All MIBs › TIC-RMTI4-G9000-G2020-MIB
Category: Industrial and Sensor Devices
Description: Manages TIC RMTI4 industrial gateway configuration, I/O interfaces, and operational state.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is TIC-RMTI4-G9000-G2020-MIB?
Based on its object set, this module manages a Toshiba-brand uninterruptible power supply (UPS), sitting under an equ/equUPS enterprise branch, rather than the industrial gateway its name might suggest. It exposes UPS identification data — manufacturer, type/form, firmware version, system name, and attached devices — alongside AC input power measurements, specifically three-phase line-to-line voltages and their percentage of nominal. It is explicitly used to monitor UPS hardware and firmware status: confirming the installed firmware version for inventory/compliance, and tracking per-phase input voltage and percent-of-nominal values to catch abnormal utility power feeding the UPS before it affects protected equipment. Its object naming closely follows the structure of the standard UPS-MIB (RFC 1628) conventions (upsIdent*, upsInput*), suggesting it was derived from or is closely aligned with that standard. It is typically deployed in a data center or equipment room where the UPS protects critical networking or industrial gateway hardware, polled by facilities or NMS systems for power-quality monitoring. Engineers can download the TIC-RMTI4-G9000-G2020-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in TIC-RMTI4-G9000-G2020-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Toshiba UPS (uninterruptible power supply)
Monitoring Examples
upsIdentManufacturer and upsIdentUPSFirmwareVersion let an administrator confirm the UPS vendor and firmware revision during an equipment audit, while upsInputLLVoltageAB, upsInputLLVoltageBC, and upsInputLLVoltageCA report the three-phase line-to-line input voltages, paired with upsInputLLVoltagePercentAB/BC/CA expressing each as a percentage of nominal. An operator would alert when any percent-of-nominal value falls outside an expected band, signaling a utility power sag or surge upstream of the UPS, and would check upsIdentAttachedDevices to see which downstream equipment depends on that UPS.
What Can Be Monitored
- UPS manufacturer/model identification
- firmware version
- attached device list
- input voltage per phase (AB/BC/CA)
- input voltage percent of nominal per phase
- number of input phases
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Gauge32 | |
| Integer32 | |
| enterprises |
From SNMPv2-TC
| AutonomousType | |
| DisplayString | |
| TestAndIncr | |
| TimeInterval | |
| TimeStamp |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| toshiba | 1.3.6.1.4.1.186 | |||
| equ | 1.3.6.1.4.1.186.1 | |||
| equUPS | 1.3.6.1.4.1.186.1.19 | |||
| ticUPS | 1.3.6.1.4.1.186.1.19.2 | |||
| rmti4 | 1.3.6.1.4.1.186.1.19.2.5 | |||
| upsG9000_G2020 | 1.3.6.1.4.1.186.1.19.2.5.1 | |||
| NTF upsTrapFault | 1.3.6.1.4.1.186.1.19.2.5.1.0.1 | Alarm: One or more fault/status alarm(s) reported. | ||
| NTF upsTrapFaultClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.2 | Alarm Clear: One or more fault/status reported. | ||
| NTF upsTrapOnBattery | 1.3.6.1.4.1.186.1.19.2.5.1.0.3 | Info: The UPS is on Battery Mode. | ||
| NTF upsTrapOnBatteryClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.4 | Info Clear: The UPS is on Battery Mode. | ||
| NTF upsTrapBatteryLow | 1.3.6.1.4.1.186.1.19.2.5.1.0.5 | Warning: Battery Low Voltage. | ||
| NTF upsTrapBatteryLowClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.6 | Warning Clear: Battery Low Voltage. | ||
| NTF upsTrapBatteryDepleted | 1.3.6.1.4.1.186.1.19.2.5.1.0.7 | Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load. | ||
| NTF upsTrapBatteryDepletedClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.8 | Warning Clear: UPS contains depleted batteries, it will be unable to support critical loads. Shutdown excess equipment to reduce load.. | ||
| NTF upsTrapBatteryOverheat | 1.3.6.1.4.1.186.1.19.2.5.1.0.9 | Fault: Battery Overheat. | ||
| NTF upsTrapBatteryOverheatClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.10 | Fault Clear: Battery Overheat. | ||
| NTF upsTrapBatteryVoltageAbnormal | 1.3.6.1.4.1.186.1.19.2.5.1.0.11 | Fault: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapBatteryVoltageAbnormalClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.12 | Fault Clear: Battery Voltage Abnormal. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapUPSOverheat | 1.3.6.1.4.1.186.1.19.2.5.1.0.13 | Fault: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapUPSOverheatClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.14 | Fault Clear: UPS Overheat, heatsinks temperature exceeds thermal settings. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapPowerFailure | 1.3.6.1.4.1.186.1.19.2.5.1.0.15 | Info: Power Failure. | ||
| NTF upsTrapPowerFailureClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.16 | Info Clear: PowerFailure. | ||
| NTF upsTrapUPSOverload | 1.3.6.1.4.1.186.1.19.2.5.1.0.17 | Fault: UPS Overload (OL), the output load exceeds the rated current. Decrease load. | ||
| NTF upsTrapUPSOverloadClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.18 | Fault Clear: UPS Overload (OL), the output load exceeds the rated current. Decrease load. | ||
| NTF upsTrapUserDefinedOverloadWarning | 1.3.6.1.4.1.186.1.19.2.5.1.0.19 | Warning: The inverter output load % is greater than the user defined overload set point (default: 110%). | ||
| NTF upsTrapUserDefinedOverloadWarningClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.20 | Warning Clear: The inverter output load % is greater than the user defined overload set point (default: 110%). | ||
| NTF upsTrapOnBypass | 1.3.6.1.4.1.186.1.19.2.5.1.0.21 | Warning:On Bypass. | ||
| NTF upsTrapOnBypassClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.22 | Warning Clear: On Bypass. | ||
| NTF upsTrapOutputOff | 1.3.6.1.4.1.186.1.19.2.5.1.0.23 | Info: The UPS output is off. | ||
| NTF upsTrapOutputOffClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.24 | Info Clear: The UPS output is off. | ||
| NTF upsTrapAsyncOperation | 1.3.6.1.4.1.186.1.19.2.5.1.0.25 | Warning: Inverter Synchronous. | ||
| NTF upsTrapAsyncOperationClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.26 | Warning Clear: Inverter Synchronous. | ||
| NTF upsTrapDCBusOverCurrent | 1.3.6.1.4.1.186.1.19.2.5.1.0.27 | Fault: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusOverCurrentClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.28 | Fault Clear: DC Overcurrent (DCOC). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusOverVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.0.29 | Fault: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusOverVoltageClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.30 | Fault Clear: DC Overvoltage (DCOV). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusUnderVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.0.31 | Fault: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusUnderVoltageClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.32 | Fault Clear: DC Undervoltage (DCUV). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusImbalance | 1.3.6.1.4.1.186.1.19.2.5.1.0.33 | Fault: DC Unbalance. