All MIBs › DANTHERM-COOLING-MIB
Category: Environmental Monitoring
Description: Monitors cooling unit status, temperature, and fan operation for Dantherm HVAC equipment.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is DANTHERM-COOLING-MIB?
This MIB monitors Dantherm precision cooling units (CC3000 controller) used for HVAC/environmental control of telecom and data-center equipment spaces. It exposes controller-level system status and configurable high-level control parameters, plus per-fan configuration for at least two cooling fans. It is directly aimed at monitoring hardware environmental status: systemStatus reflects the cooling unit's overall operational/fault condition, and fan1Config/fan2Config track fan operating parameters critical to detecting fan failure or degraded cooling capacity. No dependency on other standard MIBs is stated; it is a self-contained proprietary environmental MIB. Deployment context is Dantherm CC3000-controlled precision air-conditioning units cooling telecom shelters, data-center rooms, or outdoor equipment cabinets. Engineers can download the DANTHERM-COOLING-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in DANTHERM-COOLING-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Dantherm CC3000 precision cooling/HVAC controller
- telecom shelter/data-center cooling unit
Monitoring Examples
Poll systemStatus under danthermCooling/controllerCC3000 to detect an alarm or fault state on the cooling unit, and check fan1Config/fan2Config to confirm both fans are configured and running. A fan reporting a stopped or fault condition alongside a rising systemStatus alarm would indicate imminent overheating risk for co-located equipment.
What Can Be Monitored
- overall cooling system status/alarm state
- fan 1 configuration/operational status
- fan 2 configuration/operational status
- high-level control parameters
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC1155-SMI
| enterprises |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| danthermCooling | 1.3.6.1.4.1.46651 | |||
| NTF cc3000Trap | 1.3.6.1.4.1.46651.0.1 | Trap From CC300 Controller. Contains TRAP information | ||
| controllerCC3000 | 1.3.6.1.4.1.46651.1 | |||
| systemStatus | 1.3.6.1.4.1.46651.1.1 | |||
| INT onBoardTempr | 1.3.6.1.4.1.46651.1.1.1 | INTEGER | read-only | Controller On-Board temperature in Degree Celcius |
| INT roomTempr | 1.3.6.1.4.1.46651.1.1.2 | INTEGER | read-only | Room Sensor or Zone 1 Sensor temperature in Degree Celcius |
| INT hotSpotTempr | 1.3.6.1.4.1.46651.1.1.3 | INTEGER | read-only | Hot Spot Sensor or Zone 2 Sensor temperature in Degree Celcius |
| INT outdoor1Tempr | 1.3.6.1.4.1.46651.1.1.4 | INTEGER | read-only | Ambient Sensor 1 or Zone 1 Ambient Sensor. temperature in Degree Celcius |
| INT outdoor2Tempr | 1.3.6.1.4.1.46651.1.1.5 | INTEGER | read-only | Ambient Sensor 2 or Zone 2 Ambient Sensor. temperature in Degree Celcius |
| INT shelterTempr | 1.3.6.1.4.1.46651.1.1.6 | INTEGER | read-only | Shelter Temperature. Valid for Single-Zone solution |
| INT outdoorCombinedTempr | 1.3.6.1.4.1.46651.1.1.7 | INTEGER | read-only | Cobined minimum Outdoor Temeperature. Valid for Single-Zone solution |
| INT fan1RPM | 1.3.6.1.4.1.46651.1.1.8 | INTEGER | read-only | Fan 1 Rotation Per Minute |
| INT fan2RPM | 1.3.6.1.4.1.46651.1.1.9 | INTEGER | read-only | Fan 2 Rotation Per Minute |
| INT fan1SpeedPercentage | 1.3.6.1.4.1.46651.1.1.10 | INTEGER | read-only | Fan 1 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal |
| INT fan2SpeedPercentage | 1.3.6.1.4.1.46651.1.1.11 | INTEGER | read-only | Fan 2 Speed in Percentage of Maximum Speed. Also represents Duty-Cycle of FAn Signal |
| INT damper1Position | 1.3.6.1.4.1.46651.1.1.12 | INTEGER | read-only | Damper 1 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open |
| INT damper2Position | 1.3.6.1.4.1.46651.1.1.13 | INTEGER | read-only | Damper 2 Shutter Open Percentage. 0% - Damper Closed. 100% - Damper completely open |
| INT humidity | 1.3.6.1.4.1.46651.1.1.14 | INTEGER | read-only | Internal or external humidity in Rh% |
| INT dewpoint | 1.3.6.1.4.1.46651.1.1.15 | INTEGER | read-only | Internal or external DewPoint based on Humidity; in Degree Celcius |
| INT atmosphericPressure | 1.3.6.1.4.1.46651.1.1.16 | INTEGER | read-only | Atmospheric pressure or Pressure of installed enclosure in KiloPascal |
| INT flowPressure | 1.3.6.1.4.1.46651.1.1.17 | INTEGER | read-only | Filter flow Pressure in Pascal |
| INT fan1Status | 1.3.6.1.4.1.46651.1.1.18 | INTEGER | read-only | Fan 1 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost |
| INT fan2Status | 1.3.6.1.4.1.46651.1.1.19 | INTEGER | read-only | Fan 2 operation status. 0 - Off; 1 - On -; 2 - Emergency/Boost |
| INT damper1Status | 1.3.6.1.4.1.46651.1.1.20 | INTEGER | read-only | Damper 1 operation status. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost |
