TIC-RMTI4-G9000-G2020-MIB :: upsAlarmUPSOverheat

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › TIC-RMTI4-G9000-G2020-MIB › upsAlarmUPSOverheat

upsAlarmUPSOverheat

Module: TIC-RMTI4-G9000-G2020-MIB

OID (symbolic): TIC-RMTI4-G9000-G2020-MIB::upsAlarmUPSOverheat

OID (numeric): 1.3.6.1.4.1.186.1.19.2.5.1.6.3.7

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: Fault: The UPS is overheating (warning is given when the internal temperature reaches and exceeds 50?C rise @ 40?C ambient). Check to see if the ambient temperature is abnormally high (40?C or more). If so, turn on air conditioning. Also, check ventilation fan at the back of the UPS for operation or obstructions. Otherwise, shut down the UPS and contact your Toshiba authorized service center.

What is upsAlarmUPSOverheat?

Indicates the UPS's internal temperature has risen to a fault level (a rise of about 50°C above a 40°C ambient). Per the vendor description, check for high ambient temperature or blocked ventilation fans first, and contact Toshiba service if the condition persists.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.186.1.19.2.5.1.6.3.7
snmpwalk -v2c -c public <target> TIC-RMTI4-G9000-G2020-MIB::upsAlarmUPSOverheat

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.186.1.19.2.5.1.6.3.7.1
snmpget -v2c -c public <target> TIC-RMTI4-G9000-G2020-MIB::upsAlarmUPSOverheat.1

Start monitoring Toshiba UPS, uninterruptible power supply (firmware/AC input voltage status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the TIC-RMTI4-G9000-G2020-MIB::upsAlarmUPSOverheat OID value, configure state conditions and alerts, and monitor any Toshiba UPS, uninterruptible power supply (firmware/AC input voltage status) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.186toshibaTIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1equTIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19equUPSTIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19.2ticUPSTIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19.2.5rmti4TIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19.2.5.1upsG9000_G2020TIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19.2.5.1.6upsAlarmTIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19.2.5.1.6.3upsWellKnownAlarmsTIC-RMTI4-G9000-G2020-MIB
1.3.6.1.4.1.186.1.19.2.5.1.6.3.7upsAlarmUPSOverheatTIC-RMTI4-G9000-G2020-MIB