All MIBs › LIEBERT-UPSTATION-S3-UPS-MIB
Category: Domain: Power/UPS, Vendor: Liebert
Description: SNMP management MIB for the Liebert UPStation S3 UPS product, defining objects for power quality, battery state, and alarms.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is LIEBERT-UPSTATION-S3-UPS-MIB?
This Liebert MIB provides SNMP management for the UPStation S3 UPS product, covering power quality, battery state, and alarm conditions. It exposes objects describing input/output power quality metrics, battery charge and health status, and a set of alarm/fault indicators specific to the UPStation S3 unit. Its primary monitoring use is hardware status tracking -- battery condition, power quality anomalies, and active alarm conditions -- which are essential for anticipating UPS failures or power events before they impact connected IT equipment. It is a self-contained Liebert enterprise MIB without apparent dependency on external vendor MIB suites. It is deployed in small-to-midsize server rooms and network closets protected by a Liebert UPStation S3 UPS, where administrators can complete a LIEBERT-UPSTATION-S3-UPS-MIB download to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in LIEBERT-UPSTATION-S3-UPS-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Liebert UPStation S3 UPS
Monitoring Examples
An administrator would poll battery status and alarm objects to detect conditions like low battery, battery replacement required, or utility power failure, triggering an alert before the UPS runtime is exhausted. Power quality objects covering input/output voltage would be checked to identify brownouts or over-voltage events that caused the UPS to switch to battery mode. Active alarm objects would be cross-referenced against the alarm table to pinpoint the specific fault condition currently affecting the unit.
What Can Be Monitored
- battery status/health
- active alarm conditions
- input/output power quality
- on-battery operational state
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Counter | |
| Gauge | |
| TimeTicks | |
| enterprises |
From RFC1213-MIB
| DisplayString | |
| sysUpTime |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| emerson | 1.3.6.1.4.1.476 | |||
| lcUpsAlarm | 1.3.6.1.4.1.476.1.1.1.1.6 | |||
| lcUpsAlarmBatteryBad | 1.3.6.1.4.1.476.1.1.1.1.6.3.9 | |||
| lcUpsAlarmConditions | 1.3.6.1.4.1.476.1.1.1.1.6.3 | |||
| OID lcUpsAlarmDescr | 1.3.6.1.4.1.476.1.1.1.1.6.2.1.2 | OBJECT IDENTIFIER | read-only | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition. |
| lcUpsAlarmEntry | 1.3.6.1.4.1.476.1.1.1.1.6.2.1 | not-accessible | ||
| INT lcUpsAlarmId | 1.3.6.1.4.1.476.1.1.1.1.6.2.1.1 | INTEGER | read-only | A unique identifier for an alarm condition. This value must remain constant between agent initializations. |
| lcUpsAlarmInputOverVoltage | 1.3.6.1.4.1.476.1.1.1.1.6.3.8 | |||
| lcUpsAlarmLowBatteryShutdown | 1.3.6.1.4.1.476.1.1.1.1.6.3.2 | |||
| lcUpsAlarmLowBatteryWarning | 1.3.6.1.4.1.476.1.1.1.1.6.3.1 | |||
| lcUpsAlarmOnBattery | 1.3.6.1.4.1.476.1.1.1.1.6.3.10 | |||
| lcUpsAlarmOutputOverloadWarning | 1.3.6.1.4.1.476.1.1.1.1.6.3.6 | |||
| lcUpsAlarmOverTempWarning | 1.3.6.1.4.1.476.1.1.1.1.6.3.4 | |||
| GAU lcUpsAlarms | 1.3.6.1.4.1.476.1.1.1.1.6.1 | Gauge | read-only | The current number of alarm conditions. |
