npIoPulseCounter

Module: DKSF-70-4-X-X-1

OID (symbolic): DKSF-70-4-X-X-1::npIoPulseCounter

OID (numeric): 1.3.6.1.4.1.25728.8900.1.1.9

Node type: OBJECT-TYPE

Type: Counter32

Access: read-write

Description: Pulse Counter on IO input line (counts positive fronts) Write 0 to reset.

What is npIoPulseCounter?

Counts positive-going pulses (rising edges) detected on this input line, useful for totalizing events like door openings or flow-meter pulses; writing 0 resets the counter. Despite its Counter32 syntax it is writable specifically to support this reset behavior.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.25728.8900.1.1.9
snmpwalk -v2c -c public <target> DKSF-70-4-X-X-1::npIoPulseCounter

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.25728.8900.1.1.9.1
snmpget -v2c -c public <target> DKSF-70-4-X-X-1::npIoPulseCounter.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.25728.8900.1.1.9.1 i <value>

Start monitoring NetPing DKSF-70 environmental sensor/relay controller with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DKSF-70-4-X-X-1::npIoPulseCounter OID value, configure state conditions and alerts, and monitor any NetPing DKSF-70 environmental sensor/relay controller from a single console.

How to Use in IPNetwork Monitor

Select a NetPing DKSF-70 environmental sensor/relay controller as the target host to create a monitor — the SNMP service should be up and running on it. Click New Monitor, then check SNMP Custom on the Favorites tab, click Next, and confirm the host. On the next page, click Select... to open the built-in SNMP MIB Browser and type npIoPulseCounter into the Find box to locate it in the OID tree, selecting the specific row/instance you want to monitor since this is a table column, then select it and click OK. It reports the pulse Counter on IO input line (counts positive fronts) Write 0 to reset. On the monitor's Main parameters page you can set the target's SNMP port (default 161), credentials, polling interval, and other settings — see the SNMP Monitor help for details. On the State conditions and Alerting tabs, configure when the monitor should change state and trigger an alert; since this is a Counter32-type OID, Value bounds is the most useful condition here — trigger an alert if the counter increases sharply between polls relative to its normal baseline, since an unexpected spike often reflects a real change in traffic or activity. Click Finish to create the monitor; you can adjust any parameter later.

OID Breakdown

Upper-level ancestors (10 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.25728lightcomDKSF-201-9-X-X-1
1.3.6.1.4.1.25728.8900npIoDKSF-201-9-X-X-1
1.3.6.1.4.1.25728.8900.1npIoTableDKSF-201-9-X-X-1
1.3.6.1.4.1.25728.8900.1.1npIoEntryDKSF-201-9-X-X-1
Numeric OIDNameModule
1.3.6.1.4.1.25728.8900.1.1.9npIoPulseCounterDKSF-70-4-X-X-1