From SNMPv2-CONF
| NOTIFICATION-GROUP |
From SNMPv2-SMI
| Counter32 | |
| Integer32 | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| enterprises |
From SNMPv2-TC
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| eltek | 1.3.6.1.4.1.12148 | An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3 and compack 1.xx) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack w/WebPower sw V4.6, Smartpack2 V1.1) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.7, ComPack V1.04, Smartpack2 V1.1, V1.2) | ||
| eltekDistributedPlantV7 | 1.3.6.1.4.1.12148.9 | |||
| controlSystem | 1.3.6.1.4.1.12148.9.1 | |||
| systemTime | 1.3.6.1.4.1.12148.9.1.1 | |||
| STR systemTimeTime | 1.3.6.1.4.1.12148.9.1.1.1 | DisplayString | read-only | The system date and time. Used for event timestamps and logging |
| INT systemInfoRefresh | 1.3.6.1.4.1.12148.9.1.2 | INTEGER | read-write | This is a push button function that will rebuild all the dynamic SNMP tables. When control units are removed or added this function must be executed to make sure the tables are updated. |
| I32 systemTrapRepeatRate | 1.3.6.1.4.1.12148.9.1.3 | Integer32 | read-write | This object sets the repeat rate of any active traps, in minutes. Entering 0 (zero) will prevent repeating traps - one trap only will be sent per alarm event. |
| INT systemSendOffTrap | 1.3.6.1.4.1.12148.9.1.4 | INTEGER | read-write | A separate off-trap will be issued when an alarm condition goes off, if this flag is set to 1. Entering 0 (zero) will prevent OFF traps from being transmitted. |
| I32 systemNumOfControlUnits | 1.3.6.1.4.1.12148.9.1.5 | Integer32 | read-only | The number of Control units in a distributed system. |
| I32 systemControlUnitIndex | 1.3.6.1.4.1.12148.9.1.6 | Integer32 | accessible-for-notify | Index used for navigating in the table for configurable inputs. |
| systemControlUnitTable | 1.3.6.1.4.1.12148.9.1.7 | not-accessible | This table contains the status of the programmable inputs. There is one row for each Control unit. | |
| systemControlUnitEntry | 1.3.6.1.4.1.12148.9.1.7.1 | not-accessible | ||
| I32 inputControlUnitID | 1.3.6.1.4.1.12148.9.1.7.1.1 | Integer32 | read-only | The ID of which Control unit to be read. |
| INT inputUserConfigurable1 | 1.3.6.1.4.1.12148.9.1.7.1.2 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable2 | 1.3.6.1.4.1.12148.9.1.7.1.3 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable3 | 1.3.6.1.4.1.12148.9.1.7.1.4 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable4 | 1.3.6.1.4.1.12148.9.1.7.1.5 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable5 | 1.3.6.1.4.1.12148.9.1.7.1.6 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable6 | 1.3.6.1.4.1.12148.9.1.7.1.7 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable7 | 1.3.6.1.4.1.12148.9.1.7.1.8 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable8 | 1.3.6.1.4.1.12148.9.1.7.1.9 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable9 | 1.3.6.1.4.1.12148.9.1.7.1.10 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT inputUserConfigurable10 | 1.3.6.1.4.1.12148.9.1.7.1.11 | INTEGER | read-only | Programmable input status. The description of the input is found in the systemControlUnitInputTable |
| INT systemLinkStatus | 1.3.6.1.4.1.12148.9.1.8 | INTEGER | read-only | A flag showing the status of the serial port used between the HEIDI Webpower adapter or embedded WEB/SNMP card and the Smartpack Control system. If this flag shows status linkdown, the propable cause is that the wrong baudrate is set, which again is likely to happen when booting a brand new board. Execute a 'systemInitiateEEPROM' command to fix. Not applicable for ComPack control unit |
| INT systemInitiateEEPROM | 1.3.6.1.4.1.12148.9.1.9 | INTEGER | read-write | Pushbutton function that initiates a forced write of default data to the SB70/SB72 eeprom. This function is used for productiontest only. The 3rd party OS used in this application are not able to write default data to EEPROM at boot time. A minimum set of configuration is thus created in RAM. A production test facility must therefore run this command as a part of the production test for the unit to function properly. |
| I32 systemLastDigInput | 1.3.6.1.4.1.12148.9.1.10 | Integer32 | accessible-for-notify | The last Prog.Input that generated a trap. Used by Traps only. |
| C32 systemTrapCounter | 1.3.6.1.4.1.12148.9.1.11 | Counter32 | accessible-for-notify | The number of times a trap has been repeated.. Only acessible for Traps. |
| I32 systemHeartBeatTrapRepeatRate | 1.3.6.1.4.1.12148.9.1.12 | Integer32 | read-write | The repeat rate for the systemHeartBeatTrap. Setting this value to zero will disable the HeartBeatTrap. |
| INT systemResetManualAlarms | 1.3.6.1.4.1.12148.9.1.13 | INTEGER | read-write | A pushutton that resets all manually resettable alarms in the controlsystem. Alarms that is not manually resettable will not be affected by this. |
| I32 systemControlUnitInputIndex | 1.3.6.1.4.1.12148.9.1.14 | Integer32 | accessible-for-notify | Index used for navigating in the table for configurable inputs. |
| systemControlUnitInputTable | 1.3.6.1.4.1.12148.9.1.15 | not-accessible | This table contains the description of the programmable inputs. There is one row for each Control unit. Programmable input alarms will have description attached to the traps that explains the alarm. Default description is: ProgInput .x | |
| systemControlUnitInputEntry | 1.3.6.1.4.1.12148.9.1.15.1 | not-accessible | ||
| I32 inputUnitID | 1.3.6.1.4.1.12148.9.1.15.1.1 | Integer32 | read-only | The ID of which Control unit to be read. |