| INT damper2Status | 1.3.6.1.4.1.46651.1.1.21 | INTEGER | read-only | Damper 2 Shutter Open Percentage. 0 - Closed; 1 - Open; 2 - Dynamic or Temperature Compensation; 2 - Emergency/Boost |
| INT aircond1Status | 1.3.6.1.4.1.46651.1.1.22 | INTEGER | read-only | Airconditioner 1 operation status. 0 - Off; 1 - Restart timeout; 2 - On |
| INT aircond2Status | 1.3.6.1.4.1.46651.1.1.23 | INTEGER | read-only | Airconditioner 2 operation status. 0 - Off; 1 - Restart timeout; 2 - On |
| INT heaterStatus | 1.3.6.1.4.1.46651.1.1.24 | INTEGER | read-only | heater operation status. 0 - Off; 1 - On |
| INT shelter1Status | 1.3.6.1.4.1.46651.1.1.25 | INTEGER | read-only | Shelter Status in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively. 0 - Inactive or None State 1 - Heating State 2 - Re-Cycling State 3 - Free Cooling State 4 - Active or Aircon Coolign State 5 - Emergency State 6 - Intermediate state( strategy transistion) |
| INT shelter2Status | 1.3.6.1.4.1.46651.1.1.26 | INTEGER | read-only | Shelter Status in Dual-Zone mode or Zone 2 Status. 0 - Inactive or None State 1 - Heating State 2 - Re-Cycling State 3 - Free Cooling State 4 - Active or Aircon Coolign State 5 - Emergency State 6 - Intermediate state( strategy transistion) |
| INT shelter1Mode | 1.3.6.1.4.1.46651.1.1.27 | INTEGER | read-only | Shelter Run time mode in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively. 0 - Free Cooling Mode 1 - Standard Mode 2 - Power Save Mode 3 - Air conditioner Mode |
| INT shelter2Mode | 1.3.6.1.4.1.46651.1.1.28 | INTEGER | read-only | Shelter Run time mode in Dual-Zone mode or Zone 2 Status. 0 - Free Cooling Mode 1 - Standard Mode 2 - Power Save Mode 3 - Air conditioner Mode |
| INT shelter1Setpoint | 1.3.6.1.4.1.46651.1.1.29 | INTEGER | read-only | Shelter run time Cooling Set point in Single-Zone mode or Zone 1 Status in Dual-Zone mode respectively. Cooling setpoint can be offset by following functions RH function Night mode Digital inputs |
| INT shelter2Setpoint | 1.3.6.1.4.1.46651.1.1.30 | INTEGER | read-only | Shelter run time Cooling Set point in Dual-Zone mode or Zone 2 Status. Cooling setpoint can be offset by following functions RH function Night mode Digital inputs |
| INT errorStatus | 1.3.6.1.4.1.46651.1.1.31 | INTEGER | read-only | controller internal error status. Binary bit position - alarm drive state: 0 - inactive , 1 - active 0 - voltage low 1 - voltage high 2 - tempr low 3 - tempr limit 1 4 - tempr limit 2 5 - tempr limit 3 6 - humid. low 7 - humid. high 8 - fltr pressure 1 9 - fltr pressure 2 10 - fan 1 11 - fan 2 12 - onboard sens 13 - room sens 14 - hotspot sens 15 - ambient 1 sens 16 - ambient 2 sens 17 - dig 1 i/p 18 - dig 2 i/p 19 - dig 3 i/p 20 - filter i/p 1 21 - filter i/p 2 22 - network 23 - int storage 24 - sd card |
| INT maskedErrorStatus | 1.3.6.1.4.1.46651.1.1.32 | INTEGER | read-only | Controller Output Error status. Binary Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active 0 - Voltage Low 1 - Voltage High 2 - Tempr Low 3 - Tempr Limit 1 4 - Tempr Limit 2 5 - Tempr Limit 3 6 - Humid. Low 7 - Humid. High 8 - Fltr Pressure 1 9 - Fltr Pressure 2 10 - Fan 1 11 - Fan 2 12 - Onboard Sens 13 - Room Sens 14 - Hotspot Sens 15 - Ambient 1 Sens 16 - Ambient 2 Sens 17 - Dig 1 I/P 18 - Dig 2 I/P 19 - Dig 3 I/P 20 - Filter I/P 1 21 - Filter I/P 2 22 - Network 23 - Int storage 24 - SD Card |
| INT voltage | 1.3.6.1.4.1.46651.1.1.33 | INTEGER | read-only | System Voltage in DC. |
| INT digitalInputStatus | 1.3.6.1.4.1.46651.1.1.34 | INTEGER | read-only | Controller Alarm Drive Status. Binary Bit Position - Digital Input State: 0 - Inactive , 1 - Active 0 - DIG 1 I/P 1 - DIG 2 I/P 2 - DIG 3 I/P 3 - FILTER GUARD DIGI 1 I/P 4 - FILTER GUARD DIGI 2 I/P |
| INT alarmDriveStatus | 1.3.6.1.4.1.46651.1.1.35 | INTEGER | read-only | Controller Alarm Drive Status. Binary Bit Position - Alarm Drive State: 0 - Inactive , 1 - Active 0 - ALARM 1 1 - ALARM 2 2 - ALARM 3 3 - ALARM 4 4 - ALARM 5 5 - ALARM 6 6 - ALARM 7 7 - ALARM 8 8 - ALARM 9 9 - ALARM 10 |
| INT fan1OpertdurHour | 1.3.6.1.4.1.46651.1.1.36 | INTEGER | read-write | Fan 1 operation duration - Hour |
| INT fan1OpertdurMin | 1.3.6.1.4.1.46651.1.1.37 | INTEGER | read-write | Fan 1 operation duration - Minute |
| INT fan2OpertdurHour | 1.3.6.1.4.1.46651.1.1.38 | INTEGER | read-write | Fan 2 operation duration - Hour |
| INT fan2OpertdurMin | 1.3.6.1.4.1.46651.1.1.39 | INTEGER | read-write | Fan 2 operation duration - Minute |
| INT aircon1OpertdurHour | 1.3.6.1.4.1.46651.1.1.40 | INTEGER | read-write | Airconditioner 1 operation duration - Hour |
| INT aircon1OpertdurMin | 1.3.6.1.4.1.46651.1.1.41 | INTEGER | read-write | Airconditioner 1 operation duration - Minute |
| INT aircon2OpertdurHour | 1.3.6.1.4.1.46651.1.1.42 | INTEGER | read-write | Airconditioner 2 operation duration - Hour |
| INT aircon2OpertdurMin | 1.3.6.1.4.1.46651.1.1.43 | INTEGER | read-write | Airconditioner 2 operation duration - Minute |
