LIEBERT-UPSTATION-S3-UPS-MIB :: lcUpsSwitchedReceptOnDelay

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsLIEBERT-UPSTATION-S3-UPS-MIBlcUpsSwitchedReceptOnDelay

lcUpsSwitchedReceptOnDelay

Module: LIEBERT-UPSTATION-S3-UPS-MIB

OID (symbolic): LIEBERT-UPSTATION-S3-UPS-MIB::lcUpsSwitchedReceptOnDelay

OID (numeric): 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Setting this object causes the agent to instruct the UPS to turn on a receptacle after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsReceptOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock.

The command can be cancelled by setting lcUpsSwitchedCancelCommand to the value cancel.

What is lcUpsSwitchedReceptOnDelay?

Setting this read-write integer (0-2147483647 seconds) instructs the UPS to turn on the specific switched receptacle after the given delay, triggering an lcUpsReceptOnTrap when it finishes; the command can be cancelled. An operator uses this to stagger power-up of individual outlets, for example bringing up a server before its attached storage array.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2
snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-S3-UPS-MIB::lcUpsSwitchedReceptOnDelay

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2.1
snmpget -v2c -c public <target> LIEBERT-UPSTATION-S3-UPS-MIB::lcUpsSwitchedReceptOnDelay.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.12.2.1.2.1 i <value>

Start monitoring Liebert UPS systems with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-S3-UPS-MIB::lcUpsSwitchedReceptOnDelay OID value, configure state conditions and alerts, and monitor any Liebert UPS systems from a single console.

OID Breakdown

Upper-level ancestors (14 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.1liebertUpsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1luExtensionsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1luCoreLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1.12lcUpsSwitchedReceptaclesLIEBERT-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1.12.2lcUpsSwitchedReceptTableLIEBERT-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1.12.2.1lcUpsSwitchedReceptEntryLIEBERT-UPS-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.1.1.1.12.2.1.2lcUpsSwitchedReceptOnDelayLIEBERT-UPSTATION-S3-UPS-MIB