All MIBs › HUAWEI-POWER-MIB
Organization: Huawei Technologies Co.,Ltd.
Last Updated: 2013--0-1-
Category: Domain: Power Management, Hardware and Environment, Vendor: Huawei
Description: Huawei power supply MIB for monitoring power module status, input voltage, output load, and power redundancy state.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is HUAWEI-POWER-MIB?
HUAWEI-POWER-MIB is a Huawei hardware-monitoring MIB dedicated to power subsystem management on Huawei chassis-based equipment. It exposes power-module operational status, input voltage, output load/current, and overall power-redundancy state. Its monitoring purpose is squarely physical hardware health: detecting a power module transitioning out of a normal operating state, an out-of-range input voltage, or a loss of redundancy are all early indicators of an impending power-related outage that could take down the whole chassis if the remaining supply also fails. It is typically used alongside Huawei's entity/environment MIBs, which identify the physical module positions that the power objects refer to. It is deployed on Huawei chassis-based routers and switches with redundant power supplies in data-center and carrier environments, where SNMP monitoring of the power subsystem is essential for detecting an impending outage early.
IPNetwork Monitor allows you to monitor SNMP objects defined in HUAWEI-POWER-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Huawei chassis-based routers and switches with redundant power supplies
Monitoring Examples
No sample object names were provided for this module. In general, an operator would poll each power module's operational status and output load, watching for any module reporting a fault or an unexpected offline state. A redundancy-state object changing from redundant to non-redundant is a critical alert, since it means only one power supply remains active and any further failure would cause a full chassis outage.
What Can Be Monitored
- power module operational status
- input voltage
- output load/current
- power redundancy state
- power supply presence/failure
This MIB depends on
Related MIBs
Imported Objects
From HUAWEI-DEVICE-MIB
| hwFrameIndex | OBJECT-TYPE |
| hwDigChannelIndex | OBJECT-TYPE |
| hwEnvEmuIndex | OBJECT-TYPE |
| hwEnvEmuType | OBJECT-TYPE |
From HUAWEI-MIB
| huaweiUtility | OBJECT-IDENTITY |
From SNMPv2-SMI
| Integer32 | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE |
From SNMPv2-TC
| DateAndTime | |
| DisplayString | |
| RowStatus | |
| TEXTUAL-CONVENTION | |
| TruthValue |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| hwPower | 1.3.6.1.4.1.2011.6.2 | This MIB is used for defining Power Monitor management MIB objects. | ||
| hwPowerMonObjects | 1.3.6.1.4.1.2011.6.2.1 | |||
| hwPowerSysInfoTable | 1.3.6.1.4.1.2011.6.2.1.1 | not-accessible | Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| hwPowerSysInfoEntry | 1.3.6.1.4.1.2011.6.2.1.1.1 | not-accessible | Power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| I32 hwPowerIndex | 1.3.6.1.4.1.2011.6.2.1.1.1.1 | Integer32 | read-only | Index of the power supply monitored by the monitoring unit |
| INT hwPowerType | 1.3.6.1.4.1.2011.6.2.1.1.1.2 | INTEGER | read-write | Type of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 3.power48100(3) - Type of the Power emu device is power48100 4.power4850(4) - Type of the Power emu device is power4850 5.power48240(5) - Type of the Power emu device is power48240 6.power48120(6) - Type of the Power emu device is power48120 7.power48300(7) - Type of the Power emu device is power48300 8.power48240SinglePhase(8) - Type of the Power emu device is power48240SinglePhase 9.universalPower(9) - Type of the Power emu device is universalPower 10.power4845(10) - Type of the Power emu device is power4845 11.rpower(11) - Type of the Power emu device is rpower 12.power4805(15) - Type of the Power emu device is power4805 13.power4820(16) - Type of the Power emu device is power4820 14.onps(17) - Type of the Power emu device is onps 15.power4875l(18) - Type of the Power emu device is power4875l 16.psma(100) - Type of the Power emu device is psma 17.perm-al175nt(101) - Type of the Power emu device is perm-al175nt 18.mcs1800(102) - Type of the Power emu device is mcs1800 19.mcs1800A(103) - Type of the Power emu device is mcs1800A 20.mcs3000(104) - Type of the Power emu device is mcs3000 21.sm40sm60(105) - Type of the Power emu device is sm40sm60 22.scu(106) - Type of the Power emu device is scu 23.eltek(107) - Type of the Power emu device is eltek 24.dk04(108) - Type of the Power emu device is dk04 25.dk04C(109) - Type of the Power emu device is dk04C 26.dpc(110) - Type of the Power emu device is dpc 27.power4830(120) - Type of the Power emu device is power4830 28.h831pmua(121) - Type of the Power emu device is h831pmua 29.power3000(122) - Type of the Power emu device is power3000 30.liFeBattery(123) - Type of the Power emu device is LiFeBattery 31.etp4830(125), - Type of SMU Power emu device is etp4830 32.etp4890(126), - Type of SMU Power emu device is etp4890 33.other(255) - other Power Type |
| STR hwPowerName | 1.3.6.1.4.1.2011.6.2.1.1.1.3 | DisplayString | read-write | Power name. |
| INT hwPowerState | 1.3.6.1.4.1.2011.6.2.1.1.1.4 | INTEGER | read-only | Power board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.normal(1) - indicates the normal state 2.fault(2) - indicates the faulty state 3.protecting(3)- indicates that the backup power supply works in the protection state 4.switched(4) - indicates that the main power supply is faulty, and is protected by backup power supply 5.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| ROW hwPowerRowStatus | 1.3.6.1.4.1.2011.6.2.1.1.1.5 | RowStatus | read-write | RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status. |
| INT hwPowerControlMode | 1.3.6.1.4.1.2011.6.2.1.1.1.6 | INTEGER | read-write | Control mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is auto control mode 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| I32 hwPowerRemoteFrameID | 1.3.6.1.4.1.2011.6.2.1.1.1.7 | Integer32 | read-write | Apply for remote power system. It is the frame ID that the remote unit exists in |