| INT heaterOpertdurHour | 1.3.6.1.4.1.46651.1.1.44 | INTEGER | read-write | Heater operation duration - Hour |
| INT heaterOpertdurMin | 1.3.6.1.4.1.46651.1.1.45 | INTEGER | read-write | Heater operation duration - Minute |
| OCT ccSN | 1.3.6.1.4.1.46651.1.1.46 | OCTET STRING | read-write | CC3000 Controller serial number |
| OCT fanbox1SN | 1.3.6.1.4.1.46651.1.1.47 | OCTET STRING | read-write | Free cooling FanBox unit 1 serial number |
| OCT fanbox2SN | 1.3.6.1.4.1.46651.1.1.48 | OCTET STRING | read-write | Free cooling FanBox unit 2 serial number |
| OCT aircond1SN | 1.3.6.1.4.1.46651.1.1.49 | OCTET STRING | read-write | Aicodnitioner unit 1 serial number |
| OCT aircond2SN | 1.3.6.1.4.1.46651.1.1.50 | OCTET STRING | read-write | Aicodnitioner unit 2 serial number |
| OCT fwVersion | 1.3.6.1.4.1.46651.1.1.51 | OCTET STRING | read-only | CC3000 Firmware version |
| highlevelControl | 1.3.6.1.4.1.46651.1.2 | |||
| INT coolSetpointZone1 | 1.3.6.1.4.1.46651.1.2.1 | INTEGER | read-write | Cooling Setpoint Zone/Shelter 1 |
| INT coolSetpointZone2 | 1.3.6.1.4.1.46651.1.2.2 | INTEGER | read-write | Cooling Setpoint Zone/Shelter 2 |
| INT heaterSetpoint | 1.3.6.1.4.1.46651.1.2.3 | INTEGER | read-write | Heater Setpoint |
| INT backupConfig | 1.3.6.1.4.1.46651.1.2.4 | INTEGER | read-write | Configuration Backup to Internal memory and SD card. 0 - No change, 1 - Backup |
| INT restoreConfig | 1.3.6.1.4.1.46651.1.2.5 | INTEGER | read-write | Configuration restore from Internal memory. 0 - No change, 1 - Restore |
| INT systemReset | 1.3.6.1.4.1.46651.1.2.6 | INTEGER | read-write | Colling System reset or restart. 0 - No change, 1 - Restart |
| INT year | 1.3.6.1.4.1.46651.1.2.7 | INTEGER | read-write | Calender - Year |
| INT month | 1.3.6.1.4.1.46651.1.2.8 | INTEGER | read-write | Calender - Month |
| INT date | 1.3.6.1.4.1.46651.1.2.9 | INTEGER | read-write | Calender - Date |
| INT hour | 1.3.6.1.4.1.46651.1.2.10 | INTEGER | read-write | Clock - Hour |
| INT minute | 1.3.6.1.4.1.46651.1.2.11 | INTEGER | read-write | Clock - Minute |
| fan1Config | 1.3.6.1.4.1.46651.1.3 | |||
| INT saveReloadConff1 | 1.3.6.1.4.1.46651.1.3.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT offTemprf1 | 1.3.6.1.4.1.46651.1.3.2 | INTEGER | read-write | Fan OFF temperature |
| INT idleOnTemprf1 | 1.3.6.1.4.1.46651.1.3.3 | INTEGER | read-write | Fan Idle Speed On temperature |
| INT idleEntryTemprf1 | 1.3.6.1.4.1.46651.1.3.4 | INTEGER | read-write | Idle entry temperature |
| INT midPoint1Temprf1 | 1.3.6.1.4.1.46651.1.3.5 | INTEGER | read-write | Mid point 1 entry temperature |
| INT setPointTemprf1 | 1.3.6.1.4.1.46651.1.3.6 | INTEGER | read-write | Set Point temperature |
| INT midPoint2Temprf1 | 1.3.6.1.4.1.46651.1.3.7 | INTEGER | read-write | Mid point 2 entry temperature |
| INT highSpeedTemprf1 | 1.3.6.1.4.1.46651.1.3.8 | INTEGER | read-write | high Speed entry temperature |
| INT extendHighSpeedEntryTemprf1 | 1.3.6.1.4.1.46651.1.3.9 | INTEGER | read-write | Extended high Speed entry temperature |
| INT extendHighSpeedExitTemprf1 | 1.3.6.1.4.1.46651.1.3.10 | INTEGER | read-write | Extended high Speed exit temperature |
| INT boostEntryTemprf1 | 1.3.6.1.4.1.46651.1.3.11 | INTEGER | read-write | Boost Speed entry temperature |
| INT boostExitTemprf1 | 1.3.6.1.4.1.46651.1.3.12 | INTEGER | read-write | Boost Speed entry temperature |
| INT idleRPMf1 | 1.3.6.1.4.1.46651.1.3.13 | INTEGER | read-write | Idle speed RPM |
| INT midPointRPMf1 | 1.3.6.1.4.1.46651.1.3.14 | INTEGER | read-write | Midpoint Speed RPM |
| INT highSpeedRPMf1 | 1.3.6.1.4.1.46651.1.3.15 | INTEGER | read-write | high Speed RPM |
| INT extendHighSpeedRPMf1 | 1.3.6.1.4.1.46651.1.3.16 | INTEGER | read-write | Extended high Speed RPM |
| INT idleDutyCyclef1 | 1.3.6.1.4.1.46651.1.3.17 | INTEGER | read-write | Idle Speed Duty Cycle |
| INT midDutyCyclef1 | 1.3.6.1.4.1.46651.1.3.18 | INTEGER | read-write | Midpoint speed Duty Cycle |
| INT highSpeedDutyCyclef1 | 1.3.6.1.4.1.46651.1.3.19 | INTEGER | read-write | high speed Duty Cycle |
| INT extendHighSpeedDutyCyclef1 | 1.3.6.1.4.1.46651.1.3.20 | INTEGER | read-write | Extended high speed Duty Cycle |
| INT boostDutyCyclef1 | 1.3.6.1.4.1.46651.1.3.21 | INTEGER | read-write | Boost speed Duty Cycle |
| INT deadBandRPMf1 | 1.3.6.1.4.1.46651.1.3.22 | INTEGER | read-write | Dead band RPM |
| INT overrideDigi1f1 | 1.3.6.1.4.1.46651.1.3.23 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT overrideDigi2f1 | 1.3.6.1.4.1.46651.1.3.24 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT overrideDigi3f1 | 1.3.6.1.4.1.46651.1.3.25 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT overrideSensorfailf1 | 1.3.6.1.4.1.46651.1.3.26 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT sensorSelectf1 | 1.3.6.1.4.1.46651.1.3.27 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT tachoPulseperrotationf1 | 1.3.6.1.4.1.46651.1.3.28 | INTEGER | read-write | Number of Tacho pulses per cycle rotation for given fan |