| STR inputUserConfigurableText1 | 1.3.6.1.4.1.12148.9.1.15.1.2 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .1. |
| STR inputUserConfigurableText2 | 1.3.6.1.4.1.12148.9.1.15.1.3 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .2. |
| STR inputUserConfigurableText3 | 1.3.6.1.4.1.12148.9.1.15.1.4 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .3. |
| STR inputUserConfigurableText4 | 1.3.6.1.4.1.12148.9.1.15.1.5 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .4. |
| STR inputUserConfigurableText5 | 1.3.6.1.4.1.12148.9.1.15.1.6 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .5. |
| STR inputUserConfigurableText6 | 1.3.6.1.4.1.12148.9.1.15.1.7 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .6. |
| STR inputUserConfigurableText7 | 1.3.6.1.4.1.12148.9.1.15.1.8 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .7. |
| STR inputUserConfigurableText8 | 1.3.6.1.4.1.12148.9.1.15.1.9 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .8. |
| STR inputUserConfigurableText9 | 1.3.6.1.4.1.12148.9.1.15.1.10 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .9. |
| STR inputUserConfigurableText10 | 1.3.6.1.4.1.12148.9.1.15.1.11 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .10. |
| INT systemResetCtrlSystem | 1.3.6.1.4.1.12148.9.1.16 | INTEGER | read-write | A pushbutton function that resets the control system. Configuration data will be kept. |
| ioUnits | 1.3.6.1.4.1.12148.9.1.17 | |||
| I32 ioUnitNumberOfUnits | 1.3.6.1.4.1.12148.9.1.17.1 | Integer32 | read-only | |
| I32 ioUnitsIndex | 1.3.6.1.4.1.12148.9.1.17.2 | Integer32 | accessible-for-notify | |
| ioUnitsTable | 1.3.6.1.4.1.12148.9.1.17.3 | not-accessible | ||
| ioUnitsEntry | 1.3.6.1.4.1.12148.9.1.17.3.1 | not-accessible | ||
| I32 ioUnitID | 1.3.6.1.4.1.12148.9.1.17.3.1.1 | Integer32 | read-only | |
| I32 ioUnitOutDoorTemp1 | 1.3.6.1.4.1.12148.9.1.17.3.1.2 | Integer32 | read-only | The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. |
| I32 ioUnitOutDoorTemp2 | 1.3.6.1.4.1.12148.9.1.17.3.1.3 | Integer32 | read-only | The measured value of the temperature input. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. |
| I32 ioUnitFanSpeed1 | 1.3.6.1.4.1.12148.9.1.17.3.1.4 | Integer32 | read-only | The speed of the cooling/ circulation fan. The speed is a percentage of max RPM. |
| I32 ioUnitFanSpeedDeltaValue1 | 1.3.6.1.4.1.12148.9.1.17.3.1.5 | Integer32 | read-only | The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value. |
| I32 ioUnitFanSpeed2 | 1.3.6.1.4.1.12148.9.1.17.3.1.6 | Integer32 | read-only | The speed of the cooling/ circulation fan. The speed is a percentage of max RPM. |
| I32 ioUnitFanSpeedDeltaValue2 | 1.3.6.1.4.1.12148.9.1.17.3.1.7 | Integer32 | read-only | The deviation of the cooling/circulation fans speed set value. Is a percentage of the desired value. |
| STR ioUnitProgInputText1 | 1.3.6.1.4.1.12148.9.1.17.3.1.8 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .1 |
| INT ioUnitProgInputStatus1 | 1.3.6.1.4.1.12148.9.1.17.3.1.9 | INTEGER | read-only | Programmable input status. |
| STR ioUnitProgInputText2 | 1.3.6.1.4.1.12148.9.1.17.3.1.10 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .2 |
| INT ioUnitProgInputStatus2 | 1.3.6.1.4.1.12148.9.1.17.3.1.11 | INTEGER | read-only | Programmable input status. |
| STR ioUnitProgInputText3 | 1.3.6.1.4.1.12148.9.1.17.3.1.12 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .3 |
| INT ioUnitProgInputStatus3 | 1.3.6.1.4.1.12148.9.1.17.3.1.13 | INTEGER | read-only | Programmable input status. |
| STR ioUnitProgInputText4 | 1.3.6.1.4.1.12148.9.1.17.3.1.14 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .4 |
| INT ioUnitProgInputStatus4 | 1.3.6.1.4.1.12148.9.1.17.3.1.15 | INTEGER | read-only | Programmable input status. |
| STR ioUnitProgInputText5 | 1.3.6.1.4.1.12148.9.1.17.3.1.16 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .5 |
| INT ioUnitProgInputStatus5 | 1.3.6.1.4.1.12148.9.1.17.3.1.17 | INTEGER | read-only | Programmable input status. |
| STR ioUnitProgInputText6 | 1.3.6.1.4.1.12148.9.1.17.3.1.18 | DisplayString | read-only | Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .6 |
| INT ioUnitProgInputStatus6 | 1.3.6.1.4.1.12148.9.1.17.3.1.19 | INTEGER | read-only | Programmable input status. |
| I32 ioUnitProgInputValue1 | 1.3.6.1.4.1.12148.9.1.17.3.1.20 | Integer32 | read-only | The value read on input. |
| I32 ioUnitProgInputValue2 | 1.3.6.1.4.1.12148.9.1.17.3.1.21 | Integer32 | read-only | The value read on input. |
| I32 ioUnitProgInputValue3 | 1.3.6.1.4.1.12148.9.1.17.3.1.22 | Integer32 | read-only | The value read on input. |
| I32 ioUnitProgInputValue4 | 1.3.6.1.4.1.12148.9.1.17.3.1.23 | Integer32 | read-only | The value read on input. |
| I32 ioUnitProgInputValue5 | 1.3.6.1.4.1.12148.9.1.17.3.1.24 | Integer32 | read-only | The value read on input. |
| I32 ioUnitProgInputValue6 | 1.3.6.1.4.1.12148.9.1.17.3.1.25 | Integer32 | read-only | The value read on input. |
| INT systemServiceMode | 1.3.6.1.4.1.12148.9.1.18 | INTEGER | read-write | This is a switch function to activate (1) or deactivate (0) servicemode. Status can also be read. Servicemode prevent the system to operate relays or send traps or mail. |
| dcSystem | 1.3.6.1.4.1.12148.9.2 | |||
| dcPlant | 1.3.6.1.4.1.12148.9.2.1 | |||
| systemSiteInfo | 1.3.6.1.4.1.12148.9.2.1.3 | |||
| STR systemSiteInfoCustomer | 1.3.6.1.4.1.12148.9.2.1.3.1 | DisplayString | read-only | The Customer name (as stored in the Control Unit). |
| STR systemSiteInfoLocation | 1.3.6.1.4.1.12148.9.2.1.3.2 | DisplayString | read-only | The system/site Location details (as stored in the Control Unit). |
| STR systemSiteInfoMessage1 | 1.3.6.1.4.1.12148.9.2.1.3.3 | DisplayString | read-only | The system/site Info Message record #1 (as stored in the Control Unit). 31 Bytes. |