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapDCBusImbalanceClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.34 | Fault Clear: DC Unbalance. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapOutputUnderVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.0.35 | Fault: Output Undervoltage. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapOutputUnderVoltageClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.36 | Fault Clear: Output Undervoltage. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapOutputOverVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.0.37 | Fault: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapOutputOverVoltageClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.38 | Fault Clear: Output Overvoltage (VLOV). Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapInverterOverload | 1.3.6.1.4.1.186.1.19.2.5.1.0.39 | Fault: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load. | ||
| NTF upsTrapInverterOverloadClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.40 | Fault Clear: UPS Overload, short time over-current has been detected during On-Line operation. Decrease Load. | ||
| NTF upsTrapInverterOvercurrent | 1.3.6.1.4.1.186.1.19.2.5.1.0.41 | Fault: Inverter Overcurrent. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapInverterOvercurrentClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.42 | Fault Clear: Inverter Overcurrent. Contact your Toshiba authorized service center for examination. | ||
| NTF upsTrapRemotEyeCommError | 1.3.6.1.4.1.186.1.19.2.5.1.0.43 | Warning: RemotEye UPS communication error. | ||
| NTF upsTrapRemotEyeCommErrorClear | 1.3.6.1.4.1.186.1.19.2.5.1.0.44 | Warning Clear:RemotEye UPS communication error. | ||
| upsIdent | 1.3.6.1.4.1.186.1.19.2.5.1.1 | |||
| STR upsIdentManufacturer | 1.3.6.1.4.1.186.1.19.2.5.1.1.1 | DisplayString | read-only | The name of the UPS manufacturer. |
| STR upsIdentTypeform | 1.3.6.1.4.1.186.1.19.2.5.1.1.2 | DisplayString | read-only | The UPS Model designation. |
| STR upsIdentUPSFirmwareVersion | 1.3.6.1.4.1.186.1.19.2.5.1.1.3 | DisplayString | read-only | The UPS firmware version. |
| STR upsIdentSysName | 1.3.6.1.4.1.186.1.19.2.5.1.1.4 | DisplayString | read-write | A string identifying the UPS. This object is set by the administrator. |
| STR upsIdentAttachedDevices | 1.3.6.1.4.1.186.1.19.2.5.1.1.5 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator. |
| upsInput | 1.3.6.1.4.1.186.1.19.2.5.1.2 | |||
| NUM upsInputNumOfPhases | 1.3.6.1.4.1.186.1.19.2.5.1.2.1 | NonNegativeInteger | read-only | Number of input lines. This data is used by upsInputNumLines. |
| NUM upsInputLLVoltageAB | 1.3.6.1.4.1.186.1.19.2.5.1.2.2 | NonNegativeInteger | read-only | The input line to line voltage for AB in RMS volts. |
| NUM upsInputLLVoltageBC | 1.3.6.1.4.1.186.1.19.2.5.1.2.3 | NonNegativeInteger | read-only | The input line to line voltage for BC in RMS volts. |
| NUM upsInputLLVoltageCA | 1.3.6.1.4.1.186.1.19.2.5.1.2.4 | NonNegativeInteger | read-only | The input line to line voltage for CA in RMS volts. |
| NUM upsInputLLVoltagePercentAB | 1.3.6.1.4.1.186.1.19.2.5.1.2.5 | NonNegativeInteger | read-only | The input line to line voltage percent for AB. |
| NUM upsInputLLVoltagePercentBC | 1.3.6.1.4.1.186.1.19.2.5.1.2.6 | NonNegativeInteger | read-only | The input line to line voltage percent for BC. |
| NUM upsInputLLVoltagePercentCA | 1.3.6.1.4.1.186.1.19.2.5.1.2.7 | NonNegativeInteger | read-only | The input line to line voltage percent for CA. |
| NUM upsInputCurrentPhaseA | 1.3.6.1.4.1.186.1.19.2.5.1.2.8 | NonNegativeInteger | read-only | The input phase current for Phase A. |