| INT closedLoopenablef1 | 1.3.6.1.4.1.46651.1.3.29 | INTEGER | read-write | Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable |
| INT controlTypef1 | 1.3.6.1.4.1.46651.1.3.30 | INTEGER | read-write | 0 - 0-10V DC control. 1 - PWM control |
| INT enablef1 | 1.3.6.1.4.1.46651.1.3.31 | INTEGER | read-write | 0 - Disable Fan control. 1 - Enabel fan control |
| fan2Config | 1.3.6.1.4.1.46651.1.4 | |||
| INT saveReloadConff2 | 1.3.6.1.4.1.46651.1.4.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT offTemprf2 | 1.3.6.1.4.1.46651.1.4.2 | INTEGER | read-write | Fan OFF temperature |
| INT idleOnTemprf2 | 1.3.6.1.4.1.46651.1.4.3 | INTEGER | read-write | Fan Idle Speed On temperature |
| INT idleEntryTemprf2 | 1.3.6.1.4.1.46651.1.4.4 | INTEGER | read-write | Idle entry temperature |
| INT midPoint1Temprf2 | 1.3.6.1.4.1.46651.1.4.5 | INTEGER | read-write | Mid point 1 entry temperature |
| INT setPointTemprf2 | 1.3.6.1.4.1.46651.1.4.6 | INTEGER | read-write | Set Point temperature |
| INT midPoint2Temprf2 | 1.3.6.1.4.1.46651.1.4.7 | INTEGER | read-write | Mid point 2 entry temperature |
| INT highSpeedTemprf2 | 1.3.6.1.4.1.46651.1.4.8 | INTEGER | read-write | high Speed entry temperature |
| INT extendHighSpeedEntryTemprf2 | 1.3.6.1.4.1.46651.1.4.9 | INTEGER | read-write | Extended high Speed entry temperature |
| INT extendHighSpeedExitTemprf2 | 1.3.6.1.4.1.46651.1.4.10 | INTEGER | read-write | Extended high Speed exit temperature |
| INT boostEntryTemprf2 | 1.3.6.1.4.1.46651.1.4.11 | INTEGER | read-write | Boost Speed entry temperature |
| INT boostExitTemprf2 | 1.3.6.1.4.1.46651.1.4.12 | INTEGER | read-write | Boost Speed entry temperature |
| INT idleRPMf2 | 1.3.6.1.4.1.46651.1.4.13 | INTEGER | read-write | Idle speed RPM |
| INT midPointRPMf2 | 1.3.6.1.4.1.46651.1.4.14 | INTEGER | read-write | Midpoint Speed RPM |
| INT highSpeedRPMf2 | 1.3.6.1.4.1.46651.1.4.15 | INTEGER | read-write | high Speed RPM |
| INT extendHighSpeedRPMf2 | 1.3.6.1.4.1.46651.1.4.16 | INTEGER | read-write | Extended high Speed RPM |
| INT idleDutyCyclef2 | 1.3.6.1.4.1.46651.1.4.17 | INTEGER | read-write | Idle Speed Duty Cycle |
| INT midDutyCyclef2 | 1.3.6.1.4.1.46651.1.4.18 | INTEGER | read-write | Midpoint speed Duty Cycle |
| INT highSpeedDutyCyclef2 | 1.3.6.1.4.1.46651.1.4.19 | INTEGER | read-write | high speed Duty Cycle |
| INT extendHighSpeedDutyCyclef2 | 1.3.6.1.4.1.46651.1.4.20 | INTEGER | read-write | Extended high speed Duty Cycle |
| INT boostDutyCyclef2 | 1.3.6.1.4.1.46651.1.4.21 | INTEGER | read-write | Boost speed Duty Cycle |
| INT deadBandRPMf2 | 1.3.6.1.4.1.46651.1.4.22 | INTEGER | read-write | Dead band RPM |
| INT overrideDigi1f2 | 1.3.6.1.4.1.46651.1.4.23 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT overrideDigi2f2 | 1.3.6.1.4.1.46651.1.4.24 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT overrideDigi3f2 | 1.3.6.1.4.1.46651.1.4.25 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT overrideSensorfailf2 | 1.3.6.1.4.1.46651.1.4.26 | INTEGER | read-write | 0-100 - Fan Speed in Duty cycle. 120 - No action on Over ride. |
| INT sensorSelectf2 | 1.3.6.1.4.1.46651.1.4.27 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT tachoPulseperrotationf2 | 1.3.6.1.4.1.46651.1.4.28 | INTEGER | read-write | Number of Tacho pulses per cycle rotation for given fan |
| INT closedLoopenablef2 | 1.3.6.1.4.1.46651.1.4.29 | INTEGER | read-write | Closed Loop control enable or disable for given Fan. 0 - Enable. 1 - Disable |
| INT controlTypef2 | 1.3.6.1.4.1.46651.1.4.30 | INTEGER | read-write | 0 - 0-10V DC control. 1 - PWM control |
| INT enablef2 | 1.3.6.1.4.1.46651.1.4.31 | INTEGER | read-write | 0 - Disable Fan control. 1 - Enabel fan control |
| damper1Config | 1.3.6.1.4.1.46651.1.5 | |||
| INT saveReloadConfd1 | 1.3.6.1.4.1.46651.1.5.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT lowercloseTemprd1 | 1.3.6.1.4.1.46651.1.5.2 | INTEGER | read-write | Damper lower closing temperature |
| INT setPointd1 | 1.3.6.1.4.1.46651.1.5.3 | INTEGER | read-write | Damper opening temperature |
| INT upperOpentempd1 | 1.3.6.1.4.1.46651.1.5.4 | INTEGER | read-write | Damper upper opening temperature |
| INT upperClosetempd1 | 1.3.6.1.4.1.46651.1.5.5 | INTEGER | read-write | Damper upper closing temperature |
| INT emgncyClosetempd1 | 1.3.6.1.4.1.46651.1.5.6 | INTEGER | read-write | Damper emergency closing temperature |
| INT emgncyopentempd1 | 1.3.6.1.4.1.46651.1.5.7 | INTEGER | read-write | Damper emergency open temperature |
| INT overrideDigi1d1 | 1.3.6.1.4.1.46651.1.5.8 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT overrideDigi2d1 | 1.3.6.1.4.1.46651.1.5.9 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT overrideDigi3d1 | 1.3.6.1.4.1.46651.1.5.10 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT overrideSensorFaild1 | 1.3.6.1.4.1.46651.1.5.11 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT sensSelectd1 | 1.3.6.1.4.1.46651.1.5.12 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT runDurationd1 | 1.3.6.1.4.1.46651.1.5.13 | INTEGER | read-write | Damper Run time in minutes |