| lcUpsAlarmTable | 1.3.6.1.4.1.476.1.1.1.1.6.2 | not-accessible | ||
| TIK lcUpsAlarmTime | 1.3.6.1.4.1.476.1.1.1.1.6.2.1.3 | TimeTicks | read-only | The value of sysUpTime when the alarm condition occured. |
| NTF lcUpsAlarmTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.11 | An Alarm condition has occurred and is being reported in the lcUpsAlarmTable. | ||
| lcUpsAlarmUpsOff | 1.3.6.1.4.1.476.1.1.1.1.6.3.12 | |||
| lcUpsAlarmUtilFailed | 1.3.6.1.4.1.476.1.1.1.1.6.3.3 | |||
| INT lcUpsBatCurrent | 1.3.6.1.4.1.476.1.1.1.1.2.4 | INTEGER | read-only | The current battery discharging/charging current. (Unit of measure: Amp) |
| INT lcUpsBatTemperature | 1.3.6.1.4.1.476.1.1.1.1.2.2 | INTEGER | read-only | The battery temperature. (Unit of measure: Degree, Centigrade) |
| lcUpsBattery | 1.3.6.1.4.1.476.1.1.1.1.2 | |||
| INT lcUpsBatTimeRemaining | 1.3.6.1.4.1.476.1.1.1.1.2.1 | INTEGER | read-only | The estimated time to depletion of battery charge. (Unit of measure: Minute) |
| INT lcUpsBatVoltage | 1.3.6.1.4.1.476.1.1.1.1.2.3 | INTEGER | read-only | The current battery voltage. (Unit of measure: volt) |
| lcUpsControl | 1.3.6.1.4.1.476.1.1.1.1.8 | |||
| INT lcUpsControlCancelCommands | 1.3.6.1.4.1.476.1.1.1.1.8.7 | INTEGER | read-write | Setting this variable to 'cancel' will cause the agent to issue instructions to the UPS to cancel all outstanding commands, such as lcUpsControlOutputOff, lcUpsControlOutputOn, lcUpsControlUnixShutdown. |
| INT lcUpsControlOutputOffDelay | 1.3.6.1.4.1.476.1.1.1.1.8.1 | INTEGER | read-write | Setting this object causes the agent to instruct the UPS to turn off the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel. |
| INT lcUpsControlOutputOffTrapDelay | 1.3.6.1.4.1.476.1.1.1.1.8.3 | INTEGER | read-write | When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0. |
| INT lcUpsControlOutputOnDelay | 1.3.6.1.4.1.476.1.1.1.1.8.2 | INTEGER | read-write | Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel. |
| INT lcUpsControlOutputOnTrapDelay | 1.3.6.1.4.1.476.1.1.1.1.8.4 | INTEGER | read-write | When 'lcUpsControlOutputOnDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOnWarningTrap will be produced and this object will be reset to 0. |
| INT lcUpsControlRebootAgentDelay | 1.3.6.1.4.1.476.1.1.1.1.8.8 | INTEGER | read-write | Setting this object causes the agent to reboot after the indicated number of seconds have expired. The value will count down until the event takes place. The command can be cancelled by setting lcUpsControlCancleCommand to the value cancel. |
| INT lcUpsControlUnixShutdownDelay | 1.3.6.1.4.1.476.1.1.1.1.8.5 | INTEGER | read-write | Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'. |
| INT lcUpsControlUnixShutdownTrapDelay | 1.3.6.1.4.1.476.1.1.1.1.8.6 | INTEGER | read-write | When 'lcUpsControlUnixShutdownDelay' reaches a value less than or equal to this object's value, an lcUpsUnixShutdownWarningTrap will be produced and this object will be reset to 0. |
| lcUpsIdent | 1.3.6.1.4.1.476.1.1.1.1.1 | |||
| STR lcUpsIdentManufacturer | 1.3.6.1.4.1.476.1.1.1.1.1.1 | DisplayString | read-only | The UPS manufacturer. |
| STR lcUpsIdentModel | 1.3.6.1.4.1.476.1.1.1.1.1.2 | DisplayString | read-write | The UPS Model designation. |