| INT hwPowerProtect | 1.3.6.1.4.1.2011.6.2.1.1.1.8 | INTEGER | read-write | Apply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProtect(2) - disables the N+1 protection function |
| STR hwPowerVersion | 1.3.6.1.4.1.2011.6.2.1.1.1.9 | DisplayString | read-only | Version of power |
| INT hwPowerSupplyState | 1.3.6.1.4.1.2011.6.2.1.1.1.10 | INTEGER | read-only | Power supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries |
| hwACInputTable | 1.3.6.1.4.1.2011.6.2.1.2 | not-accessible | AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit. | |
| hwACInputEntry | 1.3.6.1.4.1.2011.6.2.1.2.1 | not-accessible | AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwACLoopIndex. hwEnvEmuIndex is the index of the monitoring unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwACLoopIndex is the index of the AC input power supply monitored by the monitoring unit. | |
| I32 hwACLoopIndex | 1.3.6.1.4.1.2011.6.2.1.2.1.1 | Integer32 | read-only | Input loop index. There are two channels of AC current input, which are the backup for each other. |
| INT hwACPowerState | 1.3.6.1.4.1.2011.6.2.1.2.1.2 | INTEGER | read-only | Status of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVoltage(3) - indicates that the power supply is overvoltage 4.belowVoltage(4) - indicates that the power supply is undervoltage 5.backup(5) - indicates that the power supply is not supported currently 6.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwACVoltA | 1.3.6.1.4.1.2011.6.2.1.2.1.3 | MeasuresRange | read-only | AC Inuput voltage A. Unit: mV |
| MEA hwACCurrentA | 1.3.6.1.4.1.2011.6.2.1.2.1.4 | MeasuresRange | read-only | AC input Current A. Unit: mA |
| MEA hwACVoltB | 1.3.6.1.4.1.2011.6.2.1.2.1.5 | MeasuresRange | read-only | AC input voltage B. Unit: mv |
| MEA hwACCurrentB | 1.3.6.1.4.1.2011.6.2.1.2.1.6 | MeasuresRange | read-only | AC input current B. Unit: mA |
| MEA hwACVoltC | 1.3.6.1.4.1.2011.6.2.1.2.1.7 | MeasuresRange | read-only | AC input voltage C. Unit: mV |
| MEA hwACCurrentC | 1.3.6.1.4.1.2011.6.2.1.2.1.8 | MeasuresRange | read-only | AC input current C. Unit: mA |
| MEA hwACVoltageHigh | 1.3.6.1.4.1.2011.6.2.1.2.1.9 | MeasuresRange | read-write | AC input over-voltage alarm threshold. Unit: mV |
| MEA hwACVoltageLow | 1.3.6.1.4.1.2011.6.2.1.2.1.10 | MeasuresRange | read-write | AC input under-voltage alarm threshold. Unit: mV |
| ROW hwACRowStatus | 1.3.6.1.4.1.2011.6.2.1.2.1.11 | RowStatus | read-write | Only the add operation, delete operation, and status query operation are supported. |
| INT hwACVoltageAState | 1.3.6.1.4.1.2011.6.2.1.2.1.12 | INTEGER | read-only | Phase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase AB/A of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase AB/A of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase AB/A of AC input state is missing-phase |
| INT hwACVoltageBState | 1.3.6.1.4.1.2011.6.2.1.2.1.13 | INTEGER | read-only | Phase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase BC/B of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase BC/B of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase BC/B of AC input state is missing-phase |
| INT hwACVoltageCState | 1.3.6.1.4.1.2011.6.2.1.2.1.14 | INTEGER | read-only | Phase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase CA/C of AC input state is belowVoltage 3. exceedVoltage(2) - indicates that the Phase CA/C of AC input state is exceedVoltage 4. missing-phase(3) - indicates that the Phase CA/C of AC input state is missing-phase |
| hwDCOutTable | 1.3.6.1.4.1.2011.6.2.1.3 | not-accessible | DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| hwDCOutEntry | 1.3.6.1.4.1.2011.6.2.1.3.1 | not-accessible | DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100 power supply can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| MEA hwDCVoltageOut | 1.3.6.1.4.1.2011.6.2.1.3.1.1 | MeasuresRange | read-only | DC voltage output. Unit: mV |
| MEA hwDCCurrentOut | 1.3.6.1.4.1.2011.6.2.1.3.1.2 | MeasuresRange | read-only | DC current output. Unit: mA |
| MEA hwDCVoltageOutHigh | 1.3.6.1.4.1.2011.6.2.1.3.1.3 | MeasuresRange | read-write | Output DC exceed-voltage alarm point. Default: 58000 Unit: mV |
| MEA hwDCVoltageOutLow | 1.3.6.1.4.1.2011.6.2.1.3.1.4 | MeasuresRange | read-write | Output DC below-voltage alarm point . Default value is 45V. Unit: mV |
| INT hwDCVoltageOutState | 1.3.6.1.4.1.2011.6.2.1.3.1.5 | INTEGER | read-only | DC output voltage status. Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output voltage state is exceedVoltage 3. belowVoltage(3) - indicates that the DC output voltage state is belowVoltage 4.invalid(-1) - indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwDCCurrentOutHigh | 1.3.6.1.4.1.2011.6.2.1.3.1.6 | MeasuresRange | read-write | Output DC exceed-current alarm point . Unit: mA |
| MEA hwDCCurrentOutLow | 1.3.6.1.4.1.2011.6.2.1.3.1.7 | MeasuresRange | read-write | Output below-current alarm point . Unit: mA |
| INT hwDCCurrentOutState | 1.3.6.1.4.1.2011.6.2.1.3.1.8 | INTEGER | read-only | DC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current state is exceedVoltage 3.belowVoltage(3) - indicates that the DC output current state is belowVoltage 4.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| ROW hwDCOutRowStatus | 1.3.6.1.4.1.2011.6.2.1.3.1.9 | RowStatus | read-write | RowStatus standard operation |
| MEA hwDCOutLoadCurrent | 1.3.6.1.4.1.2011.6.2.1.3.1.10 | MeasuresRange | read-only | Total load current of DC output . Unit: mA |
| MEA hwDCOutLoadTmpHigh | 1.3.6.1.4.1.2011.6.2.1.3.1.11 | MeasuresRange | read-write | The off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree |
| BIT hwDCOutRunState | 1.3.6.1.4.1.2011.6.2.1.3.1.12 | Bits | read-only | DC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge over-current 3.batteryVoltageOver(2) - indicates output over-voltage 4.batteryVoltageLack(3) - indicates battery lack-voltage 5.loadOff(4) - indicates load off twice 6.batteryOff(5) - indictes battery protection (off once) 7.communicationFailure(6) - indicates that the communication fails 8.dcOutManual(7) - indicates DC by manual |
| INT hwDCCommunicationState | 1.3.6.1.4.1.2011.6.2.1.3.1.13 | INTEGER | read-only | DC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is fault |