| INT enabled1 | 1.3.6.1.4.1.46651.1.5.14 | INTEGER | read-write | 0 - Disable. 1 - ONOFF. 2 - Dynamic |
| damper2Config | 1.3.6.1.4.1.46651.1.6 | |||
| INT saveReloadConfd2 | 1.3.6.1.4.1.46651.1.6.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT lowercloseTemprd2 | 1.3.6.1.4.1.46651.1.6.2 | INTEGER | read-write | Damper lower closing temperature |
| INT setPointd2 | 1.3.6.1.4.1.46651.1.6.3 | INTEGER | read-write | Damper opening temperature |
| INT upperOpentempd2 | 1.3.6.1.4.1.46651.1.6.4 | INTEGER | read-write | Damper upper opening temperature |
| INT upperClosetempd2 | 1.3.6.1.4.1.46651.1.6.5 | INTEGER | read-write | Damper upper closing temperature |
| INT emgncyClosetempd2 | 1.3.6.1.4.1.46651.1.6.6 | INTEGER | read-write | Damper emergency closing temperature |
| INT emgncyopentempd2 | 1.3.6.1.4.1.46651.1.6.7 | INTEGER | read-write | Damper emergency open temperature |
| INT overrideDigi1d2 | 1.3.6.1.4.1.46651.1.6.8 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT overrideDigi2d2 | 1.3.6.1.4.1.46651.1.6.9 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT overrideDigi3d2 | 1.3.6.1.4.1.46651.1.6.10 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT overrideSensorFaild2 | 1.3.6.1.4.1.46651.1.6.11 | INTEGER | read-write | 0 - Damper close. 1 - Damper open. 120 - No action on Over ride. |
| INT sensSelectd2 | 1.3.6.1.4.1.46651.1.6.12 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT runDurationd2 | 1.3.6.1.4.1.46651.1.6.13 | INTEGER | read-write | Damper Run time in minutes |
| INT enabled2 | 1.3.6.1.4.1.46651.1.6.14 | INTEGER | read-write | 0 - Disable. 1 - ONOFF. 2 - Dynamic |
| aircon1Config | 1.3.6.1.4.1.46651.1.7 | |||
| INT saveReloadConfac1 | 1.3.6.1.4.1.46651.1.7.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT oNTemprac1 | 1.3.6.1.4.1.46651.1.7.2 | INTEGER | read-write | Air Conditioner ON temperature |
| INT oFFTemprac1 | 1.3.6.1.4.1.46651.1.7.3 | INTEGER | read-write | Air Conditioner OFF temperature |
| INT overrideDigi1ac1 | 1.3.6.1.4.1.46651.1.7.4 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. |
| INT overrideDigi2ac1 | 1.3.6.1.4.1.46651.1.7.5 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. |
| INT overrideDigi3ac1 | 1.3.6.1.4.1.46651.1.7.6 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride |
| INT overrideSensorFailac1 | 1.3.6.1.4.1.46651.1.7.7 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride |
| INT sensSelectac1 | 1.3.6.1.4.1.46651.1.7.8 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT minimumRunDurationac1 | 1.3.6.1.4.1.46651.1.7.9 | INTEGER | read-write | Minimum AC Run time in seconds |
| INT restartTimeoutac1 | 1.3.6.1.4.1.46651.1.7.10 | INTEGER | read-write | Restart timer in seconds |
| INT enableac1 | 1.3.6.1.4.1.46651.1.7.11 | INTEGER | read-write | 0 - Disable. 1 - Enable. |
| aircon2Config | 1.3.6.1.4.1.46651.1.8 | |||
| INT saveReloadConfac2 | 1.3.6.1.4.1.46651.1.8.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT onTemprac2 | 1.3.6.1.4.1.46651.1.8.2 | INTEGER | read-write | Air Conditioner ON temperature |
| INT offTemprac2 | 1.3.6.1.4.1.46651.1.8.3 | INTEGER | read-write | Air Conditioner OFF temperature |
| INT overrideDigi1ac2 | 1.3.6.1.4.1.46651.1.8.4 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. |
| INT overrideDigi2ac2 | 1.3.6.1.4.1.46651.1.8.5 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride. |
| INT overrideDigi3ac2 | 1.3.6.1.4.1.46651.1.8.6 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride |
| INT overrideSensorFailac2 | 1.3.6.1.4.1.46651.1.8.7 | INTEGER | read-write | 0 - AC OFF. 1 - AC ON. 120 - No action on Over ride |
| INT sensSelectac2 | 1.3.6.1.4.1.46651.1.8.8 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT minimumRunDurationac2 | 1.3.6.1.4.1.46651.1.8.9 | INTEGER | read-write | Minimum AC Run time in seconds |
| INT restartTimeoutac2 | 1.3.6.1.4.1.46651.1.8.10 | INTEGER | read-write | Restart timer in seconds |
| INT enableac2 | 1.3.6.1.4.1.46651.1.8.11 | INTEGER | read-write | 0 - Disable. 1 - Enable. |
| heaterConfig | 1.3.6.1.4.1.46651.1.9 | |||
| INT saveReloadConfhtr | 1.3.6.1.4.1.46651.1.9.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT onTemprhtr | 1.3.6.1.4.1.46651.1.9.2 | INTEGER | read-write | Heater ON temperature |
| INT offTemprhtr | 1.3.6.1.4.1.46651.1.9.3 | INTEGER | read-write | Heater OFF temperature |
| INT overrideDigi1htr | 1.3.6.1.4.1.46651.1.9.4 | INTEGER | read-write | 0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride. |
| INT overrideDigi2htr | 1.3.6.1.4.1.46651.1.9.5 | INTEGER | read-write | 0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride. |
| INT overrideDigi3htr | 1.3.6.1.4.1.46651.1.9.6 | INTEGER | read-write | 0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride |
| INT overrideSensorFailhtr | 1.3.6.1.4.1.46651.1.9.7 | INTEGER | read-write | 0 - Heat OFF. 1 - Heat ON. 120 - No action on Over ride |