| STR systemSiteInfoMessage2 | 1.3.6.1.4.1.12148.9.2.1.3.4 | DisplayString | read-only | The system/site Info Message record #2 (as stored in the Control Unit). 31 Bytes. |
| STR systemSiteInfoInstalledDate | 1.3.6.1.4.1.12148.9.2.1.3.5 | DisplayString | read-only | The system's Installed Date text string (as stored in the Control Unit) 16bytes. |
| INT systemSiteInfoControllerType | 1.3.6.1.4.1.12148.9.2.1.3.6 | INTEGER | read-only | The system Controller Module currently connected. 0 = AL175 1 = AL4000 (Aeon Gold) 2 = AL6000 3 = AL175OEM 4 = MCU 5 = SmartPack 6 = ComPack |
| STR systemSiteInfoSystemSeriaNum | 1.3.6.1.4.1.12148.9.2.1.3.7 | DisplayString | read-only | The serial number for the complete system. |
| STR systemSiteInfoControllerSeriaNum | 1.3.6.1.4.1.12148.9.2.1.3.8 | DisplayString | read-only | The serial number for Control unit 1. |
| INT systemNominalVoltage | 1.3.6.1.4.1.12148.9.2.1.4 | INTEGER | read-only | The nominal voltage rating. 24V/48V/60V systems. 0=48V 1=24V 2=Not used 3=Not used 4=60V |
| INT systemOperationalStatus | 1.3.6.1.4.1.12148.9.2.2 | INTEGER | read-only | A summary status showing if the system is testing, boosting, floating etc. 0=Float, voltage regulated 1=Float, temperature comp. regulated; 2=boost 3=battery test |
| battery | 1.3.6.1.4.1.12148.9.3 | |||
| STR batteryName | 1.3.6.1.4.1.12148.9.3.1 | DisplayString | read-only | A descriptive name of the battery installed in the system. |
| I32 batteryVoltage | 1.3.6.1.4.1.12148.9.3.2 | Integer32 | read-only | The measured battery voltage. |
| I32 batteryCurrent | 1.3.6.1.4.1.12148.9.3.3 | Integer32 | read-only | The measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the batteries. Positive battery current indicates charging of the batteries. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| I32 batteryTemp | 1.3.6.1.4.1.12148.9.3.4 | Integer32 | read-only | The highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit. |
| INT batteryBreakerStatus | 1.3.6.1.4.1.12148.9.3.5 | INTEGER | read-only | The state of the battery fuses/breakers can be either normal(0) or alarm(1). |
| INT batteryChargeCurrentLimitCtrl | 1.3.6.1.4.1.12148.9.3.6 | INTEGER | read-write | Enable/disable of the battery charge current limitation feature; 0=disable, 1=enable. |
| I32 batteryChargeCurrentLimitValue | 1.3.6.1.4.1.12148.9.3.7 | Integer32 | read-write | Battery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT batteryTempCompEnable | 1.3.6.1.4.1.12148.9.3.8 | INTEGER | read-write | Enable (0) or Disable (1) of Battery Temperature Compensated output regulation mode |
| I32 batteryFloatVoltConfig | 1.3.6.1.4.1.12148.9.3.9 | Integer32 | read-write | The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging. |
| I32 batteryBoostVoltConfig | 1.3.6.1.4.1.12148.9.3.10 | Integer32 | read-write | The Voltage at which the DC System boost charges the batteries. |
| I32 batteryHighMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.11 | Integer32 | read-write | The Major High Battery Voltage alarm limit set voltage |
| I32 batteryHighMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.12 | Integer32 | read-write | The Minor High Battery Voltage alarm limit set voltage |
| I32 batteryLowMajorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.13 | Integer32 | read-write | The Major Low Battery Voltage Alarm limit set voltage |
| I32 batteryLowMinorAlarmVoltageConfig | 1.3.6.1.4.1.12148.9.3.14 | Integer32 | read-write | The Minor Low Battery Voltage Alarm limit set voltage |
| INT batteryStartManualTest | 1.3.6.1.4.1.12148.9.3.15 | INTEGER | read-write | This pushbutton will start or stop a manual battery test if the system allows it. |
| INT batteryStartManualBoost | 1.3.6.1.4.1.12148.9.3.16 | INTEGER | read-write | This pushbutton will start or stop a manual battery boost if the system allows it. |
| batteryLVD | 1.3.6.1.4.1.12148.9.3.17 | |||
| INT batteryLVDStatus | 1.3.6.1.4.1.12148.9.3.17.1 | INTEGER | read-only | The Battery Contactor is connected(0), disconnected(1) or disabled(2) |
| I32 batteryLVDDisconnectVoltage | 1.3.6.1.4.1.12148.9.3.17.2 | Integer32 | read-write | The Battery Contactors Disconnect Voltage |
| I32 batteryLVDConnectVoltage | 1.3.6.1.4.1.12148.9.3.17.3 | Integer32 | read-write | The Battery Contactors Reconnect Voltage |
| I32 batteryBanksNumofBanks | 1.3.6.1.4.1.12148.9.3.18 | Integer32 | read-only | The number of Control units that is used to measure battery parameters. |
| batteryBanks | 1.3.6.1.4.1.12148.9.3.19 | |||
| I32 batterySymmetryDeltaLimitVoltage | 1.3.6.1.4.1.12148.9.3.19.1 | Integer32 | read-write | The allowable deviation of the symmetry voltage from the theoretical. Exceeding this value in either direction (+/-) causes an alarm state. |
| I32 batteryBanksIndex | 1.3.6.1.4.1.12148.9.3.19.2 | Integer32 | accessible-for-notify | Index used for navigating the rows 1..8 of batteryBanksTable |
| batteryBanksTable | 1.3.6.1.4.1.12148.9.3.19.3 | not-accessible | A table of up to 8 battery banks. Each banks may have up to 8 symmetry measuments. | |
| batteryBanksEntry | 1.3.6.1.4.1.12148.9.3.19.3.1 | not-accessible | ||
| I32 batteryBankID | 1.3.6.1.4.1.12148.9.3.19.3.1.1 | Integer32 | read-only | The ID of the selected row in the table. i.e. the battery bank. |