| NUM upsInputCurrentPhaseB | 1.3.6.1.4.1.186.1.19.2.5.1.2.9 | NonNegativeInteger | read-only | The input phase current unit for Phase B. |
| NUM upsInputCurrentPhaseC | 1.3.6.1.4.1.186.1.19.2.5.1.2.10 | NonNegativeInteger | read-only | The input phase current unit for Phase C. |
| NUM upsInputFrequency | 1.3.6.1.4.1.186.1.19.2.5.1.2.11 | NonNegativeInteger | read-only | The input frequency unit 0.1 Hertz. |
| NUM upsInputActivePowerA | 1.3.6.1.4.1.186.1.19.2.5.1.2.12 | NonNegativeInteger | read-only | The magnitude of the present input true power for phase A. |
| NUM upsInputActivePowerB | 1.3.6.1.4.1.186.1.19.2.5.1.2.13 | NonNegativeInteger | read-only | The magnitude of the present input true power for phase B. |
| NUM upsInputActivePowerC | 1.3.6.1.4.1.186.1.19.2.5.1.2.14 | NonNegativeInteger | read-only | The magnitude of the present input true power for phase C. |
| NUM upsInputTotalActivePower | 1.3.6.1.4.1.186.1.19.2.5.1.2.15 | NonNegativeInteger | read-only | The magnitude of the total input true power. |
| NUM upsInputRatedLLVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.2.16 | NonNegativeInteger | read-only | The input line to line rated voltage in RMS volts. |
| upsOutput | 1.3.6.1.4.1.186.1.19.2.5.1.3 | |||
| INT upsOutputSource | 1.3.6.1.4.1.186.1.19.2.5.1.3.1 | INTEGER | read-only | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker. |
| NUM upsOutputNumOfPhases | 1.3.6.1.4.1.186.1.19.2.5.1.3.2 | NonNegativeInteger | read-only | The number of output lines utilized in this device. |
| NUM upsOutputLLVoltageAB | 1.3.6.1.4.1.186.1.19.2.5.1.3.3 | NonNegativeInteger | read-only | The output line to line voltage for AB in RMS volts. |
| NUM upsOutputLLVoltageBC | 1.3.6.1.4.1.186.1.19.2.5.1.3.4 | NonNegativeInteger | read-only | The output line to line voltage for BC in RMS volts. |
| NUM upsOutputLLVoltageCA | 1.3.6.1.4.1.186.1.19.2.5.1.3.5 | NonNegativeInteger | read-only | The output line to line voltage for CA in RMS volts. |
| NUM upsOutputCurrentPhaseA | 1.3.6.1.4.1.186.1.19.2.5.1.3.6 | NonNegativeInteger | read-only | The Output phase current for phase A in amps. |
| NUM upsOutputCurrentPhaseB | 1.3.6.1.4.1.186.1.19.2.5.1.3.7 | NonNegativeInteger | read-only | The Output phase current for phase B in amps. |
| NUM upsOutputCurrentPhaseC | 1.3.6.1.4.1.186.1.19.2.5.1.3.8 | NonNegativeInteger | read-only | The Output phase current for phase C in amps. |
| NUM upsOutputFrequency | 1.3.6.1.4.1.186.1.19.2.5.1.3.9 | NonNegativeInteger | read-only | The Output Frequency for phase A in 1/10 of HZ. |
| INT upsOutputCurrentPercentA | 1.3.6.1.4.1.186.1.19.2.5.1.3.10 | INTEGER | read-only | The output current for phase A in percent. |
| INT upsOutputCurrentPercentB | 1.3.6.1.4.1.186.1.19.2.5.1.3.11 | INTEGER | read-only | The output current for phase B in percent. |
| INT upsOutputCurrentPercentC | 1.3.6.1.4.1.186.1.19.2.5.1.3.12 | INTEGER | read-only | The output current for phase C in percent. |
| NUM upsOutputTotalActivePower | 1.3.6.1.4.1.186.1.19.2.5.1.3.13 | NonNegativeInteger | read-only | The output active power. |
| NUM upsOutputTotalActivePowerPercent | 1.3.6.1.4.1.186.1.19.2.5.1.3.14 | NonNegativeInteger | read-only | The output active power in percent. |
| NUM upsOutputPowerFactor | 1.3.6.1.4.1.186.1.19.2.5.1.3.15 | NonNegativeInteger | read-only | The UPS output power factor. |
| NUM upsOutputRatedActivePower | 1.3.6.1.4.1.186.1.19.2.5.1.3.16 | NonNegativeInteger | read-only | The output rated active power for the UPS. |
| NUM upsOutputRatedApparentPower | 1.3.6.1.4.1.186.1.19.2.5.1.3.17 | NonNegativeInteger | read-only | The output rated apparent power for the UPS. |
| NUM upsOutputRatedLLVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.3.18 | NonNegativeInteger | read-only | The output rated line to line voltage for the UPS. |