| INT sensSelecthtr | 1.3.6.1.4.1.46651.1.9.8 | INTEGER | read-write | 0 - Onboard sensor. 1 - Room Sensor. 2 - Hotspot sensor. 3 - Ambient 2 sensor. 4 - Ambient 1 sensor. 5 - Shelter temperature |
| INT enablehtr | 1.3.6.1.4.1.46651.1.9.9 | INTEGER | read-write | 0 - Disable. 1 - Enable. |
| humidityConfig | 1.3.6.1.4.1.46651.1.10 | |||
| INT saveReloadConfhum | 1.3.6.1.4.1.46651.1.10.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT rhEntryhum | 1.3.6.1.4.1.46651.1.10.2 | INTEGER | read-write | Humidity function entry value |
| INT rhExithum | 1.3.6.1.4.1.46651.1.10.3 | INTEGER | read-write | Humidity function exit value |
| INT coolingmodehum | 1.3.6.1.4.1.46651.1.10.4 | INTEGER | read-write | 0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon. |
| INT temprsetpoffsethum | 1.3.6.1.4.1.46651.1.10.5 | INTEGER | read-write | Cooling setpoint offset |
| INT rhSensPositionhum | 1.3.6.1.4.1.46651.1.10.6 | INTEGER | read-write | 0 - Indoor. 1 - Outdoor |
| INT enablehum | 1.3.6.1.4.1.46651.1.10.7 | INTEGER | read-write | 0 - Disable. 1 - Enable. |
| systemConfig | 1.3.6.1.4.1.46651.1.11 | |||
| INT saveReloadConfsysc | 1.3.6.1.4.1.46651.1.11.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT vdcLowEntrysys | 1.3.6.1.4.1.46651.1.11.2 | INTEGER | read-write | Low voltage shut down entry |
| INT vdcLowExitsys | 1.3.6.1.4.1.46651.1.11.3 | INTEGER | read-write | Low voltage shut down exit |
| INT vdcHighEntrysys | 1.3.6.1.4.1.46651.1.11.4 | INTEGER | read-write | High voltage shut down entry |
| INT vdcHighExitsys | 1.3.6.1.4.1.46651.1.11.5 | INTEGER | read-write | High voltage shut down exit |
| INT temprLowlimitsys | 1.3.6.1.4.1.46651.1.11.6 | INTEGER | read-write | Low temperature alarm limit |
| INT temprHighlimit1sys | 1.3.6.1.4.1.46651.1.11.7 | INTEGER | read-write | High temperature alarm limit 1 |
| INT temprHighlimit2sys | 1.3.6.1.4.1.46651.1.11.8 | INTEGER | read-write | High temperature alarm limit 2 |
| INT temprHighlimit3sys | 1.3.6.1.4.1.46651.1.11.9 | INTEGER | read-write | High temperature alarm limit 3 |
| INT temprlimithyssys | 1.3.6.1.4.1.46651.1.11.10 | INTEGER | read-write | Temperature alarm limit hysteresis |
| INT rhLowlimitsys | 1.3.6.1.4.1.46651.1.11.11 | INTEGER | read-write | Humidity alarm low limit %RH |
| INT rhHighlimitsys | 1.3.6.1.4.1.46651.1.11.12 | INTEGER | read-write | Humidity alarm High limit %RH |
| INT flowpresslimit1sys | 1.3.6.1.4.1.46651.1.11.13 | INTEGER | read-write | Flow pressure limit 1 Pa |
| INT flowpresslimit2sys | 1.3.6.1.4.1.46651.1.11.14 | INTEGER | read-write | Flow pressure limit 2 Pa |
| INT flowpresshyssys | 1.3.6.1.4.1.46651.1.11.15 | INTEGER | read-write | Flow pressure limit hysteresis Pa |
| INT coolingzonessys | 1.3.6.1.4.1.46651.1.11.16 | INTEGER | read-write | 1 - One cooling zone, 2 - Two cooling zones |
| INT coolingModesys | 1.3.6.1.4.1.46651.1.11.17 | INTEGER | read-write | 0 - FC, 1 - Std, 2 - Ps, 3 - Acon |
| INT negCoolingDeltaOverridesys | 1.3.6.1.4.1.46651.1.11.18 | INTEGER | read-write | 0 - Disable, 1 - Enable |
| INT negCoolingDeltaHyssys | 1.3.6.1.4.1.46651.1.11.19 | INTEGER | read-write | Negative cooling delta hysteresis |
| INT coolingDeltatempsys | 1.3.6.1.4.1.46651.1.11.20 | INTEGER | read-write | Cooling delta temperature |
| INT shelterTemprsys | 1.3.6.1.4.1.46651.1.11.21 | INTEGER | read-write | 0 - RA, 1 - HS, 2 - Both |
| INT acleadlagsys | 1.3.6.1.4.1.46651.1.11.22 | INTEGER | read-write | 0 - Disable, 1 - Enable |
| INT coolingModeXzonesys | 1.3.6.1.4.1.46651.1.11.23 | INTEGER | read-write | 0 - FC, 1 - Std, 2 - Ps, 3 - Acon |
| INT negCoolingDeltaOverrideXzonesys | 1.3.6.1.4.1.46651.1.11.24 | INTEGER | read-write | 0 - Disable, 1 - Enable |
| INT negCoolingDeltaHysXzonesys | 1.3.6.1.4.1.46651.1.11.25 | INTEGER | read-write | Negative cooling delta hysteresis |
| INT coolingDeltatempXzonesys | 1.3.6.1.4.1.46651.1.11.26 | INTEGER | read-write | Cooling delta temperature |
| INT fan1Zonesys | 1.3.6.1.4.1.46651.1.11.27 | INTEGER | read-write | 1 - Fan 1 for Zone 1, 2 - Fan 1 for zone 2 |
| INT fan2Zonesys | 1.3.6.1.4.1.46651.1.11.28 | INTEGER | read-write | 1 - Fan 2 for Zone 1, 2 - Fan 2 for zone 2 |
| INT ac1Zonesys | 1.3.6.1.4.1.46651.1.11.29 | INTEGER | read-write | 1 - AC 1 for Zone 1, 2 - AC 1 for zone 2 |
| INT ac2Zonesys | 1.3.6.1.4.1.46651.1.11.30 | INTEGER | read-write | 1 - AC 2 for Zone 1, 2 - AC 2 for zone 2 |
| INT damper1Zonesys | 1.3.6.1.4.1.46651.1.11.31 | INTEGER | read-write | 1 - Damper 1 for Zone 1, 2 - Damper 1 for zone 2 |
| INT damper2Zonesys | 1.3.6.1.4.1.46651.1.11.32 | INTEGER | read-write | 1 - Damper 2 for Zone 1, 2 - Damper 2 for zone 2 |
| INT heaterZonesys | 1.3.6.1.4.1.46651.1.11.33 | INTEGER | read-write | 1 - Heater for Zone 1, 2 - Heater for zone 2 |
| INT statusLogsys | 1.3.6.1.4.1.46651.1.11.34 | INTEGER | read-write | 0 - Disable, 1 - Enable |
| INT logintervalsys | 1.3.6.1.4.1.46651.1.11.35 | INTEGER | read-write | Log interval in minutes |