| INT batteryBanksSymmetry1enable | 1.3.6.1.4.1.12148.9.3.19.3.1.2 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry1status | 1.3.6.1.4.1.12148.9.3.19.3.1.3 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry1deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.4 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry2enable | 1.3.6.1.4.1.12148.9.3.19.3.1.5 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry2status | 1.3.6.1.4.1.12148.9.3.19.3.1.6 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry2deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.7 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry3enable | 1.3.6.1.4.1.12148.9.3.19.3.1.8 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry3status | 1.3.6.1.4.1.12148.9.3.19.3.1.9 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry3deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.10 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry4enable | 1.3.6.1.4.1.12148.9.3.19.3.1.11 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry4status | 1.3.6.1.4.1.12148.9.3.19.3.1.12 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry4deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.13 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry5enable | 1.3.6.1.4.1.12148.9.3.19.3.1.14 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry5status | 1.3.6.1.4.1.12148.9.3.19.3.1.15 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry5deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.16 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry6enable | 1.3.6.1.4.1.12148.9.3.19.3.1.17 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry6status | 1.3.6.1.4.1.12148.9.3.19.3.1.18 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry6deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.19 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry7enable | 1.3.6.1.4.1.12148.9.3.19.3.1.20 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry7status | 1.3.6.1.4.1.12148.9.3.19.3.1.21 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry7deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.22 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| INT batteryBanksSymmetry8enable | 1.3.6.1.4.1.12148.9.3.19.3.1.23 | INTEGER | read-write | Enable/Disable the individual symmetry input. If disabled this will read 0 volts and the alarm flag will be turned off. |
| INT batteryBanksSymmetry8status | 1.3.6.1.4.1.12148.9.3.19.3.1.24 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryBanksSymmetry8deltaVoltage | 1.3.6.1.4.1.12148.9.3.19.3.1.25 | Integer32 | read-only | The difference between the measured value and the expected value. The expected value is calculated by taking the measured total batteryvoltage and divide it with the number of battery blocks. You'll then have the theoretical correct value for each battery block. |
| I32 batteryBanksNumberOfStrings | 1.3.6.1.4.1.12148.9.3.19.4 | Integer32 | read-only | Number of strings in the power system. |
| I32 batteryBanksExtensionIndex | 1.3.6.1.4.1.12148.9.3.19.5 | Integer32 | accessible-for-notify | Index used for navigating the rows 1..14 of batteryBanksExtensionTable |
| batteryBanksExtensionTable | 1.3.6.1.4.1.12148.9.3.19.6 | not-accessible | This table shows the measured value on the symmetry inputs. | |
| batteryBanksExtensionEntry | 1.3.6.1.4.1.12148.9.3.19.6.1 | not-accessible | ||
| I32 batteryBanksExtensionID | 1.3.6.1.4.1.12148.9.3.19.6.1.1 | Integer32 | read-only | The ID of the selected row in the table. i.e. the battery bank. |
| I32 batteryBanksExtensionSymmetryInputValue1 | 1.3.6.1.4.1.12148.9.3.19.6.1.2 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue2 | 1.3.6.1.4.1.12148.9.3.19.6.1.3 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue3 | 1.3.6.1.4.1.12148.9.3.19.6.1.4 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue4 | 1.3.6.1.4.1.12148.9.3.19.6.1.5 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue5 | 1.3.6.1.4.1.12148.9.3.19.6.1.6 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue6 | 1.3.6.1.4.1.12148.9.3.19.6.1.7 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue7 | 1.3.6.1.4.1.12148.9.3.19.6.1.8 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryBanksExtensionSymmetryInputValue8 | 1.3.6.1.4.1.12148.9.3.19.6.1.9 | Integer32 | read-only | The measured voltage on the symmetry input. |
| batteryCapacityData | 1.3.6.1.4.1.12148.9.3.20 | |||
| I32 batteryTimeToDisconnect | 1.3.6.1.4.1.12148.9.3.20.1 | Integer32 | read-only | Remaining time to low voltage battery disconnect. |
| I32 batteryCapacityLeft | 1.3.6.1.4.1.12148.9.3.20.2 | Integer32 | read-only | Capacity left in the battery. |
| I32 batteryCapacityUsed | 1.3.6.1.4.1.12148.9.3.20.3 | Integer32 | read-only | Capacity consumed. |
| I32 batteryCapacityTotal | 1.3.6.1.4.1.12148.9.3.20.4 | Integer32 | read-only | This is the total Capacity of the battery. This value is the installed capacity compensated with the last battery tests quality level |
| I32 batteryQuality | 1.3.6.1.4.1.12148.9.3.20.5 | Integer32 | read-only | This is the battery quality (%) of the latest battery test. |
| batteryMonitorUnits | 1.3.6.1.4.1.12148.9.3.21 | |||
| I32 battmonNumberOfUnits | 1.3.6.1.4.1.12148.9.3.21.1 | Integer32 | read-only | Number of battery monitor units in the power system. |
| I32 battmonUnitsIndex | 1.3.6.1.4.1.12148.9.3.21.2 | Integer32 | accessible-for-notify | Index used for navigating the rows 1..14 of battmonUnitsTable |
| battmonUnitsTable | 1.3.6.1.4.1.12148.9.3.21.3 | not-accessible | A table of up to 14 battery monitor control units. | |
| battmonUnitsEntry | 1.3.6.1.4.1.12148.9.3.21.3.1 | not-accessible | ||
| I32 batteryMonitorID | 1.3.6.1.4.1.12148.9.3.21.3.1.1 | Integer32 | read-only | The ID of the selected row |
| INT batteryMonitorSymmetry1status | 1.3.6.1.4.1.12148.9.3.21.3.1.2 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryMonitorSymmetry1InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.3 | Integer32 | read-only | The measured voltage on the symmetry input. |