| STR lcUpsIdentSoftwareVersion | 1.3.6.1.4.1.476.1.1.1.1.1.3 | DisplayString | read-only | The UPS SNMP Agent software version. |
| OID lcUpsIdentSpecific | 1.3.6.1.4.1.476.1.1.1.1.1.4 | OBJECT IDENTIFIER | read-only | A reference to MIB definitions specific to the particular UPS being managed. This object is used to locate the product-specific MIB for this device. If this information is not present, its value should be the OBJECT IDENTIFIER { 0 0 }, which is a syntactically valid object identifier, and any conformant implementation of ASN.1 and BER must be able to generate and recognize this value. |
| lcUpsInput | 1.3.6.1.4.1.476.1.1.1.1.3 | |||
| CTR lcUpsInputBlackOuts | 1.3.6.1.4.1.476.1.1.1.1.3.3 | Counter | read-only | The number of black-out conditions the UPS has experienced. |
| CTR lcUpsInputBrownOuts | 1.3.6.1.4.1.476.1.1.1.1.3.2 | Counter | read-only | The number of brown-out conditions the UPS has experienced. |
| INT lcUpsInputCurrent | 1.3.6.1.4.1.476.1.1.1.1.3.6.1.3 | INTEGER | read-only | The input current. (Unit of measure: Amp) |
| lcUpsInputEntry | 1.3.6.1.4.1.476.1.1.1.1.3.6.1 | not-accessible | ||
| INT lcUpsInputFrequency | 1.3.6.1.4.1.476.1.1.1.1.3.1 | INTEGER | read-only | The current input frequency. (Unit of measure: Hertz) |
| INT lcUpsInputLine | 1.3.6.1.4.1.476.1.1.1.1.3.6.1.1 | INTEGER | read-only | The input Line. |
| INT lcUpsInputNumLines | 1.3.6.1.4.1.476.1.1.1.1.3.5 | INTEGER | read-only | The number of input lines utilized in this device. This entry indicates the number of rows in the input table. |
| NTF lcUpsInputOverVoltageTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.8 | An lcUpsInputOverVoltageTrap signifies that the UPS has detected a high input voltage condition. | ||
| lcUpsInputTable | 1.3.6.1.4.1.476.1.1.1.1.3.6 | not-accessible | ||
| CTR lcUpsInputTransients | 1.3.6.1.4.1.476.1.1.1.1.3.4 | Counter | read-only | The number of transient (surge and spike) conditions the UPS has experienced. |
| INT lcUpsInputVA | 1.3.6.1.4.1.476.1.1.1.1.3.6.1.4 | INTEGER | read-only | The input volt-amps. |
| INT lcUpsInputVoltage | 1.3.6.1.4.1.476.1.1.1.1.3.6.1.2 | INTEGER | read-only | The input voltage. (Unit of measure: Volt) |
| lcUpsInverter | 1.3.6.1.4.1.476.1.1.1.1.5 | |||
| INT lcUpsInverterStatus | 1.3.6.1.4.1.476.1.1.1.1.5.1 | INTEGER | read-only | The state of the inverter. Unknown is returned if the state can not be determined. |
| INT lcUpsInverterTemp | 1.3.6.1.4.1.476.1.1.1.1.5.2 | INTEGER | read-only | The temperature of the inverter. (Unit of measure: degree, Centigrade) |
| NTF lcUpsLowBatteryWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.4 | An lcUpsLowBatteryWarningTrap signifies that the UPS has entered a Low Battery state. | ||
| lcUpsNominal | 1.3.6.1.4.1.476.1.1.1.1.9 | |||
| INT lcUpsNominalInputFreq | 1.3.6.1.4.1.476.1.1.1.1.9.6 | INTEGER | read-write | The nominal input frequency. (Unit of measure: Hertz) |
| INT lcUpsNominalInputVoltage | 1.3.6.1.4.1.476.1.1.1.1.9.2 | INTEGER | read-write | The nominal input voltage. (Unit of measure: volt) |
| INT lcUpsNominalOutputFreq | 1.3.6.1.4.1.476.1.1.1.1.9.5 | INTEGER | read-write | The nominal output frequency. (Unit of measure: Hertz) |
