| OID symbolic | OID numeric | Type | Access | Description |
| directory | 1.3.6.1.1 | | | |
| mgmt | 1.3.6.1.2 | | | |
| mib_2 | 1.3.6.1.2.1 | | | |
| experimental | 1.3.6.1.3 | | | |
| univPowerSupply | 1.3.6.1.3.9999 | | | |
| ident | 1.3.6.1.3.9999.1 | | | |
| OCT identDescr | 1.3.6.1.3.9999.1.1 | OCTET STRING | read-only | The UPS description. This should include the
vendor name, model number and software revision. |
| OID identSpecific | 1.3.6.1.3.9999.1.2 | OBJECT IDENTIFIER | read-only | A reference to MIB definitions
specific to the particular UPS being
managed. If this information is not
present, its value should be set to
the OBJECT IDENTIFIER { 0 0 }, which
is a syntactically valid object
identifier, and any conformant
implementation of ASN.1 and BER must
be able to generate and recognize this
value. |
| battery | 1.3.6.1.3.9999.2 | | | |
| INT batTimeRemaining | 1.3.6.1.3.9999.2.1 | INTEGER | read-only | The estimated time to battery charge
depletion. (Unit of measure: Minute) |
| INT batTemperature | 1.3.6.1.3.9999.2.2 | INTEGER | read-only | The battery temperature. (Unit of
measure: Degree, Centigrade) |
| INT batVoltage | 1.3.6.1.3.9999.2.3 | INTEGER | read-only | The current battery voltage. (Unit of
measure: volt) |
| INT batChargeCurrent | 1.3.6.1.3.9999.2.4 | INTEGER | read-only | The current battery charging current.
(Unit of measure: Amp/10) |
| INT batDischargeCurrent | 1.3.6.1.3.9999.2.5 | INTEGER | read-only | The current battery discharging current.
(Unit of measure: Amp/10) |
| INT batCapacity | 1.3.6.1.3.9999.2.6 | INTEGER | read-only | The current battery capacity in percentage
of total available. |
| input | 1.3.6.1.3.9999.3 | | | |
| INT inputFrequency | 1.3.6.1.3.9999.3.1 | INTEGER | read-only | The current input frequency. (Unit of
measure: mHz) |
| CTR inputBrownOuts | 1.3.6.1.3.9999.3.2 | Counter | read-only | The number of brown-out conditions since the
agent started. |
| CTR inputBlackOuts | 1.3.6.1.3.9999.3.3 | Counter | read-only | The number of black-out conditions since the
agent started. |
| CTR inputTransients | 1.3.6.1.3.9999.3.4 | Counter | read-only | The number of transient (sag and surge)
conditions since the agent started. |
| INT inputNumPhases | 1.3.6.1.3.9999.3.5 | INTEGER | read-only | The number of input phases utilized in this
device. This entry indicates the number of rows
in the input table. |
| inputTable | 1.3.6.1.3.9999.3.6 | | not-accessible | |
| inputEntry | 1.3.6.1.3.9999.3.6.1 | | not-accessible | |
| INT inputPhase | 1.3.6.1.3.9999.3.6.1.1 | INTEGER | read-only | The input phase. |
| INT inputVoltage | 1.3.6.1.3.9999.3.6.1.2 | INTEGER | read-only | The input voltage. (Unit of measure: Volt) |
| INT inputCurrent | 1.3.6.1.3.9999.3.6.1.3 | INTEGER | read-only | The input current. (Unit of measure: Amp/10) |
| INT inputVA | 1.3.6.1.3.9999.3.6.1.4 | INTEGER | read-only | The input volt-amps. |
| INT inputWatts | 1.3.6.1.3.9999.3.6.1.5 | INTEGER | read-only | The input power. (Unit of measure: Watt) |
| output | 1.3.6.1.3.9999.4 | | | |
| INT outputFrequency | 1.3.6.1.3.9999.4.1 | INTEGER | read-only | Measured in mHz. |
| INT outputInverterTemp | 1.3.6.1.3.9999.4.2 | INTEGER | read-only | The temperature of the inverter. (Unit of
measure: degree, Centigrade) |
| INT outputControllerTemp | 1.3.6.1.3.9999.4.3 | INTEGER | read-only | The temperature of the controller. (Unit of
measure: degree, Centigrade) |
| INT outputNumPhases | 1.3.6.1.3.9999.4.4 | INTEGER | read-only | The number of output phases utilized in this
device. This entry indicates the number of rows in
the output table. |
| outputTable | 1.3.6.1.3.9999.4.5 | | not-accessible | |
| outputEntry | 1.3.6.1.3.9999.4.5.1 | | not-accessible | |
| INT outputPhase | 1.3.6.1.3.9999.4.5.1.1 | INTEGER | read-only | The output phase. |
| INT outputVoltage | 1.3.6.1.3.9999.4.5.1.2 | INTEGER | read-only | The output voltage. (Unit of measure: Volt) |
| INT outputCurrent | 1.3.6.1.3.9999.4.5.1.3 | INTEGER | read-only | The output current. (Unit of measure: Amp/10) |
| INT outputVA | 1.3.6.1.3.9999.4.5.1.4 | INTEGER | read-only | The output volt-amps. |
| INT outputWatts | 1.3.6.1.3.9999.4.5.1.5 | INTEGER | read-only | The output power. (Unit of measure: Watt) |
| bypass | 1.3.6.1.3.9999.5 | | | |
| INT bypassFrequency | 1.3.6.1.3.9999.5.1 | INTEGER | read-only | The bypass frequency. (Unit of measure: mHz) |
| INT bypassNumPhases | 1.3.6.1.3.9999.5.2 | INTEGER | read-only | The number of bypass phases utilized in this