| INT batteryMonitorSymmetry2status | 1.3.6.1.4.1.12148.9.3.21.3.1.4 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryMonitorSymmetry2InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.5 | Integer32 | read-only | The measured voltage on the symmetry input. |
| INT batteryMonitorSymmetry3status | 1.3.6.1.4.1.12148.9.3.21.3.1.6 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryMonitorSymmetry3InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.7 | Integer32 | read-only | The measured voltage on the symmetry input. |
| INT batteryMonitorSymmetry4status | 1.3.6.1.4.1.12148.9.3.21.3.1.8 | INTEGER | read-only | Contains the status of this battery symmetry input. Possible States: 0=Normal 1=MinorAlarm 2=MajorAlarm 3=Disabled 4=Error |
| I32 batteryMonitorSymmetry4InputValue | 1.3.6.1.4.1.12148.9.3.21.3.1.9 | Integer32 | read-only | The measured voltage on the symmetry input. |
| I32 batteryMonitorCurrentValue | 1.3.6.1.4.1.12148.9.3.21.3.1.10 | Integer32 | read-only | The measured current to/from the battery. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT batteryMonitorFuseStatus | 1.3.6.1.4.1.12148.9.3.21.3.1.11 | INTEGER | read-only | The state of the battery fuse/breaker can be either normal(0) or alarm(1). |
| I32 batteryMonitorTemperature | 1.3.6.1.4.1.12148.9.3.21.3.1.12 | Integer32 | read-only | The battery temperature. |
| I32 batteryHighMajorTempAlarmLevel | 1.3.6.1.4.1.12148.9.3.22 | Integer32 | read-write | This is the Major High Temperature Alarm level. |
| I32 batteryHighMinorTempAlarmLevel | 1.3.6.1.4.1.12148.9.3.23 | Integer32 | read-write | This is the Minor High Temperature Alarm level. |
| loadDistribution | 1.3.6.1.4.1.12148.9.4 | |||
| I32 loadDistributionCurrent | 1.3.6.1.4.1.12148.9.4.1 | Integer32 | read-only | The total load current Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadDistributionBreakerStatus | 1.3.6.1.4.1.12148.9.4.2 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| loadDistributionLVDStatus | 1.3.6.1.4.1.12148.9.4.3 | |||
| INT loadLVD1Enable | 1.3.6.1.4.1.12148.9.4.3.1 | INTEGER | read-only | The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. |
| INT loadLVD1Status | 1.3.6.1.4.1.12148.9.4.3.2 | INTEGER | read-only | The load Contactor 1 is connected(0), disconnected(1) or disabled(2) |
| I32 loadLVD1ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.3 | Integer32 | read-write | LVLD1 Connect Voltage |
| I32 loadLVD1DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.4 | Integer32 | read-write | LVLD1 Disconnect Voltage |
| INT loadLVD2Enable | 1.3.6.1.4.1.12148.9.4.3.5 | INTEGER | read-only | The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. |
| INT loadLVD2Status | 1.3.6.1.4.1.12148.9.4.3.6 | INTEGER | read-only | The load Contactor 2 is connected(0), disconnected(1) or disabled(2) |
| I32 loadLVD2ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.7 | Integer32 | read-write | LVLD2 Connect Voltage |
| I32 loadLVD2DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.8 | Integer32 | read-write | LVLD2 Disconnect Voltage |
| INT loadLVD3Enable | 1.3.6.1.4.1.12148.9.4.3.9 | INTEGER | read-only | The status of contactors configuration. 'enabled' means that the contactor is in use. 'disabled' means that the contactor is disconfigured and not in use. |
| INT loadLVD3Status | 1.3.6.1.4.1.12148.9.4.3.10 | INTEGER | read-only | The load Contactor 3 is connected(0), disconnected(1) or disabled(2) |
| I32 loadLVD3ConnectVoltage | 1.3.6.1.4.1.12148.9.4.3.11 | Integer32 | read-write | LVLD3 Connect Voltage |
| I32 loadLVD3DisconnectVoltage | 1.3.6.1.4.1.12148.9.4.3.12 | Integer32 | read-write | LVLD3 Disconnect Voltage |
| loadMonitorUnits | 1.3.6.1.4.1.12148.9.4.4 | |||
| I32 loadmonitorNumberOfUnits | 1.3.6.1.4.1.12148.9.4.4.1 | Integer32 | read-only | |
| I32 loadMonitorUnitsIndex | 1.3.6.1.4.1.12148.9.4.4.2 | Integer32 | accessible-for-notify | |
| loadMonitorUnitsTable | 1.3.6.1.4.1.12148.9.4.4.3 | not-accessible | ||
| loadMonitorUnitsEntry | 1.3.6.1.4.1.12148.9.4.4.3.1 | not-accessible | ||
| I32 loadMonitorID | 1.3.6.1.4.1.12148.9.4.4.3.1.1 | Integer32 | read-only | |
| INT loadMonitorFuseStatus1 | 1.3.6.1.4.1.12148.9.4.4.3.1.2 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent1 | 1.3.6.1.4.1.12148.9.4.4.3.1.3 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus2 | 1.3.6.1.4.1.12148.9.4.4.3.1.4 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent2 | 1.3.6.1.4.1.12148.9.4.4.3.1.5 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus3 | 1.3.6.1.4.1.12148.9.4.4.3.1.6 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent3 | 1.3.6.1.4.1.12148.9.4.4.3.1.7 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus4 | 1.3.6.1.4.1.12148.9.4.4.3.1.8 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent4 | 1.3.6.1.4.1.12148.9.4.4.3.1.9 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus5 | 1.3.6.1.4.1.12148.9.4.4.3.1.10 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent5 | 1.3.6.1.4.1.12148.9.4.4.3.1.11 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus6 | 1.3.6.1.4.1.12148.9.4.4.3.1.12 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent6 | 1.3.6.1.4.1.12148.9.4.4.3.1.13 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus7 | 1.3.6.1.4.1.12148.9.4.4.3.1.14 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent7 | 1.3.6.1.4.1.12148.9.4.4.3.1.15 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| INT loadMonitorFuseStatus8 | 1.3.6.1.4.1.12148.9.4.4.3.1.16 | INTEGER | read-only | The state of the load fuses/breakers can be either normal(0) or alarm(1) |