| INT lcUpsNominalOutputVA | 1.3.6.1.4.1.476.1.1.1.1.9.3 | INTEGER | read-write | The nominal Volt-Amp rating. |
| INT lcUpsNominalOutputVoltage | 1.3.6.1.4.1.476.1.1.1.1.9.1 | INTEGER | read-write | The nominal output voltage. (Unit of measure: volt) |
| INT lcUpsNominalOutputWatts | 1.3.6.1.4.1.476.1.1.1.1.9.4 | INTEGER | read-write | The nominal power rating. (Unit of measure: watt) |
| NTF lcUpsOnBatteryTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.3 | An lcUpsOnBatteryTrap signifies that the UPS is currently on Battery Power. | ||
| lcUpsOutput | 1.3.6.1.4.1.476.1.1.1.1.4 | |||
| INT lcUpsOutputCurrent | 1.3.6.1.4.1.476.1.1.1.1.4.4.1.3 | INTEGER | read-only | The output current. (Unit of measure: Amp) |
| lcUpsOutputEntry | 1.3.6.1.4.1.476.1.1.1.1.4.4.1 | not-accessible | ||
| INT lcUpsOutputFrequency | 1.3.6.1.4.1.476.1.1.1.1.4.1 | INTEGER | read-only | The current output frequency. (Unit of measure: Hertz) |
| INT lcUpsOutputLine | 1.3.6.1.4.1.476.1.1.1.1.4.4.1.1 | INTEGER | read-only | The output Line. |
| INT lcUpsOutputLoad | 1.3.6.1.4.1.476.1.1.1.1.4.2 | INTEGER | read-only | The current output load percentage. |
| INT lcUpsOutputNumLines | 1.3.6.1.4.1.476.1.1.1.1.4.3 | INTEGER | read-only | The number of output lines utilized in this device. This entry indicates the number of rows in the output table. |
| NTF lcUpsOutputOffTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.12 | An lcUpsOutputOffTrap is sent when the UPS turns all of its output off, either at the inverter or via a relay. | ||
| NTF lcUpsOutputOffWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.13 | An lcUpsOutputOffWarningTrap is sent when the lcUpsControlOutputOffDelay reaches the value of lcUpsControlOutputOffTrapDelay. | ||
| NTF lcUpsOutputOnTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.14 | An lcUpsOutputOnTrap is sent when the UPS turns all of its output back on, either at the inverter or via a relay. | ||
| NTF lcUpsOutputOnWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.15 | An lcUpsOutputOnWarningTrap is sent when the lcUpsControlOutputOnDelay reaches the value of lcUpsControlOutputOnTrapDelay. | ||
| lcUpsOutputTable | 1.3.6.1.4.1.476.1.1.1.1.4.4 | not-accessible | ||
| INT lcUpsOutputVA | 1.3.6.1.4.1.476.1.1.1.1.4.4.1.4 | INTEGER | read-only | The output volt-amps. |
| INT lcUpsOutputVoltage | 1.3.6.1.4.1.476.1.1.1.1.4.4.1.2 | INTEGER | read-only | The output voltage. (Unit of measure: Volt) |
| NTF lcUpsOverloadWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.1 | An lcUpsOverloadWarningTrap signifies that the UPS has detected an Overload condition where the output load has exceeded the UPS's rated capacity. | ||
| NTF lcUpsOverTempWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.9 | An lcUpsOverTempWarningTrap signifies that the UPS has detected a excessive temperature condition. | ||
| NTF lcUpsReceptOffTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.18 | An lcUpsReceptOffTrap is sent when the UPS turns an output receptacle off. | ||
| NTF lcUpsReceptOffWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.19 | An lcUpsReceptOffWarningTrap is sent when the lcUpsSwitchedReceptOffDelay reaches the value of lcUpsSwitchedReceptOffTrapDelay. | ||
