DANTHERM-COOLING-MIB :: digitalInputStatus

MIB Reference — IPNetwork Monitor · Updated October 02, 2026

All MIBs › DANTHERM-COOLING-MIB › digitalInputStatus

digitalInputStatus

Module: DANTHERM-COOLING-MIB

OID (symbolic): DANTHERM-COOLING-MIB::digitalInputStatus

OID (numeric): 1.3.6.1.4.1.46651.1.1.34

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: Controller Alarm Drive Status. Binary Bit Position - Digital Input State: 0 - Inactive , 1 - Active 0 - DIG 1 I/P 1 - DIG 2 I/P 2 - DIG 3 I/P 3 - FILTER GUARD DIGI 1 I/P 4 - FILTER GUARD DIGI 2 I/P

What is digitalInputStatus?

Bit field of the digital input states, 1 meaning active: bit 0 digital input 1, 1 digital input 2, 2 digital input 3, 3 filter guard input 1, 4 filter guard input 2. The source heading calls it 'alarm drive status', which looks copied; it describes inputs.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.46651.1.1.34
snmpwalk -v2c -c public <target> DANTHERM-COOLING-MIB::digitalInputStatus

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.46651.1.1.34.1
snmpget -v2c -c public <target> DANTHERM-COOLING-MIB::digitalInputStatus.1

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> digitalInputStatus.1

Start monitoring Dantherm CC3000 precision cooling/HVAC controller with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DANTHERM-COOLING-MIB::digitalInputStatus OID value, configure state conditions and alerts, and monitor any Dantherm CC3000 precision cooling/HVAC controller from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.46651danthermCoolingDANTHERM-COOLING-MIB
1.3.6.1.4.1.46651.1controllerCC3000DANTHERM-COOLING-MIB
1.3.6.1.4.1.46651.1.1systemStatusDANTHERM-COOLING-MIB
1.3.6.1.4.1.46651.1.1.34digitalInputStatusDANTHERM-COOLING-MIB