| I32 loadMonitorCurrent8 | 1.3.6.1.4.1.12148.9.4.4.3.1.17 | Integer32 | read-only | The current consumed by this load branch. Note that the units measured may be i Amperes or in Deciamperes depending on global system settings |
| rectifier | 1.3.6.1.4.1.12148.9.5 | |||
| I32 rectifierInstalledRectifiers | 1.3.6.1.4.1.12148.9.5.1 | Integer32 | read-only | The number of installed rectifiers for this DC Power System. |
| I32 rectifierRectifiersActive | 1.3.6.1.4.1.12148.9.5.2 | Integer32 | read-only | Not Used! |
| I32 rectifierTotalCurrent | 1.3.6.1.4.1.12148.9.5.3 | Integer32 | read-only | The DC system's total delivered rectifier current |
| I32 rectifierUtilization | 1.3.6.1.4.1.12148.9.5.4 | Integer32 | read-only | Utilization in % of available rectifier capacity |
| rectifierStatus | 1.3.6.1.4.1.12148.9.5.5 | |||
| I32 rectifierStatusNoIndex | 1.3.6.1.4.1.12148.9.5.5.1 | Integer32 | read-write | An offset for the rectifierStatusTable array. The rectifier status table has a fixed number of 20 rows. This OID sets the offset for the rectifier in the first row i.e. setting the index to 11 will give a range from rectifier ID12 to ID31. Setting the index to 0 will give a range from rectifier ID1 to ID20. |
| rectifierStatusTable | 1.3.6.1.4.1.12148.9.5.5.2 | not-accessible | A table listing up to 20 recifiers, starting from the rectifier number specified by rectifierStatusNoIndex | |
| rectifierStatusEntry | 1.3.6.1.4.1.12148.9.5.5.2.1 | not-accessible | A row of rectifier status data corresponding to the rectifierStatusNoIndex value | |
| I32 rectifierStatusID | 1.3.6.1.4.1.12148.9.5.5.2.1.1 | Integer32 | read-only | The rectifier ID number of the rectifier. |
| INT rectifierStatusStatus | 1.3.6.1.4.1.12148.9.5.5.2.1.2 | INTEGER | read-only | The operational status of the rectifier record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4) |
| I32 rectifierStatusOutputCurrent | 1.3.6.1.4.1.12148.9.5.5.2.1.3 | Integer32 | read-only | The output current of the rectifier. |
| I32 rectifierStatusOutputVoltage | 1.3.6.1.4.1.12148.9.5.5.2.1.4 | Integer32 | read-only | The rectifier voltage of the rectifier record. |
| I32 rectifierStatusTemp | 1.3.6.1.4.1.12148.9.5.5.2.1.5 | Integer32 | read-only | The input air temperature of the rectifier. |
| STR rectifierStatusType | 1.3.6.1.4.1.12148.9.5.5.2.1.6 | DisplayString | read-only | The rectifier article number string of the rectifier record. |
| STR rectifierStatusSKU | 1.3.6.1.4.1.12148.9.5.5.2.1.7 | DisplayString | read-only | The rectifier part number. |
| STR rectifierStatusSerialNo | 1.3.6.1.4.1.12148.9.5.5.2.1.8 | DisplayString | read-only | The rectifier serial number string of the rectifier record. |
| STR rectifierStatusRevisionLevel | 1.3.6.1.4.1.12148.9.5.5.2.1.9 | DisplayString | read-only | The rectifier HW revision number string of the rectifier record. |
| acDistribution | 1.3.6.1.4.1.12148.9.6 | |||
| I32 acVoltage1 | 1.3.6.1.4.1.12148.9.6.1 | Integer32 | read-only | The AC Voltage of phase 1 |
| I32 acVoltage2 | 1.3.6.1.4.1.12148.9.6.2 | Integer32 | read-only | The AC Voltage of phase 2 |
| I32 acVoltage3 | 1.3.6.1.4.1.12148.9.6.3 | Integer32 | read-only | The AC Voltage of phase 3 |
| alarmGroup | 1.3.6.1.4.1.12148.9.7 | |||
| alarmWellknownAlarms | 1.3.6.1.4.1.12148.9.7.1 | |||
| INT alarmMajorHighBattVolt | 1.3.6.1.4.1.12148.9.7.1.1 | INTEGER | read-only | The Major High Battery Voltage Alarm |
| INT alarmMinorHighBattVolt | 1.3.6.1.4.1.12148.9.7.1.2 | INTEGER | read-only | The Minor High Battery Voltage alarm |
| INT alarmMajorLowBattVolt | 1.3.6.1.4.1.12148.9.7.1.3 | INTEGER | read-only | The Major Low Battery Voltage Alarm |
| INT alarmMinorLowBattVolt | 1.3.6.1.4.1.12148.9.7.1.4 | INTEGER | read-only | The Minor Low Battery Voltage Alarm |
| INT alarmMajorBatteryHighTemp | 1.3.6.1.4.1.12148.9.7.1.5 | INTEGER | read-only | The Major High Battery Temperature alarm. |
| INT alarmMinorBatteryHighTemp | 1.3.6.1.4.1.12148.9.7.1.6 | INTEGER | read-only | The Minor High Battery Temperature alarm. |
| INT alarmBatteryDisconnectOpen | 1.3.6.1.4.1.12148.9.7.1.7 | INTEGER | read-only | The Battery Disconnect Contactor alarm |
| INT alarmLVD1open | 1.3.6.1.4.1.12148.9.7.1.8 | INTEGER | read-only | The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. |
| INT alarmLVD2open | 1.3.6.1.4.1.12148.9.7.1.9 | INTEGER | read-only | The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. |
| INT alarmLVD3open | 1.3.6.1.4.1.12148.9.7.1.10 | INTEGER | read-only | The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. |
| INT alarmACmains | 1.3.6.1.4.1.12148.9.7.1.11 | INTEGER | read-only | The AC voltage has dropped below critical level, or one or more AC input phases was lost. |
| INT alarmBatteryBreakerOpen | 1.3.6.1.4.1.12148.9.7.1.12 | INTEGER | read-only | A battery breaker/fuse alarm. |
| INT alarmDistributionBreakerOpen | 1.3.6.1.4.1.12148.9.7.1.13 | INTEGER | read-only | A Load Distribution breaker/fuse alarm. |
| INT alarmMajorRectifier | 1.3.6.1.4.1.12148.9.7.1.14 | INTEGER | read-only | This is a Major Rectifier alarm. |
| INT alarmMinorRectifier | 1.3.6.1.4.1.12148.9.7.1.15 | INTEGER | read-only | This is a Minor Rectifier alarm. |
| INT alarmMajorBatterySymmetry | 1.3.6.1.4.1.12148.9.7.1.16 | INTEGER | read-only | Battery Symmetry Delta Voltage Major alarm. |
| INT alarmMinorBatterySymmetry | 1.3.6.1.4.1.12148.9.7.1.17 | INTEGER | read-only | Battery Symmetry Delta Voltage Minor alarm |
| INT alarmBatteryLifeEnded | 1.3.6.1.4.1.12148.9.7.1.18 | INTEGER | read-only | The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. |
| INT alarmBatteryTestmodeEntered | 1.3.6.1.4.1.12148.9.7.1.19 | INTEGER | read-only | The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. |