| upsBypass | 1.3.6.1.4.1.186.1.19.2.5.1.4 | |||
| NUM upsBypassNumOfPhases | 1.3.6.1.4.1.186.1.19.2.5.1.4.1 | NonNegativeInteger | read-only | The number of bypass lines utilized. |
| NUM upsBypassLLVoltageAB | 1.3.6.1.4.1.186.1.19.2.5.1.4.2 | NonNegativeInteger | read-only | The Bypass line to line voltage for AB in RMS volts. |
| NUM upsBypassLLVoltageBC | 1.3.6.1.4.1.186.1.19.2.5.1.4.3 | NonNegativeInteger | read-only | The Bypass line to line voltage for BC in RMS volts. |
| NUM upsBypassLLVoltageCA | 1.3.6.1.4.1.186.1.19.2.5.1.4.4 | NonNegativeInteger | read-only | The Bypass line to line voltage for CA in RMS volts. |
| NUM upsBypassFrequency | 1.3.6.1.4.1.186.1.19.2.5.1.4.5 | NonNegativeInteger | read-only | The Bypass frequency in 0.1 Hertz. |
| upsBattery | 1.3.6.1.4.1.186.1.19.2.5.1.5 | |||
| INT upsBatteryStatus | 1.3.6.1.4.1.186.1.19.2.5.1.5.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run time sufficient to handle the load. A value of batteryLow indicates the battery level is low. Continued operation in battery mode will deplate batteries. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output). A value of batteryDischarging indicates UPS system is in Battery power. |
| NUM upsElapsedTimeOnBatteryPower | 1.3.6.1.4.1.186.1.19.2.5.1.5.2 | NonNegativeInteger | read-only | If the unit is on battery power, the elapsed time since the UPS on battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power. |
| NUM upsEstimatedBatteryRuntime | 1.3.6.1.4.1.186.1.19.2.5.1.5.3 | PositiveInteger | read-only | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. |
| NUM upsBatteryVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.5.4 | NonNegativeInteger | read-only | The battery voltage DC. |
| NUM upsBatteryVoltagePercent | 1.3.6.1.4.1.186.1.19.2.5.1.5.5 | NonNegativeInteger | read-only | Battery voltage in percent. |
| INT upsBatteryEstimatedCharge | 1.3.6.1.4.1.186.1.19.2.5.1.5.6 | INTEGER | read-only | An estimate of the charge to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off. |
| I32 upsBatteryDischargeCurrent | 1.3.6.1.4.1.186.1.19.2.5.1.5.7 | Integer32 | read-only | The present battery discharge Current in percent. |
| I32 upsBatteryChargeCurrent | 1.3.6.1.4.1.186.1.19.2.5.1.5.8 | Integer32 | read-only | The present battery charge Current in percent. |
| STR upsBatteryModel | 1.3.6.1.4.1.186.1.19.2.5.1.5.9 | DisplayString | read-write | The Battery manufacturer. |
| NUM upsBatteryInSeries | 1.3.6.1.4.1.186.1.19.2.5.1.5.10 | NonNegativeInteger | read-write | The Battery rated holding time in minutes. |
| NUM upsBatteryNumStrings | 1.3.6.1.4.1.186.1.19.2.5.1.5.11 | NonNegativeInteger | read-write | The Battery rated holding time in minutes. |
| NUM upsBatteryRatedAmpereHour | 1.3.6.1.4.1.186.1.19.2.5.1.5.12 | NonNegativeInteger | read-write | The Battery rated holding time in minutes. |
| STR upsBatteryRatedBackupTime | 1.3.6.1.4.1.186.1.19.2.5.1.5.13 | DisplayString | read-write | The Battery rated holding time in minutes. |
| STR upsBatteryInstallationDate | 1.3.6.1.4.1.186.1.19.2.5.1.5.14 | DisplayString | read-only | The battery install date. |
| upsAlarm | 1.3.6.1.4.1.186.1.19.2.5.1.6 | |||
| G32 upsAlarmsPresent | 1.3.6.1.4.1.186.1.19.2.5.1.6.1 | Gauge32 | read-only | The present number of active alarm conditions. |