| hwLoadinfoTable | 1.3.6.1.4.1.2011.6.2.1.4 | not-accessible | Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load. | |
| hwLoadinfoEntry | 1.3.6.1.4.1.2011.6.2.1.4.1 | not-accessible | Load information table. Through this table, the load parameter can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwLoadIndex is the index of the monitored load. | |
| I32 hwLoadIndex | 1.3.6.1.4.1.2011.6.2.1.4.1.1 | Integer32 | read-only | Loop index: usually each DC output loop corresponds to a load. |
| INT hwLoadInfoAdminState | 1.3.6.1.4.1.2011.6.2.1.4.1.2 | INTEGER | read-write | Load operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| INT hwLoadInfoOperStatus | 1.3.6.1.4.1.2011.6.2.1.4.1.3 | INTEGER | read-only | Status of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is abnormal 3. stop(3) - indicates that the state of power supply is stopping power supply 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwLoadCurrent | 1.3.6.1.4.1.2011.6.2.1.4.1.4 | MeasuresRange | read-only | Present current . Unit: mA |
| MEA hwLoadVoltage | 1.3.6.1.4.1.2011.6.2.1.4.1.5 | MeasuresRange | read-only | Present voltage . Unit: mV |
| MEA hwLoadVoltageHigh | 1.3.6.1.4.1.2011.6.2.1.4.1.6 | MeasuresRange | read-write | Off voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Default: 43500 Unit: mV |
| STR hwLoadLoadName | 1.3.6.1.4.1.2011.6.2.1.4.1.7 | DisplayString | read-write | Load name: usually each DC output loop corresponds to a load. |
| ROW hwLoadInfoRowStatus | 1.3.6.1.4.1.2011.6.2.1.4.1.8 | RowStatus | read-write | RowStatus standard operation |
| INT hwLoadFuseState | 1.3.6.1.4.1.2011.6.2.1.4.1.9 | INTEGER | read-only | Load fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| I32 hwLoadHoreIndex | 1.3.6.1.4.1.2011.6.2.1.4.1.10 | Integer32 | read-write | load hore index |
| hwRectifierTable | 1.3.6.1.4.1.2011.6.2.1.5 | not-accessible | Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply. | |
| hwRectifierEntry | 1.3.6.1.4.1.2011.6.2.1.5.1 | not-accessible | Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwRectifierIndex. hwEnvEmuIndex, which comes from hwEnvironmentInfoTable, is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwRectifierIndex is the index of the monitored rectifier module under the power supply. | |
| I32 hwRectifierIndex | 1.3.6.1.4.1.2011.6.2.1.5.1.1 | Integer32 | read-only | Rectifier Module index. There are multiple rectifier modules to a power source. |
| INT hwRectifierAdminState | 1.3.6.1.4.1.2011.6.2.1.5.1.2 | INTEGER | read-write | Switch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disabled 3.invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| INT hwRectifierOperState | 1.3.6.1.4.1.2011.6.2.1.5.1.3 | INTEGER | read-only | Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state is normal 2. fault(2) - indicates that the Rectifier operation state is fault 3. protect(3) - indicates that the Rectifier operation state is protect 4. communicationFailure(4) - indicates that the Rectifier operation state is communicationFailure 5. on(5) - indicates that the Rectifier operation state is on 6. off(6) - indicates that the Rectifier operation state is off 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwRectifierVoltage | 1.3.6.1.4.1.2011.6.2.1.5.1.4 | MeasuresRange | read-only | Output voltage . Unit: mV |
| MEA hwRectifierCurrent | 1.3.6.1.4.1.2011.6.2.1.5.1.5 | MeasuresRange | read-only | Output current . Unit: mA |
| ROW hwRectifierRowStatus | 1.3.6.1.4.1.2011.6.2.1.5.1.6 | RowStatus | read-write | RowStatus standard operation |
| T/F hwRectifierCurrentLimit | 1.3.6.1.4.1.2011.6.2.1.5.1.7 | TruthValue | read-write | current limit switch |
| BIT hwRectifierRunState | 1.3.6.1.4.1.2011.6.2.1.5.1.8 | Bits | read-only | Running state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagely charged. 3.output(2) - indicates that the module has output 4. isLimit(3) - indicates the current limit switch |
| INT hwRectifierChargeState | 1.3.6.1.4.1.2011.6.2.1.5.1.9 | INTEGER | read-only | Charging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Rectifier is average 3. test(2) - indicates that the Charge state of Rectifier is test |
| hwBatteryGroup | 1.3.6.1.4.1.2011.6.2.1.6 | |||
| hwBatteryGroupTable | 1.3.6.1.4.1.2011.6.2.1.6.1 | not-accessible | Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| hwBatteryGroupEntry | 1.3.6.1.4.1.2011.6.2.1.6.1.1 | not-accessible | Basic information table of battery group. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| I32 hwBatteryGroupCapacity | 1.3.6.1.4.1.2011.6.2.1.6.1.1.1 | Integer32 | read-only | Total capacity of the present battery group. Unit: Ah |
| I32 hwBatteryGroupCapcaityRemain | 1.3.6.1.4.1.2011.6.2.1.6.1.1.2 | Integer32 | read-only | Total remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. Unit: Ah |
| I32 hwBatteryGroups | 1.3.6.1.4.1.2011.6.2.1.6.1.1.3 | Integer32 | read-write | Number of battery group |
| MEA hwBatteryGroupVoltageLow | 1.3.6.1.4.1.2011.6.2.1.6.1.1.4 | MeasuresRange | read-write | When the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV |
| MEA hwBatteryGroupChargeLimit | 1.3.6.1.4.1.2011.6.2.1.6.1.1.5 | MeasuresRange | read-write | Charge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent |
| ROW hwBatteryGroupRowStatus | 1.3.6.1.4.1.2011.6.2.1.6.1.1.6 | RowStatus | read-write | RowStatus standard operation |
| INT hwBatteryGroupOperStatus | 1.3.6.1.4.1.2011.6.2.1.6.1.1.7 | INTEGER | read-only | The State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and the Power EMU state is Normal. When the mains supply is abnormal, the battery group usually supplies power in an emergency. Options: 1.on(1) - indicates that the state of the battery power supply is on 2.off(2) - indicates that the state of the battery power supply is off 3.invalid(-1) - indicates that the device can not get the value,e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwBatteryGroupVoltageHigh | 1.3.6.1.4.1.2011.6.2.1.6.1.1.8 | MeasuresRange | read-write | When the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV |
| MEA hwBatteryGroupTwiceOffVoltage | 1.3.6.1.4.1.2011.6.2.1.6.1.1.9 | MeasuresRange | read-write | The twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV |
| MEA hwBatteryGroupProtectVoltage | 1.3.6.1.4.1.2011.6.2.1.6.1.1.10 | MeasuresRange | read-write | The first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV |
| MEA hwBatteryGroupTmpOffHigh | 1.3.6.1.4.1.2011.6.2.1.6.1.1.11 | MeasuresRange | read-write | The high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree |
| STR hwBatteryInstallTime | 1.3.6.1.4.1.2011.6.2.1.6.1.1.12 | DisplayString | read-only | The installing date of battery group. |
| OCT hwBatteryGroupBomCode | 1.3.6.1.4.1.2011.6.2.1.6.1.1.13 | OCTET STRING | read-write | The BAR code of battery. |
| hwChargeTable | 1.3.6.1.4.1.2011.6.2.1.6.2 | not-accessible | Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| hwChargeEntry | 1.3.6.1.4.1.2011.6.2.1.6.2.1 | not-accessible | Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| INT hwChargeAdminStatus | 1.3.6.1.4.1.2011.6.2.1.6.2.1.1 | INTEGER | read-write | Charge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management mode is float charge 3. auto(3) - indicates that the charge management mode is auto-control charge 4. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| INT hwChargeOperStatus | 1.3.6.1.4.1.2011.6.2.1.6.2.1.2 | INTEGER | read-only | Charge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation state is float charge 3. full(3) - indicates that the charge operation state is full 4. noCharge(4) - indicates that there is no charge in operation 5. discharge(5) - indicates that there is discharge in operation 6. sleep(6) - indicates that the charge operation state is sleep 7. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwAverageChargeVoltage | 1.3.6.1.4.1.2011.6.2.1.6.2.1.3 | MeasuresRange | read-write | Voltage value of average charge, in unit of mV. Default: 56500 Unit: mV |
| MEA hwFloatChargeVoltage | 1.3.6.1.4.1.2011.6.2.1.6.2.1.4 | MeasuresRange | read-write | Voltage value of float charge . Default: 53500 Unit: mV |
| ROW hwChargeControlRowStatus | 1.3.6.1.4.1.2011.6.2.1.6.2.1.5 | RowStatus | read-write | RowStatus standard operation |
| I32 hwAverageChargeTime | 1.3.6.1.4.1.2011.6.2.1.6.2.1.6 | Integer32 | read-write | Timing average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day |
| I32 hwBatteryTmpRedeemingQuotiety | 1.3.6.1.4.1.2011.6.2.1.6.2.1.7 | Integer32 | read-write | Temperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float charge voltage decrease with the increasing of every degree centigrade of the battery temperature. The unit is mV. Specific value is determined by the redeem feature curve of floating charge for the battery group used. Default value is 100mV |
| hwBatteryTable | 1.3.6.1.4.1.2011.6.2.1.6.3 | not-accessible | Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group. | |
| hwBatteryEntry | 1.3.6.1.4.1.2011.6.2.1.6.3.1 | not-accessible | Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryIndex is the index of the monitored battery group. | |
| I32 hwBatteryIndex | 1.3.6.1.4.1.2011.6.2.1.6.3.1.1 | Integer32 | read-only | Battery group loop index |
| I32 hwBatteryCapacity | 1.3.6.1.4.1.2011.6.2.1.6.3.1.2 | Integer32 | read-write | The permitted max battery capacity of the battery group loop charge. Unit: Ah |
| INT hwBatteryLoopState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.3 | INTEGER | read-only | The battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of battery group is off 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwBatteryVoltage | 1.3.6.1.4.1.2011.6.2.1.6.3.1.4 | MeasuresRange | read-only | The loop voltage of the battery group. Unit: mV |
| INT hwBatteryState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.5 | INTEGER | read-only | The present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - indicates that the present state of the battery group loop is discharge 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| MEA hwBatteryCurrent | 1.3.6.1.4.1.2011.6.2.1.6.3.1.6 | MeasuresRange | read-only | Present current . Unit: mA |
| I32 hwBatteryTemperature | 1.3.6.1.4.1.2011.6.2.1.6.3.1.7 | Integer32 | read-only | The loop temperature of the battery group. Unit: degree |
| ROW hwBatteryRowStatus | 1.3.6.1.4.1.2011.6.2.1.6.3.1.8 | RowStatus | read-write | RowStatus standard operation |
| MEA hwBatteryCurrentHigh | 1.3.6.1.4.1.2011.6.2.1.6.3.1.9 | MeasuresRange | read-write | The over-current alarm point of the battery group. Unit: mA |
| INT hwBatteryFuseState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.10 | INTEGER | read-only | Battery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| INT hwBatteryContactState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.11 | INTEGER | read-only | The state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. invalid(-1) - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal |
| I32 hwBatteryRemainCapacity | 1.3.6.1.4.1.2011.6.2.1.6.3.1.12 | Integer32 | read-only | Remain capacity of the battery |
| INT hwBatteryProtectState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.13 | INTEGER | read-only | Protection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that the Protection status of the battery is overtemperature 3. overCurrent(3) - indicates that the Protection status of the battery is overCurrent |
| INT hwBatteryVoltageState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.14 | INTEGER | read-only | Voltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Battery is exceedVoltage 3. belowVoltage(3) - indicates that Voltage state of Battery is belowVoltage |
| INT hwBatteryHardwareState | 1.3.6.1.4.1.2011.6.2.1.6.3.1.15 | INTEGER | read-only | Hardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Battery is fault |
| hwBatteryTestTable | 1.3.6.1.4.1.2011.6.2.1.6.4 | not-accessible | Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| hwBatteryTestEntry | 1.3.6.1.4.1.2011.6.2.1.6.4.1 | not-accessible | Battery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| INT hwBatteryTestAdminStatus | 1.3.6.1.4.1.2011.6.2.1.6.4.1.1 | INTEGER | read-write | Battery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. enableAutoTest(3) - indicates that the Battery enables auto test function 4. disableAutoTest(4) - indicates that the Battery disables auto test function 5. timeautoTest(5) - indicates that the Battery enable timing auto test function 6. offautoTest(6) - indicates that the Battery enable off auto test function 7. timeoffautoTest(7) - indicates that the Battery enable timing+off auto test |