| INT alarm1NONCsys | 1.3.6.1.4.1.46651.1.11.36 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm2NONCsys | 1.3.6.1.4.1.46651.1.11.37 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm3NONCsys | 1.3.6.1.4.1.46651.1.11.38 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm4NONCsys | 1.3.6.1.4.1.46651.1.11.39 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm5NONCsys | 1.3.6.1.4.1.46651.1.11.40 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm6NONCsys | 1.3.6.1.4.1.46651.1.11.41 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm7NONCsys | 1.3.6.1.4.1.46651.1.11.42 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm8NONCsys | 1.3.6.1.4.1.46651.1.11.43 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm9NONCsys | 1.3.6.1.4.1.46651.1.11.44 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm10NONCsys | 1.3.6.1.4.1.46651.1.11.45 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT alarm1Delaysys | 1.3.6.1.4.1.46651.1.11.46 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm2Delaysys | 1.3.6.1.4.1.46651.1.11.47 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm3Delaysys | 1.3.6.1.4.1.46651.1.11.48 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm4Delaysys | 1.3.6.1.4.1.46651.1.11.49 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm5Delaysys | 1.3.6.1.4.1.46651.1.11.50 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm6Delaysys | 1.3.6.1.4.1.46651.1.11.51 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm7Delaysys | 1.3.6.1.4.1.46651.1.11.52 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm8Delaysys | 1.3.6.1.4.1.46651.1.11.53 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm9Delaysys | 1.3.6.1.4.1.46651.1.11.54 | INTEGER | read-write | Alarm output delay in seconds |
| INT alarm10Delaysys | 1.3.6.1.4.1.46651.1.11.55 | INTEGER | read-write | Alarm output delay in seconds |
| INT ac1NONCsys | 1.3.6.1.4.1.46651.1.11.56 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT ac2NONCsys | 1.3.6.1.4.1.46651.1.11.57 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT dig1NONCsys | 1.3.6.1.4.1.46651.1.11.58 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT dig2NONCsys | 1.3.6.1.4.1.46651.1.11.59 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT dig3NONCsys | 1.3.6.1.4.1.46651.1.11.60 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT dig2funcoverridesys | 1.3.6.1.4.1.46651.1.11.61 | INTEGER | read-write | 0 - Override, 1 - setpoint offset, 2 - mode X |
| INT dig3funcoverridesys | 1.3.6.1.4.1.46651.1.11.62 | INTEGER | read-write | 0 - Override, 1 - setpoint offset, 2 - mode X |
| INT dig2offsetsys | 1.3.6.1.4.1.46651.1.11.63 | INTEGER | read-write | Cooling setpoint offset |
| INT dig3offsetsys | 1.3.6.1.4.1.46651.1.11.64 | INTEGER | read-write | Cooling setpoint offset |
| INT dig2trigModesys | 1.3.6.1.4.1.46651.1.11.65 | INTEGER | read-write | 0 - FC, 1 - Std, 2 - Ps, 3 - Acon |
| INT dig3TrigModesys | 1.3.6.1.4.1.46651.1.11.66 | INTEGER | read-write | 0 - FC, 1 - Std, 2 - Ps, 3 - Acon |
| INT filterGuard1NONCsys | 1.3.6.1.4.1.46651.1.11.67 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT filterGuard2NONCsys | 1.3.6.1.4.1.46651.1.11.68 | INTEGER | read-write | 0 - NO, 1 - NC |
| INT temprUnitsCFsys | 1.3.6.1.4.1.46651.1.11.69 | INTEGER | read-write | 0 - Celcius, 1 - Fahrenheit |
| INT languageEnglishsys | 1.3.6.1.4.1.46651.1.11.70 | INTEGER | read-write | 0 - Disable, 1 - Enable |
| alarmConfig | 1.3.6.1.4.1.46651.1.12 | |||
| INT saveReloadConfAlm | 1.3.6.1.4.1.46651.1.12.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Alarm Mapping reloaded |
| INT alarm1mask | 1.3.6.1.4.1.46651.1.12.2 | INTEGER | read-write | Alarm drive 1 Mask [Can have multiple Alarm Errors]. Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select 1 - 1 - Voltage Low 2 - 2 - Voltage High 3 - 4 - Tempr Low 4 - 8 - Tempr Limit 1 5 - 16 - Tempr Limit 2 6 - 32 - Tempr Limit 3 7 - 64 - Humid. Low 8 - 128 - Humid. High 9 - 256 - Fltr Pressure 1 10 - 512 - Fltr Pressure 2 11 - 1024 - Fan 1 12 - 2048 - Fan 2 13 - 4096 - Onboard Sens 14 - 8192 - Room Sens 15 - 16384 - Hotspot Sens 16 - 32768 - Ambient 1 Sens 17 - 65536 - Ambient 2 Sens 18 - 131072 - Dig 1 I/P 19 - 262144 - Dig 2 I/P 20 - 524288 - Dig 3 I/P 21 - 1048576 - Filter I/P 1 22 - 2097152 - Filter I/P 2 23 - 4194304 - Network 24 - 8388608 - Int storage 25 - 16777216 - SD Card |
| INT alarm2mask | 1.3.6.1.4.1.46651.1.12.3 | INTEGER | read-write | Alarm drive 2 Mask [Can have multiple Alarm Errors]. Bit Position - Value - Alarm Drive State: 0 - Unselect, 1 - Select 1 - 1 - Voltage Low 2 - 2 - Voltage High 3 - 4 - Tempr Low 4 - 8 - Tempr Limit 1 5 - 16 - Tempr Limit 2 6 - 32 - Tempr Limit 3 7 - 64 - Humid. Low 8 - 128 - Humid. High 9 - 256 - Fltr Pressure 1 10 - 512 - Fltr Pressure 2 11 - 1024 - Fan 1 12 - 2048 - Fan 2 13 - 4096 - Onboard Sens 14 - 8192 - Room Sens 15 - 16384 - Hotspot Sens 16 - 32768 - Ambient 1 Sens 17 - 65536 - Ambient 2 Sens 18 - 131072 - Dig 1 I/P 19 - 262144 - Dig 2 I/P 20 - 524288 - Dig 3 I/P 21 - 1048576 - Filter I/P 1 22 - 2097152 - Filter I/P 2 23 - 4194304 - Network 24 - 8388608 - Int storage 25 - 16777216 - SD Card |