| upsAlarmTable | 1.3.6.1.4.1.186.1.19.2.5.1.6.2 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmId equal to 1, and increments the value of upsAlarmId each time a new row is created, wrapping to the first free value greater than or equal to 1 when the maximum value of upsAlarmId would otherwise be exceeded. Consequently, after multiple operations, the table may become sparse, e.g., containing entries for rows 95, 100, 101, and 203 and the entries should not be assumed to be in chronological order because upsAlarmId might have wrapped. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms defined by a particular implementation, i.e., as documented in the private enterprise MIB definition for the device. No two rows will have the same value of upsAlarmDescr, since alarms define conditions. In order to meet this requirement, care should be taken in the definition of alarm conditions to insure that a system cannot enter the same condition multiple times simultaneously. The number of rows in the table at any given time is reflected by the value of upsAlarmsPresent. | |
| upsAlarmEntry | 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1 | not-accessible | An entry containing information applicable to a particular alarm. | |
| NUM upsAlarmId | 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.1 | PositiveInteger | not-accessible | A unique identifier for an alarm condition. This value must remain constant. |
| OID upsAlarmDescr | 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.2 | AutonomousType | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
| TIM upsAlarmTime | 1.3.6.1.4.1.186.1.19.2.5.1.6.2.1.3 | TimeStamp | read-only | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0. |
| upsWellKnownAlarms | 1.3.6.1.4.1.186.1.19.2.5.1.6.3 | |||
| INT upsAlarmFault | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.1 | INTEGER | read-only | Fault: A UPS fault/Alarm condition exists. |
| INT upsAlarmOnBattery | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.2 | INTEGER | read-only | Info: The UPS is on Battery mode; it is supplying output power from its batteries. |
| INT upsAlarmBatteryLow | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.3 | INTEGER | read-only | Warning: The battery level is low. It has dropped to less than 90% of its nominal value. Continued operation in Battery Mode will deplete Batteries and result in UPS output shut down. Reduce critical load to increase battery runtime. |
| INT upsAlarmBatteryDepleted | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.4 | INTEGER | read-only | Warning: UPS contains depleted batteries, it will be unable to support critical loads. Shut down excess equipment to reduce Load. |
| INT upsAlarmBatteryOverheat | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.5 | INTEGER | read-only | Fault: Detection of over temperature at the batteries. |
| INT upsAlarmBatteryVoltageAbnormal | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.6 | INTEGER | read-only | Fault: Battery voltage is abnormality. |
| INT upsAlarmUPSOverheat | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.7 | INTEGER | read-only | Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center. |
| INT upsAlarmPowerFailure | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.8 | INTEGER | read-only | Info: Power Failure. |
| INT upsAlarmUPSOverload | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.9 | INTEGER | read-only | Fault: The UPS is overloaded. UPS will switch to bypass operation or shut down if no action is taken. Shut down excess equipment to reduce Load. |
| INT upsAlarmUserDefinedOverloadWarning | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.10 | INTEGER | read-only | Warning: The inverter output load % is greater than the user defined overload set point (default: 110%). |
| INT upsAlarmOnBypass | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.11 | INTEGER | read-only | Warning: The UPS is in Stop (Bypass) mode. |