| I32 hwBatteryTestAutoDischargePeriod | 1.3.6.1.4.1.2011.6.2.1.6.4.1.2 | Integer32 | read-write | Auto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day |
| INT hwBatteryTestResult | 1.3.6.1.4.1.2011.6.2.1.6.4.1.3 | INTEGER | read-only | Test result: Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3. alarmTerminated(3) - indicates that the Battery test is stopped by alarms 4. hostTerminated(4) - indicates that the Battery test is stopped by the host 5. overtimeTerminated(5) - indicates that the Battery test is stopped because of over time 6. normal(6) - indicates that the Battery test is not started 7. supplyRecoverAutotestTerminated(7) - indicates that the Battery test is stopped because of supply recover |
| DAT hwBatteryTestStartTime | 1.3.6.1.4.1.2011.6.2.1.6.4.1.4 | DateAndTime | read-only | Time of starting test |
| I32 hwBatteryTestDuration | 1.3.6.1.4.1.2011.6.2.1.6.4.1.5 | Integer32 | read-write | Battery discharge test duration . Effective range is 1-100 hours. Default :value is 10 hours Unit: hour |
| I32 hwBatteryTestTerminateVoltage | 1.3.6.1.4.1.2011.6.2.1.6.4.1.6 | Integer32 | read-write | Battery discharge test end voltage. Effective range (DC lack alarm voltage+0.5V-voltage of floating charge). Default: 45600 Unit: mV |
| I32 hwBatteryTestTotalDischargeAH | 1.3.6.1.4.1.2011.6.2.1.6.4.1.7 | Integer32 | read-only | Total discharge AH. Unit: mAH |
| INT hwBatteryTestOperStatus | 1.3.6.1.4.1.2011.6.2.1.6.4.1.8 | INTEGER | read-only | Battery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto discharge test is disabled 3. timeautoTestPermit(3) - indicates that timing auto discharge test is enabled 4. offautoTestPermit(4) - indicates that off auto discharge test is enabled 5. timeoffautoTestPermit(5) - indicates that timing-off auto discharge test is enabled |
| INT hwBatteryTestPhase | 1.3.6.1.4.1.2011.6.2.1.6.4.1.9 | INTEGER | read-only | Battery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(3) - indicates the power equipment recording test result 4. finish(4) - indicates that the discharge is complete 5.waitingfordischarge(5) - indicates that preparation is ready for discharge command |
| I32 hwBatteryTestStartHour | 1.3.6.1.4.1.2011.6.2.1.6.4.1.10 | Integer32 | read-write | Discharge start time. Effective range is 0 23 Default: 0 Unit: hour |
| I32 hwBatteryTestAlarmThreshold | 1.3.6.1.4.1.2011.6.2.1.6.4.1.11 | Integer32 | read-write | The battery discharge test alarm threshold in ratio of the range:1~79. |
| hwBatteryLogTestTable | 1.3.6.1.4.1.2011.6.2.1.6.5 | not-accessible | Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery. | |
| hwBatteryLogTestEntry | 1.3.6.1.4.1.2011.6.2.1.6.5.1 | not-accessible | Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwBatteryLogTestIndex. hwEnvEmuIndex is the index of the monitored unit. hwPowerIndex is the index of the power supply monitored by the monitoring unit. hwBatteryLogTestIndex is the index of the monitored battery. | |
| I32 hwBatteryLogTestIndex | 1.3.6.1.4.1.2011.6.2.1.6.5.1.1 | Integer32 | read-only | Battery discharge test result index |
| DAT hwBatteryLogTestStartTime | 1.3.6.1.4.1.2011.6.2.1.6.5.1.2 | DateAndTime | read-only | Battery discharge test start time |
| I32 hwBatteryLogTestDischargeDuration | 1.3.6.1.4.1.2011.6.2.1.6.5.1.3 | Integer32 | read-only | Duration of discharge. Unit: minute |
| I32 hwBatteryLogTestTerminateVoltage | 1.3.6.1.4.1.2011.6.2.1.6.5.1.4 | Integer32 | read-only | End voltage of battery discharge test . Unit: mV |
| INT hwBatteryLogTestBatteryStatus | 1.3.6.1.4.1.2011.6.2.1.6.5.1.5 | INTEGER | read-only | Battery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unknown(3) - indicates the batter test state is unknown |
| I32 hwBatteryLogTestTotalDischargeAH | 1.3.6.1.4.1.2011.6.2.1.6.5.1.6 | Integer32 | read-only | Discharge cumulate AH. Unit: mAH |
| INT hwBatteryLogTestFinish | 1.3.6.1.4.1.2011.6.2.1.6.5.1.7 | INTEGER | read-only | Battery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTerminated(3) - indicates that the test is stopped by alarms 4. hostTerminated(4) - indicates that the test is stopped by the host 5. overtimeTerminated(5) - indicates that the test is stopped because of over 100 hours 6. notTest(6) - indicates that the test is not started |
| I32 hwBatteryLogTestEfficiency | 1.3.6.1.4.1.2011.6.2.1.6.5.1.8 | Integer32 | read-only | The information of battery test efficiency. |
| I32 hwBatteryLogTestBatteryTemperature | 1.3.6.1.4.1.2011.6.2.1.6.5.1.9 | Integer32 | read-only | Battery discharge test end Temperature. Unit: 0.01 Degree |
| I32 hwBatteryLogTestBatteryCurrent | 1.3.6.1.4.1.2011.6.2.1.6.5.1.10 | Integer32 | read-only | Battery discharge test average Current. Unit: mA |
| hwRemoteProvidePowerInfoTable | 1.3.6.1.4.1.2011.6.2.1.7 | not-accessible | Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| hwRemoteProvidePowerInfoEntry | 1.3.6.1.4.1.2011.6.2.1.7.1 | not-accessible | Remote provide power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the index of the power supply monitored by the monitoring unit. | |
| INT hwPowerCentralState | 1.3.6.1.4.1.2011.6.2.1.7.1.1 | INTEGER | read-only | State of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature |
| INT hwPowerCentralDCInPutState | 1.3.6.1.4.1.2011.6.2.1.7.1.2 | INTEGER | read-only | State of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the voltage overflow |
| INT hwPowerCentralDCOutputState | 1.3.6.1.4.1.2011.6.2.1.7.1.3 | INTEGER | read-only | State of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates the voltage overflow 4. loadOver(4) - indicates the over-loading 5. shortCircuit(5) - indicates the short circuit 6. noLoad(6) - indicates no load |
| INT hwPowerCentralDCOutputMode | 1.3.6.1.4.1.2011.6.2.1.7.1.4 | INTEGER | read-only | Mode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode |
| INT hwPowerRemoteCommState | 1.3.6.1.4.1.2011.6.2.1.7.1.5 | INTEGER | read-write | Remote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) - indicates the sending of fault |