| INT alarm3mask | 1.3.6.1.4.1.46651.1.12.4 | INTEGER | read-write | Alarm drive 3 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm4mask | 1.3.6.1.4.1.46651.1.12.5 | INTEGER | read-write | Alarm drive 4 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm5mask | 1.3.6.1.4.1.46651.1.12.6 | INTEGER | read-write | Alarm drive 5 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm6mask | 1.3.6.1.4.1.46651.1.12.7 | INTEGER | read-write | Alarm drive 6 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm7mask | 1.3.6.1.4.1.46651.1.12.8 | INTEGER | read-write | Alarm drive 7 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm8mask | 1.3.6.1.4.1.46651.1.12.9 | INTEGER | read-write | Alarm drive 8 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm9mask | 1.3.6.1.4.1.46651.1.12.10 | INTEGER | read-write | Alarm drive 9 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| INT alarm10mask | 1.3.6.1.4.1.46651.1.12.11 | INTEGER | read-write | Alarm drive 10 Select [Single Alarm Error]. Bit Position - Alarm Drive State: 0 - Unselect, 1-25 - Select 1 - Voltage Low 2 - Voltage High 3 - Tempr Low 4 - Tempr Limit 1 5 - Tempr Limit 2 6 - Tempr Limit 3 7 - Humid. Low 8 - Humid. High 9 - Fltr Pressure 1 10 - Fltr Pressure 2 11 - Fan 1 12 - Fan 2 13 - Onboard Sens 14 - Room Sens 15 - Hotspot Sens 16 - Ambient 1 Sens 17 - Ambient 2 Sens 18 - Dig 1 I/P 19 - Dig 2 I/P 20 - Dig 3 I/P 21 - Filter I/P 1 22 - Filter I/P 2 23 - Network 24 - Int storage 25 - SD Card |
| nightModeConfig | 1.3.6.1.4.1.46651.1.13 | |||
| INT saveReloadConfNm | 1.3.6.1.4.1.46651.1.13.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT starttimeHournm | 1.3.6.1.4.1.46651.1.13.2 | INTEGER | read-write | Night Mode Start time hour |
| INT startTimeMinutesnm | 1.3.6.1.4.1.46651.1.13.3 | INTEGER | read-write | Night Mode Start time minutes |
| INT endTimeHournm | 1.3.6.1.4.1.46651.1.13.4 | INTEGER | read-write | Night Mode End time hour |
| INT endTimeMinutesnm | 1.3.6.1.4.1.46651.1.13.5 | INTEGER | read-write | Night Mode End time minutes |
| INT fanMaxRPMnm | 1.3.6.1.4.1.46651.1.13.6 | INTEGER | read-write | % of max fan speed |
| INT setPointOffsetnm | 1.3.6.1.4.1.46651.1.13.7 | INTEGER | read-write | Cooling setpoint offset |
| INT coolingModenm | 1.3.6.1.4.1.46651.1.13.8 | INTEGER | read-write | 0 - Freecooling. 1 - Standard. 2 - Power save. 3 - Aircon. |
| INT enablenm | 1.3.6.1.4.1.46651.1.13.9 | INTEGER | read-write | 0 - Disable. 1 - Enable. |
| networkConfig | 1.3.6.1.4.1.46651.1.14 | |||
| INT saveReloadConfNW | 1.3.6.1.4.1.46651.1.14.1 | INTEGER | read-write | 0 - Discard modifications, 1 - Save Modifications. Configuration reloaded |
| INT dhcpenable | 1.3.6.1.4.1.46651.1.14.2 | INTEGER | read-write | 0 - Static IP, 1 - Dynamic IP |
| OCT ipaddr | 1.3.6.1.4.1.46651.1.14.3 | OCTET STRING | read-write | System IP Address |
| OCT subnetmask | 1.3.6.1.4.1.46651.1.14.4 | OCTET STRING | read-write | Sub-net Mask |
| OCT gatewayIPaddr | 1.3.6.1.4.1.46651.1.14.5 | OCTET STRING | read-write | Default Gateway IP Address |
| OCT ntpIPaddr | 1.3.6.1.4.1.46651.1.14.6 | OCTET STRING | read-write | DNS IP Address |
| INT snmpPort | 1.3.6.1.4.1.46651.1.14.7 | INTEGER | read-write | SNMP Agent Port |
| OCT trapServer1IPaddr | 1.3.6.1.4.1.46651.1.14.8 | OCTET STRING | read-write | SNMP TRAP manager 1 IP address |
| INT trapServer1port | 1.3.6.1.4.1.46651.1.14.9 | INTEGER | read-write | SNMP TRAP manager 1 Port Number |
| OCT trapServer2IPaddr | 1.3.6.1.4.1.46651.1.14.10 | OCTET STRING | read-write | SNMP TRAP manager 2 IP address |
| INT trapServer2port | 1.3.6.1.4.1.46651.1.14.11 | INTEGER | read-write | SNMP TRAP manager 2 Port Number |
| OCT trapServer3IPaddr | 1.3.6.1.4.1.46651.1.14.12 | OCTET STRING | read-write | SNMP TRAP manager 3 IP address |
| INT trapServer3port | 1.3.6.1.4.1.46651.1.14.13 | INTEGER | read-write | SNMP TRAP manager 3 Port Number |
| OCT snmpCommunity | 1.3.6.1.4.1.46651.1.14.14 | OCTET STRING | read-write | SNMP Read/write Community string |
| OCT hostName | 1.3.6.1.4.1.46651.1.14.15 | OCTET STRING | read-write | System Netwrok Host name |
| trapError | 1.3.6.1.4.1.46651.1.15 | |||
| INT errorNumber | 1.3.6.1.4.1.46651.1.15.1 | INTEGER | not-accessible | Error Number corresponding to CC3000 controller Error. |
| INT status | 1.3.6.1.4.1.46651.1.15.2 | INTEGER | not-accessible | Error Status Active/SET or Inactive/CLEAR. |
| OCT value | 1.3.6.1.4.1.46651.1.15.3 | OCTET STRING | not-accessible | Value Corresponding to Error Occurance Instance. |
| OCT info | 1.3.6.1.4.1.46651.1.15.4 | OCTET STRING | not-accessible | Description of Current Error. |
RFC description
Dantherm CC3000 cooling controller management including fan, damper, and temperature monitoring.