EATON-PDU-MIB :: pduNominalOutputVoltage

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › EATON-PDU-MIB › pduNominalOutputVoltage

pduNominalOutputVoltage

Module: EATON-PDU-MIB

OID (symbolic): EATON-PDU-MIB::pduNominalOutputVoltage

OID (numeric): 1.3.6.1.4.1.534.6.6.4.1.1.1.2

Node type: OBJECT-TYPE

Type: PositiveInteger

Access: read-only

Description: The nominal Output Voltage of this PDU (as distributed to the panels). May differ from the nominal Input Voltage if the PDU has an input transformer. This is either Line-to-Line or Line-to-Neutral, as indicated in pduOutputVoltageUnits.

What is pduNominalOutputVoltage?

Gives the PDU's nominal output voltage as distributed to its panels, which can differ from the input voltage when the unit has a step-down/step-up transformer; check pduOutputVoltageUnits to know whether it's a line-to-line or line-to-neutral figure before comparing it to panel readings.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.6.6.4.1.1.1.2
snmpwalk -v2c -c public <target> EATON-PDU-MIB::pduNominalOutputVoltage

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.6.6.4.1.1.1.2.1
snmpget -v2c -c public <target> EATON-PDU-MIB::pduNominalOutputVoltage.1

Start monitoring Eaton PDU (power distribution unit) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-PDU-MIB::pduNominalOutputVoltage OID value, configure state conditions and alerts, and monitor any Eaton PDU (power distribution unit) from a single console.

OID Breakdown

Upper-level ancestors (10 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.6productsEATON-OIDS
1.3.6.1.4.1.534.6.6pduAgentEATON-OIDS
1.3.6.1.4.1.534.6.6.4eatonPduEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.6.6.4.1eatonPduMIBObjectsEATON-PDU-MIB
1.3.6.1.4.1.534.6.6.4.1.1mainPduEATON-PDU-MIB
1.3.6.1.4.1.534.6.6.4.1.1.1pduNameplateEATON-PDU-MIB
1.3.6.1.4.1.534.6.6.4.1.1.1.2pduNominalOutputVoltageEATON-PDU-MIB