| INT hwPowerRemoteDCInputState | 1.3.6.1.4.1.2011.6.2.1.7.1.6 | INTEGER | read-write | State of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow |
| INT hwPowerRemoteLineCurState | 1.3.6.1.4.1.2011.6.2.1.7.1.7 | INTEGER | read-write | state of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage(3) - indicates the cur Leakage 4.curOver(4) - indicates the cur Over |
| INT hwPowerRemotePowerState | 1.3.6.1.4.1.2011.6.2.1.7.1.8 | INTEGER | read-write | state of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state |
| BIT hwPowerRemoteLineState | 1.3.6.1.4.1.2011.6.2.1.7.1.9 | Bits | read-write | State of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state 3. u3state(2) - indicates the power remote line state is u3 state 4. u4state(3) - indicates the power remote line state is u4 state 5. a1state(4) - indicates the power remote line state is a1 state 6. a2state(5) - indicates the power remote line state is a2 state 7. a3state(6) - indicates the power remote line state is a3 state 8. a4state(7) - indicates the power remote line state is a4 state |
| INT hwPowerCentralLoadState | 1.3.6.1.4.1.2011.6.2.1.7.1.10 | INTEGER | read-write | state of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load |
| hwACInfomationTable | 1.3.6.1.4.1.2011.6.2.1.8 | not-accessible | AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. | |
| hwACInfomationEntry | 1.3.6.1.4.1.2011.6.2.1.8.1 | not-accessible | AC infomation table. The table is not supported. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. | |
| INT hwACInfoCommState | 1.3.6.1.4.1.2011.6.2.1.8.1.1 | INTEGER | read-only | communication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indicates the communication state of AC is fault |
| INT hwACInfoThunderState | 1.3.6.1.4.1.2011.6.2.1.8.1.2 | INTEGER | read-only | Thunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fault |
| I32 hwACInfoCurrentLoop | 1.3.6.1.4.1.2011.6.2.1.8.1.3 | Integer32 | read-only | Current AC input working loop. The leaf is not supported. |
| INT hwACInfoMCBTrigger | 1.3.6.1.4.1.2011.6.2.1.8.1.4 | INTEGER | read-only | AC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. break-down(1)- indicates the AC input MCB trigger state is break-down |
| I32 hwACInfoFrequency | 1.3.6.1.4.1.2011.6.2.1.8.1.5 | Integer32 | read-only | The infomation of AC input frequency. This leaf is not supported. Unit: HZ |
| ROW hwACInfoRowStatus | 1.3.6.1.4.1.2011.6.2.1.8.1.6 | RowStatus | read-write | RowStatus standard operation The leaf is not supported. |
| hwPowerMibTrap | 1.3.6.1.4.1.2011.6.2.2 | |||
| hwPowerTrapOid | 1.3.6.1.4.1.2011.6.2.2.1 | |||
| hwPowerTrapsDefine | 1.3.6.1.4.1.2011.6.2.2.2 | |||
| hwPowerTraps | 1.3.6.1.4.1.2011.6.2.2.2.0 | |||
| NTF powerConnFaultAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.1 | This trap message is reported when the communication between the power module and the monitoring board is fault. | ||
| NTF powerConnFaultAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.2 | This trap message is reported when the communication between the power module and the monitoring board resumes. | ||
| NTF acInputVoltageAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.3 | This trap message is reported when there is a exception of AC input voltage. | ||
| NTF acInputVoltageAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.4 | This trap message is reported when the state of AC input voltage resumes. | ||
| NTF acInputVoltageHighAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.5 | This trap message is reported when the input voltage is too high. | ||
| NTF acInputVoltageHighAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.6 | This trap message is reported when the input voltage resumes to the normal range from a high value. | ||
| NTF acInputVoltageLowAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.7 | This trap message is reported when the input voltage is too low. | ||
| NTF acInputVoltageLowAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.8 | This trap message is reported when the input voltage resumes to the normal range from a low value. | ||
| NTF dcOutputVoltageHighAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.9 | This trap message is reported when the output voltage is too high. | ||
| NTF dcOutputVoltageHighAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.10 | This trap message is reported when the output voltage resumes to the normal range from a high value. | ||
| NTF dcOutputCurrentHighAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.11 | This trap message is reported when the output current is too high. | ||
| NTF dcOutputCurrentHighAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.12 | This trap message is reported when the output current resumes to the normal range from a high value. | ||
| NTF dcOutputVoltageLowAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.13 | This trap message is reported when the output voltage is too low. | ||
| NTF dcOutputVoltageLowAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.14 | This trap message is reported when the output voltage resumes to the normal range from a low value. | ||
| NTF dcOutputCurrentLowAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.15 | This trap message is reported when the output current is too low. | ||
| NTF dcOutputCurrentLowAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.16 | This trap message is reported when the output current resumes to the normal range from a low value. | ||
| NTF overLoadPowerAbnormalAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.17 | This trap message is reported when the state of load power is abnormal. | ||
| NTF overLoadPowerAbnormalAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.18 | This trap message is reported when the state of load power recovers to normal. | ||
| NTF overBattPowerOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.19 | This trap message is reported when the battery is powered off. | ||
| NTF overBattPowerOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.20 | This trap message is reported when the battery is powered on. | ||
| NTF overLoadPowerOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.21 | This trap message is reported when the loadpower is powered off. | ||