| INT upsAlarmOutputOff | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.12 | INTEGER | read-only | Info: The UPS output is off. |
| INT upsAlarmAsyncOperation | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.13 | INTEGER | read-only | Warning: Async Operation |
| INT upsAlarmDCBusOverCurrent | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.14 | INTEGER | read-only | Fault: UPS is reporting a DC bus overcurrent condition. Contact your Toshiba authorized service center for examination of a DCOC fault. |
| INT upsAlarmDCBusOverVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.15 | INTEGER | read-only | Fault: UPS is reporting a DC bus overvoltage condition. Contact your Toshiba authorized service center for examination of a DCOV fault. |
| INT upsAlarmDCBusUnderVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.16 | INTEGER | read-only | Fault: UPS is reporting a DC bus undervoltage condition. Contact your Toshiba authorized service center for examination of a DCUV fault. |
| INT upsAlarmDCBusImbalanced | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.17 | INTEGER | read-only | Fault: The DC imbalanced alarm detection. |
| INT upsAlarmOutputUnderVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.18 | INTEGER | read-only | Fault: UPS is reporting an output undervoltage condition. Contact your Toshiba authorized service center for examination of a INVUV fault. |
| INT upsAlarmOutputOverVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.19 | INTEGER | read-only | Fault: UPS is reporting an output overvoltage condition. Contact your Toshiba authorized service center for examination of a INVOV fault. |
| INT upsAlarmInverterOverload | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.20 | INTEGER | read-only | Fault: Short time over-current has been detected. |
| INT upsAlarmInverterOvercurrent | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.21 | INTEGER | read-only | Fault: Detection of inverter overcurrent. |
| INT upsAlarmRemotEyeCommError | 1.3.6.1.4.1.186.1.19.2.5.1.6.3.22 | INTEGER | read-only | Warning: Communication error between the RemotEye 4 and the UPS. |
| upsConfig | 1.3.6.1.4.1.186.1.19.2.5.1.7 | |||
| STR upsConfigModelIDString | 1.3.6.1.4.1.186.1.19.2.5.1.7.1 | DisplayString | read-only | UPS Model ID string. This string contains codes for the UPS series,input voltage, output voltage, output VA, and addition option. |
| STR upsConfigUPSFirmwareVersion | 1.3.6.1.4.1.186.1.19.2.5.1.7.2 | DisplayString | read-only | The G9000 software version. |
| NUM upsConfigInputNumOfPhases | 1.3.6.1.4.1.186.1.19.2.5.1.7.3 | NonNegativeInteger | read-only | Number of input lines. This data is used by upsInputNumLines. |
| NUM upsConfigRatedInputFrequency | 1.3.6.1.4.1.186.1.19.2.5.1.7.4 | NonNegativeInteger | read-only | The nominal input frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. |
| NUM upsConfigRatedInputLLVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.7.5 | NonNegativeInteger | read-write | The magnitude of the nominal input voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., badValue for SNMPv1, or inconsistentValue for SNMPv2. |
| NUM upsConfigRatedInputPowerFactor | 1.3.6.1.4.1.186.1.19.2.5.1.7.6 | PositiveInteger | read-only | UNITS are in hundredths. For 0.95 = 95. |
| NUM upsConfigOutputNumOfPhases | 1.3.6.1.4.1.186.1.19.2.5.1.7.7 | NonNegativeInteger | read-only | Number of output lines. This data is used by upsOutputNumLines. |
| NUM upsConfigRatedOutputFrequency | 1.3.6.1.4.1.186.1.19.2.5.1.7.8 | NonNegativeInteger | read-only | The nominal output frequency. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2. |
| NUM upsConfigRatedOutputLLVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.7.9 | NonNegativeInteger | read-write | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a value that is not supported, the request must be rejected and the agent shall respond with an appropriate error message, i.e., bad Value for SNMPv1, or inconsistent Value for SNMPv2. |
| NUM upsConfigRatedOutputApperentPower | 1.3.6.1.4.1.186.1.19.2.5.1.7.10 | NonNegativeInteger | read-only | The magnitude of the nominal Volt-Amp rating. |
| NUM upsConfigRatedOutputActivePower | 1.3.6.1.4.1.186.1.19.2.5.1.7.11 | NonNegativeInteger | read-only | The magnitude of the nominal true power rating. |
| NUM upsConfigRatedOutputPowerFactor | 1.3.6.1.4.1.186.1.19.2.5.1.7.12 | NonNegativeInteger | read-only | UNITS are in hundredths. For 0.70 = 70. |
| NUM upsConfigBypassNumOfPhases | 1.3.6.1.4.1.186.1.19.2.5.1.7.13 | NonNegativeInteger | read-only | The number of bypass lines utilized. |
| NUM upsConfigLowVoltageTransferPoint | 1.3.6.1.4.1.186.1.19.2.5.1.7.14 | NonNegativeInteger | read-write | The minimum input line voltage allowed before the UPS system transfers to battery backup. |
| NUM upsConfigHighVoltageTransferPoint | 1.3.6.1.4.1.186.1.19.2.5.1.7.15 | NonNegativeInteger | read-write | The maximum line voltage allowed before the UPS system transfers to battery backup. |
| NUM upsConfigBatteryInSeries | 1.3.6.1.4.1.186.1.19.2.5.1.7.16 | NonNegativeInteger | read-write | The number of batteries in each string connected in series. |
| NUM upsConfigBatteryNumStrings | 1.3.6.1.4.1.186.1.19.2.5.1.7.17 | NonNegativeInteger | read-write | The number of parallel battery strings. |
| NUM upsConfigRatedBatteryVoltage | 1.3.6.1.4.1.186.1.19.2.5.1.7.18 | NonNegativeInteger | read-write | Rated voltage of a single battery. |
| INT upsConfigRatedBatteryAmpereHour | 1.3.6.1.4.1.186.1.19.2.5.1.7.19 | INTEGER | read-write | The rated battery in ampere hour. |
| STR upsConfigBatteryModel | 1.3.6.1.4.1.186.1.19.2.5.1.7.20 | DisplayString | read-write | The manufacturer of the battery. |
| NUM upsConfigBatteryRatedBackupTime | 1.3.6.1.4.1.186.1.19.2.5.1.7.21 | NonNegativeInteger | read-write | The rated duration batteries can hold when unit is in backup mode with full load. |
| INT upsConfigUserDefinedOverloadSetPoint | 1.3.6.1.4.1.186.1.19.2.5.1.7.22 | INTEGER | read-write | The maximum output load % defined by the user. |
| STR upsConfigBatteryInstallationDate | 1.3.6.1.4.1.186.1.19.2.5.1.7.23 | DisplayString | read-write | The battery install date. |
| STR upsConfigSysName | 1.3.6.1.4.1.186.1.19.2.5.1.7.24 | DisplayString | read-write | A string identifying the UPS. This object is set by the administrator. |
| STR upsConfigAttachedDevices | 1.3.6.1.4.1.186.1.19.2.5.1.7.25 | DisplayString | read-write | A string identifying the devices attached to the output(s) of the UPS. This object is set by the administrator. |
| STR upsConfigPassword | 1.3.6.1.4.1.186.1.19.2.5.1.7.26 | DisplayString | read-write | Password. |
| upsTime | 1.3.6.1.4.1.186.1.19.2.5.1.8 | |||
| STR upsTimeRealDate | 1.3.6.1.4.1.186.1.19.2.5.1.8.1 | DisplayString | read-write | Present date: year-month-date-day of the week. |
| STR upsTimeRealTime | 1.3.6.1.4.1.186.1.19.2.5.1.8.2 | DisplayString | read-write | Present time (military format): hour-minute-second. For example,2:00pm would be 14:00:00. |
| upsTrap | 1.3.6.1.4.1.186.1.19.2.5.1.9 |
RFC description
Telecommunications management MIB for remote monitoring and testing of TIC infrastructure on G9000/G2020 platforms.
Start monitoring Toshiba UPS, uninterruptible power supply (firmware/AC input voltage status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.