| NTF lcUpsReceptOnTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.20 | An lcUpsReceptOnTrap is sent when the UPS turns an output receptacle on. | ||
| NTF lcUpsReceptOnWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.21 | An lcUpsReceptOnWarningTrap is sent when the lcUpsSwitchedReceptOnDelay reaches the value of lcUpsSwitchedReceptOnTrapDelay. | ||
| lcUpsSwitchedReceptacles | 1.3.6.1.4.1.476.1.1.1.1.12 | |||
| lcUpsSwitchedReceptEntry | 1.3.6.1.4.1.476.1.1.1.1.12.2.1 | not-accessible | ||
| INT lcUpsSwitchedReceptIndex | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.1 | INTEGER | read-only | |
| STR lcUpsSwitchedReceptLabel | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.7 | DisplayString | read-write | A user-defined text string associated with a switched receptacle. This may be used to describe the load powered from the receptacle. The text string is stored in non-volatile memory. |
| INT lcUpsSwitchedReceptMaxNum | 1.3.6.1.4.1.476.1.1.1.1.12.1 | INTEGER | read-only | The maximum number of switched receptacles supported by the Ups. |
| INT lcUpsSwitchedReceptOffDelay | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.4 | INTEGER | read-write | Setting this object causes the agent to instruct the UPS to turn off a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOffTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel. |
| INT lcUpsSwitchedReceptOffTrapDelay | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.5 | INTEGER | read-write | When 'lcUpsSwitchedReceptOffDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOffWarningTrap will be produced and this object will be reset to 0. |
| INT lcUpsSwitchedReceptOnDelay | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2 | INTEGER | read-write | Setting this object causes the agent to instruct the UPS to turn on a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock. The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel. |
| INT lcUpsSwitchedReceptOnTrapDelay | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.3 | INTEGER | read-write | When 'lcUpsSwitchedReceptOnDelay' reaches a value less than or equal to this object's value, an lcUpsReceptOnWarningTrap will be produced and this object will be reset to 0. |
| INT lcUpsSwitchedReceptStatus | 1.3.6.1.4.1.476.1.1.1.1.12.2.1.6 | INTEGER | read-only | The status of the device receptacle. Note that some devices may support Switched of device receptacles as a group only (by using lcUpsSwitchedOutputOffDelay and lcUpsSwitchedOutputOnDelay). |
| lcUpsSwitchedReceptTable | 1.3.6.1.4.1.476.1.1.1.1.12.2 | not-accessible | ||
| lcUpsTest | 1.3.6.1.4.1.476.1.1.1.1.7 | |||
| INT lcUpsTestBattery | 1.3.6.1.4.1.476.1.1.1.1.7.1 | INTEGER | read-write | Setting this variable to 'start' will initiate the battery test. Setting this variable to 'abort' will stop the battery test if the test is in- progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. If 'lcUpsTestBatteryStatus' is 'failed' the test may not be performed again and the status will remain in the failure state. |
| INT lcUpsTestBatteryStatus | 1.3.6.1.4.1.476.1.1.1.1.7.2 | INTEGER | read-only | The status of the battery test. |
| INT lcUpsTestDiag | 1.3.6.1.4.1.476.1.1.1.1.7.3 | INTEGER | read-write | Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'. |