| NTF overLoadPowerOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.22 | This trap message is reported when the loadpower is powered on. | ||
| NTF acMainsSupplyAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.23 | This trap message is reported when the AC mains supply is abnormal. | ||
| NTF acMainsSupplyAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.24 | This trap message is reported when the AC mains supply recovers to normal. | ||
| NTF batteryLoopAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.25 | This trap message is reported when the loop of battery group disconnects. | ||
| NTF batteryLoopAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.26 | This trap message is reported when the loop of battery group connects. | ||
| NTF batteryFuseAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.27 | This trap message is reported when the fuse of battery group disconnects. | ||
| NTF batteryFuseAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.28 | This trap message is reported when the fuse of battery group connects. | ||
| NTF batteryContachAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.29 | This trap message is reported when the contactor of battery group disconnects. | ||
| NTF batteryContachAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.30 | This trap message is reported when the contactor of battery group connects. | ||
| NTF userModuleOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.31 | This trap message is reported when the user module is powered off. | ||
| NTF userModuleOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.32 | This trap message is reported when the user module is powered on. | ||
| NTF transferModuleOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.33 | This trap message is reported when the transfer module is powered off. | ||
| NTF transferModuleOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.34 | This trap message is reported when the transfer module is powered on. | ||
| NTF userModuleSwitchAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.35 | This trap message is reported when the user module is switched off. | ||
| NTF transferModuleSwitchAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.37 | This trap message is reported when the transfer module is switched off. | ||
| NTF loadFuseAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.39 | This trap message is reported when the load fuse is abnormal. | ||
| NTF loadFuseAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.40 | This trap message is reported when the load fuse resumes. | ||
| NTF chargeCtrlStateAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.41 | This trap message is reported when the control state of average or floating charge converts. | ||
| NTF chargeModeAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.42 | This trap message is reported when the charge state converts. | ||
| NTF acCommFailAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.43 | This trap message is reported when the AC panel communication fails. | ||
| NTF acCommFailAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.44 | This trap message is reported when the AC panel communication resumes. | ||
| NTF batteryChargeOverAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.45 | This trap message is reported when the Over-current of battery group happens. | ||
| NTF batteryChargeOverAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.46 | OThis trap message is reported when the Over-current of battery group resumes. | ||
| NTF batteryVoltageLackAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.47 | This trap message is reported when the voltage of battery group lacks. | ||
| NTF batteryVoltageLackAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.48 | This trap message is reported when the voltage of battery group recovers from lack. | ||
| NTF loadTwiceOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.49 | This trap message is reported when the load is powered off twice. | ||
| NTF loadTwiceOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.50 | This trap message is reported when the load recovers from powering off twice. | ||
| NTF loadOnceOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.51 | This trap message is reported when the load is powered off once. | ||
| NTF loadOnceOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.52 | This trap message is reported when the load recovers from powering off once. | ||
| NTF acInputPowerOffAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.53 | This trap message is reported when the AC input is powered off. | ||
| NTF acInputPowerOffAlarmResume | 1.3.6.1.4.1.2011.6.2.2.2.0.54 | This trap message is reported when the AC input power is powered off. | ||
| NTF acInputLoopSwtichAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.55 | This trap message is reported when the AC input loop switches to another one. | ||
| NTF batteryDischargeTestStartAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.56 | This trap message is reported when the battery discharge test starts. | ||
| NTF batteryDischargeTestStopAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.57 | This trap message is reported when the battery discharge test stops. | ||
| NTF powerProtectAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.58 | This trap message is reported when the power protection function is enbaled. | ||
| NTF powerUndoProtectAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.59 | This trap message is reported when the power protection function is disabled. | ||
| NTF powerCentralOutputModeSwtichAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.60 | This trap message is reported when the central output mode swtiches to another one. | ||
| NTF powerCentralTempretaureAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.61 | This trap message is reported when the central tempretaure is abnormal. | ||
| NTF powerCentralInputAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.62 | This trap message is reported when the central input voltage is abnormal. | ||
| NTF powerCentralOutputAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.63 | This trap message is reported when the central output voltage is abnormal. | ||