device. This entry indicates the number of rows in
the input table. |
| bypassTable | 1.3.6.1.3.9999.5.3 | | not-accessible | |
| bypassEntry | 1.3.6.1.3.9999.5.3.1 | | not-accessible | |
| INT bypassPhase | 1.3.6.1.3.9999.5.3.1.1 | INTEGER | read-only | The bypass phase. |
| INT bypassVoltage | 1.3.6.1.3.9999.5.3.1.2 | INTEGER | read-only | The bypass voltage. (Unit of measure: Volt) |
| INT bypassCurrent | 1.3.6.1.3.9999.5.3.1.3 | INTEGER | read-only | The bypass current. (Unit of measure: Amp/10) |
| status | 1.3.6.1.3.9999.6 | | | |
| INT statSummary | 1.3.6.1.3.9999.6.1 | INTEGER | read-only | A summary of non-critical conditions. Each of the
enumerated values are added to compute the value
of this object. |
| alarm | 1.3.6.1.3.9999.7 | | | |
| INT alarmSummary | 1.3.6.1.3.9999.7.1 | INTEGER | read-only | A summary of critical conditions. Each of the
enumerated values are added to compute the value
of this object. |
| test | 1.3.6.1.3.9999.8 | | | |
| INT testBattery | 1.3.6.1.3.9999.8.1 | INTEGER | read-write | Setting this variable to 'start' will initiate
the battery test. Setting this variable to 'abort'
will stop the battery test if the test is in-
progress, otherwise it has no effect. Reading this
variable will return zero. If 'testBatteryStatus'
is remain in the failure state. |
| INT testBatteryStatus | 1.3.6.1.3.9999.8.2 | INTEGER | read-only | The status of the battery test. |
| INT testDiag | 1.3.6.1.3.9999.8.3 | INTEGER | read-write | Setting this variable to 'start' will initiate
the diagnostics test. Setting this variable to
'abort' will stop the diagnostics test if the test
is in-progress, otherwise it has no effect.
Reading this variable will return zero. |
| INT testDiagStatus | 1.3.6.1.3.9999.8.4 | INTEGER | read-only | The status of the diagnostics test. |
| INT testIndicators | 1.3.6.1.3.9999.8.5 | INTEGER | read-write | Setting this variable to 'start' will initiate
the indicators test. Setting this variable to
'abort' will stop the indicators test if the test
is in-progress, otherwise it has no effect.
Reading this variable will return zero. |
| schedule | 1.3.6.1.3.9999.9 | | | |
| TIK schedOutputOffDelay | 1.3.6.1.3.9999.9.1 | TimeTicks | read-write | Setting this object will stop the output after
the indicated number of TimeTicks. Setting this
object to -1 will abort any shutdown sequence. The
output will restart in the number of TimeTicks
indicated by 'schedOutputOnDelay' unless it is
equal to -1. In the later case, the output will
remain inactive. This object will be set to -1
when the device is initialized on power-up or
restart. |
| TIK schedOutputOnDelay | 1.3.6.1.3.9999.9.2 | TimeTicks | read-write | The length of time to delay before coming on-
line. If this value is -1 the output will remain
off. This object will be set to -1 when the
device is initialized on power-up or restart. |
| INT schedSystemShutdown | 1.3.6.1.3.9999.9.3 | INTEGER | read-write | Setting this object to 'true' will shutdown the
device. |
| INT schedUnixShutdown | 1.3.6.1.3.9999.9.4 | INTEGER | read-write | Setting this device to 'true' will cause unix
shutdown traps to be issued at a system-dependent
rate, or until this object is set to false. |
| config | 1.3.6.1.3.9999.10 | | | |
| INT configOutputVoltage | 1.3.6.1.3.9999.10.1 | INTEGER | read-only | The nominal output voltage. (Unit of measure:
volt) |
| INT configInputVoltage | 1.3.6.1.3.9999.10.2 | INTEGER | read-only | The nominal input voltage. (Unit of measure:
volt) |
| INT configOutputFreq | 1.3.6.1.3.9999.10.3 | INTEGER | read-only | The nominal output frequency. (Unit of measure:
mHz) |
| INT configInputFreq | 1.3.6.1.3.9999.10.4 | INTEGER | read-only | The nominal input frequency. (Unit of measure:
mHz) |
| INT configNominalBatTime | 1.3.6.1.3.9999.10.5 | INTEGER | read-only | The nominal battery time. (Unit of measure:
minute) |
| INT configAudioStatus | 1.3.6.1.3.9999.10.6 | INTEGER | read-write | The status of the audio alarm. 'Off' indicates
the alarm will not sound, while the 'squelch'
value indicates the alarm has sounded and
squelched. A squelched audio status will return to
the previous state ('on' or 'off') when the alarm
stops sounding. |
| INT configAutoRestart | 1.3.6.1.3.9999.10.7 | INTEGER | read-write | Setting this object to 'on' will cause the device
to restart after a shutdown. |
| private | 1.3.6.1.4 | | | |
| enterprises | 1.3.6.1.4.1 | | | |