| INT alarmBatteryBoostmodeEntered | 1.3.6.1.4.1.12148.9.7.1.20 | INTEGER | read-only | The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. |
| INT alarmIoUnitTemp1 | 1.3.6.1.4.1.12148.9.7.1.21 | INTEGER | read-only | High or low temperature alarm 1 from any of the IO units. |
| INT alarmIoUnitTemp2 | 1.3.6.1.4.1.12148.9.7.1.22 | INTEGER | read-only | High or low temperature alarm 2 from any of the IO units. |
| INT alarmIoUnitDeltaFanSpeed1 | 1.3.6.1.4.1.12148.9.7.1.23 | INTEGER | read-only | Delta fan speed 1 from any of the IO units. |
| INT alarmIoUnitDeltaFanSpeed2 | 1.3.6.1.4.1.12148.9.7.1.24 | INTEGER | read-only | Delta fan speed 2 from any of the IO units. |
| INT alarmMajorSolar | 1.3.6.1.4.1.12148.9.7.1.25 | INTEGER | read-only | This is a Major Solar alarm. |
| INT alarmMinorSolar | 1.3.6.1.4.1.12148.9.7.1.26 | INTEGER | read-only | This is a Major Solar alarm. |
| INT alarmMajorRectifierCapacity | 1.3.6.1.4.1.12148.9.7.1.27 | INTEGER | read-only | This is a Major Rectifier Capacity alarm. |
| INT alarmMinorRectifierCapacity | 1.3.6.1.4.1.12148.9.7.1.28 | INTEGER | read-only | This is a Minor Rectifier Capacity alarm. |
| dcSystemTraps | 1.3.6.1.4.1.12148.9.8 | This branch contains the Alarm Notification Traps, which duplicate the alarmGroup OIDs. Each alarm condition is represented by a Alarm Condition Trap and an associated OFF Trap, which is optionally transmitted according to the state of OID systemSendOffTrap | ||
| NTF alarmMajorHighBattVoltTrap | 1.3.6.1.4.1.12148.9.8.1 | The Major High Battery Voltage alarm | ||
| NTF alarmMinorHighBattVoltTrap | 1.3.6.1.4.1.12148.9.8.2 | The Minor High Battery Voltage alarm | ||
| NTF alarmMajorLowBattVoltTrap | 1.3.6.1.4.1.12148.9.8.3 | The Major Low Battery Voltage Alarm | ||
| NTF alarmMinorLowBattVoltTrap | 1.3.6.1.4.1.12148.9.8.4 | The Minor Low Battery Voltage Alarm | ||
| NTF alarmMajorBatteryHighTempTrap | 1.3.6.1.4.1.12148.9.8.5 | The Major High Battery Temperature alarm. | ||
| NTF alarmMinorBatteryHighTempTrap | 1.3.6.1.4.1.12148.9.8.6 | The Minor High Battery Temperature alarm. | ||
| NTF alarmBatteryDisconnectOpenTrap | 1.3.6.1.4.1.12148.9.8.7 | The Battery Disconnect Contactor alarm | ||
| NTF alarmLVD1openTrap | 1.3.6.1.4.1.12148.9.8.8 | The load Contactor 1 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | ||
| NTF alarmLVD2openTrap | 1.3.6.1.4.1.12148.9.8.9 | The load Contactor 2 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | ||
| NTF alarmLVD3openTrap | 1.3.6.1.4.1.12148.9.8.10 | The load Contactor 3 alarm. The contactor disconnect voltage has been reached and the contactor has disconnected. | ||
| NTF alarmACmainsTrap | 1.3.6.1.4.1.12148.9.8.11 | The AC voltage has dropped below critical level, or one or more AC input phases was lost. | ||
| NTF alarmBatteryBreakerOpenTrap | 1.3.6.1.4.1.12148.9.8.12 | A battery breaker/fuse alarm. | ||
| NTF alarmDistributionBreakerOpenTrap | 1.3.6.1.4.1.12148.9.8.13 | A Load Distribution breaker/fuse alarm. | ||
| NTF alarmMajorRectifierTrap | 1.3.6.1.4.1.12148.9.8.14 | This is a Major Rectifier alarm. | ||
| NTF alarmMinorRectifierTrap | 1.3.6.1.4.1.12148.9.8.15 | This is a Minor Rectifier alarm. | ||
| NTF alarmMajorBatterySymmetryTrap | 1.3.6.1.4.1.12148.9.8.16 | Battery Symmetry Delta Voltage Major alarm | ||
| NTF alarmMinorBatterySymmetryTrap | 1.3.6.1.4.1.12148.9.8.17 | Battery Symmetry Delta Voltage Minor alarm | ||
| NTF alarmBatteryLifeEndedTrap | 1.3.6.1.4.1.12148.9.8.18 | The battery quality has dropped below critical level. A battery test has measured the fully charged capacity to be too low, and thus probably the battery lifecycle to be near expired. | ||
| NTF alarmBatteryTestmodeEnteredTrap | 1.3.6.1.4.1.12148.9.8.19 | The system has lowered the battery charge voltage in order to discharge the batteries to a predefined level. When the criteria for stopping the battery testing is reached, the charge voltage is increased to commence normal charging. | ||
| NTF alarmBatteryBoostmodeEnteredTrap | 1.3.6.1.4.1.12148.9.8.20 | The system has increased the battery charge voltage in order to boost the battery. When the criteria for stopping the battery boost is reached, the charge voltage is lowered to commence normal charging. | ||
| NTF alarmController1proginputTrap | 1.3.6.1.4.1.12148.9.8.21 | Programmable input alarm for Control unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController2proginputTrap | 1.3.6.1.4.1.12148.9.8.22 | Programmable input alarm for Control unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController3proginputTrap | 1.3.6.1.4.1.12148.9.8.23 | Programmable input alarm for Control unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController4proginputTrap | 1.3.6.1.4.1.12148.9.8.24 | Programmable input alarm for Control unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController5proginputTrap | 1.3.6.1.4.1.12148.9.8.25 | Programmable input alarm for Control unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController6proginputTrap | 1.3.6.1.4.1.12148.9.8.26 | Programmable input alarm for Control unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController7proginputTrap | 1.3.6.1.4.1.12148.9.8.27 | Programmable input alarm for Control unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmController8proginputTrap | 1.3.6.1.4.1.12148.9.8.28 | Programmable input alarm for Control unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF infoHeartBeatTrap | 1.3.6.1.4.1.12148.9.8.29 | When enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is alive and the link is up. | ||
| NTF alarmIoUnitTemp1Trap | 1.3.6.1.4.1.12148.9.8.30 | High or low temperature alarm 1 from any of the IO units. | ||