| NTF powerRemoteCommFaultAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.64 | This trap message is reported when the communiction between the remote and central fails. | ||
| NTF powerRemoteVoltageAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.65 | This trap message is reported when the remote voltage is abnormal. | ||
| NTF powerLineAlarm | 1.3.6.1.4.1.2011.6.2.2.2.0.66 | This trap message is reported when the power line is abnormal. | ||
| NTF powerRemotePowerAlarm1 | 1.3.6.1.4.1.2011.6.2.2.2.0.67 | This trap message is reported when the remote power is abnormal. | ||
| NTF powerRemotePowerAlarm2 | 1.3.6.1.4.1.2011.6.2.2.2.0.68 | This trap message is reported when the Line UA is abnormal. | ||
| NTF powerRemotePowerAlarm3 | 1.3.6.1.4.1.2011.6.2.2.2.0.69 | This trap message is reported when the Central load is abnormal. | ||
| powerConformance | 1.3.6.1.4.1.2011.6.2.3 | |||
| powerCompliances | 1.3.6.1.4.1.2011.6.2.3.1 | |||
| powerGroups | 1.3.6.1.4.1.2011.6.2.3.2 | |||
| hwEnvironPowerTraps | 1.3.6.1.4.1.2011.6.2.4 | |||
| hwEnvironPowerCommonTraps | 1.3.6.1.4.1.2011.6.2.4.1 | |||
| hwEnvironPowerAlarmTraps | 1.3.6.1.4.1.2011.6.2.4.2 | |||
| hwEnvironPowerAlarmTrapsPrefix | 1.3.6.1.4.1.2011.6.2.4.2.0 | |||
| NTF hwEmmPowerBattaryTestStartTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.1 | The agent generates this trap when the power device battary discharge test starts. | ||
| NTF hwEmmPowerBattaryTestStopTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.2 | The agent generates this trap when the power device battary discharge test ends. | ||
| NTF hwEmmPowerAcvolFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.3 | The agent generates this trap when the power device AC input voltage is abnormal. | ||
| NTF hwEmmPowerAcvolRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.4 | The agent generates this trap when the power device AC input voltage recovers. | ||
| NTF hwEmmPowerDcvolFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.5 | The agent generates this trap when the power device DC output voltage is abnormal. | ||
| NTF hwEmmPowerDcvolRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.6 | The agent generates this trap when the power device DC output voltage recovers. | ||
| NTF hwEmmPowerBattloopFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.7 | The agent generates this trap when the power device the battery loop is broken. In this case, the function of he backup power is lost. | ||
| NTF hwEmmPowerBattloopRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.8 | The agent generates this trap when the power device battery loop recovers. | ||
| NTF hwEmmPowerLoadfuseFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.9 | The agent generates this trap when the fuse of the power device is broken. In this case, the device is powered off. | ||
| NTF hwEmmPowerLoadfuseRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.10 | The agent generates this trap when the fuse of the power device recovers. | ||
| NTF hwEmmPowerRectifierFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.11 | The agent generates this trap when the rectifier module of the power device is abnormal and the spully power may decrease. | ||
| NTF hwEmmPowerRectifierRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.12 | The agent generates this trap when the rectifier module of the power device recovers. | ||
| NTF hwEmmDigMainsupplyFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.13 | The agent generates this trap when the main supply digital is faulty. | ||
| NTF hwEmmDigMainsupplyRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.14 | The agent generates this trap when the main supply digital recovers. | ||
| NTF hwEmmPowerBatteryOffTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.15 | The agent generates this trap when the power of battary is off. | ||
| NTF hwEmmBatt1TempFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.16 | The agent generates this trap when the battery group 1 temperature sensor fault occurs. | ||
| NTF hwEmmBatt1TempRestoreTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.17 | The agent generates this trap when the battery group 1 temperature sensor fault recovers. | ||
| NTF hwEmmEnviHumFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.18 | The agent generates this trap when the environment humidity sensor fault occurs. | ||
| NTF hwEmmEnviHumRestoreTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.19 | The agent generates this trap when the environment humidity sensor fault recovers. | ||
| NTF hwEmmEnvi1TempFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.20 | The agent generates this trap when the environment 1 temperature sensor fault occurs. | ||
| NTF hwEmmEnvi1TempRestoreTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.21 | The agent generates this trap when the environment 1 temperature sensor fault recovers. | ||
| NTF hwEmmBattTemFaultTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.22 | The agent generates this trap when the battery temperature out of normal range. | ||
| NTF hwEmmBattTemRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.23 | The agent generates this trap when the battery temperature recovers to normal range. | ||
| NTF hwEmmPowerBatteryOffRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.24 | The agent generates this trap when the power of battary recovers to on state. | ||
| NTF hwEmmPowerBatteryUnDetectTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.25 | The agent generates this trap when the one or more batteries are not detected. | ||
| NTF hwEmmPowerBatteryDetectRecoverTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.26 | The agent generates this trap when the batteries recover. | ||
| NTF hwPowerModuleMismatchTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.27 | The agent generates this trap when the the power supply system detects mismatched power module . | ||
| NTF hwPowerModuleRestoreTrap | 1.3.6.1.4.1.2011.6.2.4.2.0.28 | The agent generates this trap when the power module recovers. |
RFC description
Huawei power monitoring MIB for managing power supplies, batteries, chargers, and battery test operations in network devices.