| INT lcUpsTestDiagStatus | 1.3.6.1.4.1.476.1.1.1.1.7.4 | INTEGER | read-only | The status of the diagnostics test. |
| lcUpsTraps | 1.3.6.1.4.1.476.1.1.1.1.11 | |||
| NTF lcUpsUnixShutdownTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.16 | An lcUpsUnixShutodwnTrap is sent 2 seconds before the UPS is scheduled to perform a Unix Shutdown. | ||
| NTF lcUpsUnixShutdownWarningTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.17 | An lcUpsUnixShutdownWarningTrap is sent when the lcUpsControlUnixShudownDelay reaches the value of lcUpsControlUnixShutdownTrapDelay. | ||
| NTF lcUpsUtilPowerFailedTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.6 | An lcUpsUtilPowerFailedTrap signifies that the utility power input to the UPS has been lost. | ||
| NTF lcUpsUtilPowerRestoredTrap | 1.3.6.1.4.1.476.1.1.1.1.11.0.7 | An lcUpsUtilPowerRestoredTrap signifies that the utility power has been restored to the UPS. | ||
| liebertCorp | 1.3.6.1.4.1.476.1 | |||
| liebertUps | 1.3.6.1.4.1.476.1.1 | |||
| lsUpsAlarm | 1.3.6.1.4.1.476.1.1.1.2.6 | |||
| lsUpsAlarmCheckAirFilter | 1.3.6.1.4.1.476.1.1.1.2.6.1.1 | |||
| lsUpsAlarmConditions | 1.3.6.1.4.1.476.1.1.1.2.6.1 | |||
| lsUpsBypass | 1.3.6.1.4.1.476.1.1.1.2.13 | |||
| INT lsUpsBypassCurrent | 1.3.6.1.4.1.476.1.1.1.2.13.4.1.3 | INTEGER | read-only | The bypass current. (Unit of measure: Amp) |
| lsUpsBypassEntry | 1.3.6.1.4.1.476.1.1.1.2.13.4.1 | not-accessible | ||
| INT lsUpsBypassFrequency | 1.3.6.1.4.1.476.1.1.1.2.13.2 | INTEGER | read-only | The current bypass frequency. (Unit of measure: Hertz) |
| INT lsUpsBypassLine | 1.3.6.1.4.1.476.1.1.1.2.13.4.1.1 | INTEGER | read-only | The bypass Line. |
| INT lsUpsBypassNumLines | 1.3.6.1.4.1.476.1.1.1.2.13.3 | INTEGER | read-only | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| lsUpsBypassTable | 1.3.6.1.4.1.476.1.1.1.2.13.4 | not-accessible | ||
| INT lsUpsBypassVoltage | 1.3.6.1.4.1.476.1.1.1.2.13.4.1.2 | INTEGER | read-only | The bypass voltage. (Unit of measure: Volt) |
| NTF lsUpsCheckAirFilterTrap | 1.3.6.1.4.1.476.1.1.1.2.11.0.1 | An lsUpsCheckAirFilterTrap signifies that the programmed time interval for checking the air filter has passed and it is time to check the air filter. | ||
| lsUpsConfig | 1.3.6.1.4.1.476.1.1.1.2.12 | |||
| INT lsUpsConfigBypassInstalled | 1.3.6.1.4.1.476.1.1.1.2.12.1 | INTEGER | read-only | Indicates if a bypass is installed in the UPS. |
| lsUpsIdent | 1.3.6.1.4.1.476.1.1.1.2.1 | |||
| STR lsUpsIdentFirmwareVersion | 1.3.6.1.4.1.476.1.1.1.2.1.1 | DisplayString | read-only | The firmware revision level of the UPS. |
| INT lsUpsOnBypass | 1.3.6.1.4.1.476.1.1.1.2.13.1 | INTEGER | read-only | Indicates that the UPS is currently on bypass. |
| lsUpsTraps | 1.3.6.1.4.1.476.1.1.1.2.11 | |||
| luCore | 1.3.6.1.4.1.476.1.1.1.1 | |||
| luExperimental | 1.3.6.1.4.1.476.1.1.2 | |||
| luExtensions | 1.3.6.1.4.1.476.1.1.1 | |||
| luPrivate | 1.3.6.1.4.1.476.1.1.3 | |||
| luUPStationS | 1.3.6.1.4.1.476.1.1.1.2 | |||
| luUPStationS3 | 1.3.6.1.4.1.476.1.1.1.7 |
RFC description
Manages Liebert UpStation S3 UPS systems, providing SNMP agent support for monitoring and controlling uninterruptible power supplies.
Start monitoring Liebert UPS systems with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.