| NTF alarmIoUnitTemp2Trap | 1.3.6.1.4.1.12148.9.8.31 | High or low temperature alarm 2 from any of the IO units. | ||
| NTF alarmIoUnitDeltaFanSpeed1Trap | 1.3.6.1.4.1.12148.9.8.32 | Delta fan speed 1 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level. | ||
| NTF alarmIoUnitDeltaFanSpeed2Trap | 1.3.6.1.4.1.12148.9.8.33 | Delta fan speed 2 from any of the IO units. Occurs if the fan speed deviation is above/below the configured level. | ||
| NTF alarmIoUnit1proginputTrap | 1.3.6.1.4.1.12148.9.8.34 | Programmable input alarm for IO Unit 1. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit2proginputTrap | 1.3.6.1.4.1.12148.9.8.35 | Programmable input alarm for IO Unit 2. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit3proginputTrap | 1.3.6.1.4.1.12148.9.8.36 | Programmable input alarm for IO Unit 3. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit4proginputTrap | 1.3.6.1.4.1.12148.9.8.37 | Programmable input alarm for IO Unit 4. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit5proginputTrap | 1.3.6.1.4.1.12148.9.8.38 | Programmable input alarm for IO Unit 5. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit6proginputTrap | 1.3.6.1.4.1.12148.9.8.39 | Programmable input alarm for IO Unit 6. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit7proginputTrap | 1.3.6.1.4.1.12148.9.8.40 | Programmable input alarm for IO Unit 7. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit8proginputTrap | 1.3.6.1.4.1.12148.9.8.41 | Programmable input alarm for IO Unit 8. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit9proginputTrap | 1.3.6.1.4.1.12148.9.8.42 | Programmable input alarm for IO Unit 9. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit10proginputTrap | 1.3.6.1.4.1.12148.9.8.43 | Programmable input alarm for IO Unit 10. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit11proginputTrap | 1.3.6.1.4.1.12148.9.8.44 | Programmable input alarm for IO Unit 11. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit12proginputTrap | 1.3.6.1.4.1.12148.9.8.45 | Programmable input alarm for IO Unit 12. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit13proginputTrap | 1.3.6.1.4.1.12148.9.8.46 | Programmable input alarm for IO Unit 13. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmIoUnit14proginputTrap | 1.3.6.1.4.1.12148.9.8.47 | Programmable input alarm for IO Unit 14. Programmable input alarms will have description attached that explains the alarm. Default description is: ProgInput .x. | ||
| NTF alarmMajorSolarChargerTrap | 1.3.6.1.4.1.12148.9.8.48 | The Major Solar Charger alarm | ||
| NTF alarmMinorSolarChargerTrap | 1.3.6.1.4.1.12148.9.8.49 | The Minor Solar Charger alarm | ||
| NTF alarmMajorRectifierCapacityTrap | 1.3.6.1.4.1.12148.9.8.50 | The Major Rectifier Capacity alarm | ||
| NTF alarmMinorRectifierCapacityTrap | 1.3.6.1.4.1.12148.9.8.51 | The Minor Rectifier Capacity alarm | ||
| solarCharger | 1.3.6.1.4.1.12148.9.9 | |||
| I32 solarChargerInstalledsolarChargers | 1.3.6.1.4.1.12148.9.9.1 | Integer32 | read-only | The number of installed solar chargers for this DC Power System. |
| I32 solarChargersActive | 1.3.6.1.4.1.12148.9.9.2 | Integer32 | read-only | Not Used! |
| I32 solarChargerTotalCurrent | 1.3.6.1.4.1.12148.9.9.3 | Integer32 | read-only | The DC system's total delivered solar current |
| I32 solarChargerUtilization | 1.3.6.1.4.1.12148.9.9.4 | Integer32 | read-only | Utilization in % of available solar capacity |
| solarChargerStatus | 1.3.6.1.4.1.12148.9.9.5 | |||
| I32 solarChargerStatusNoIndex | 1.3.6.1.4.1.12148.9.9.5.1 | Integer32 | read-write | An offset for the solarStatusTable array. The solar status table has a fixed number of 20 rows. This OID sets the offset for the solarcharger in the first row i.e. setting the index to 11 will give a range from solarcharger ID12 to ID31. Setting the index to 0 will give a range from solarcharger ID1 to ID20. |
| solarChargerStatusTable | 1.3.6.1.4.1.12148.9.9.5.2 | not-accessible | A table listing up to 20 solarchargers, starting from the solarcharger number specified by solarStatusNoIndex | |
| solarChargerStatusEntry | 1.3.6.1.4.1.12148.9.9.5.2.1 | not-accessible | A row of rectifier status data corresponding to the rectifierStatusNoIndex value | |
| I32 solarChargerStatusID | 1.3.6.1.4.1.12148.9.9.5.2.1.1 | Integer32 | read-only | The ID number of the solarcharger. |
| INT solarChargerStatusStatus | 1.3.6.1.4.1.12148.9.9.5.2.1.2 | INTEGER | read-only | The operational status of the solarcharger record. Not Present (0), normal (1), alarm (2), notUsed (3), disabled (4) |
| I32 solarChargerOutputCurrent | 1.3.6.1.4.1.12148.9.9.5.2.1.3 | Integer32 | read-only | The output current of the solarcharger. |
| I32 solarChargerOutputVoltage | 1.3.6.1.4.1.12148.9.9.5.2.1.4 | Integer32 | read-only | The output voltage of the solarcharger. |
| I32 solarChargerTemp | 1.3.6.1.4.1.12148.9.9.5.2.1.5 | Integer32 | read-only | The input air temperature of the solarcharger. |
| STR solarChargerType | 1.3.6.1.4.1.12148.9.9.5.2.1.6 | DisplayString | read-only | The article number string of the solarcharger. |
| STR solarChargerSKU | 1.3.6.1.4.1.12148.9.9.5.2.1.7 | DisplayString | read-only | The solarcharger part number. |
| STR solarChargerSerialNo | 1.3.6.1.4.1.12148.9.9.5.2.1.8 | DisplayString | read-only | The serial number string of the solarcharger. |
| STR solarChargerRevisionLevel | 1.3.6.1.4.1.12148.9.9.5.2.1.9 | DisplayString | read-only | The HW revision number string of the solarcharger. |
RFC description
Generic MIB for ELTEK power management products including SmartPack and related systems with distributed control.