All MIBs › BESTPOWER-MIB
Category: Hardware and Environment
Description: Manages Best Power UPS units, monitoring battery status, input/output voltage, load percentage, and fault conditions.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is BESTPOWER-MIB?
BESTPOWER-MIB manages Best Power (a legacy UPS brand) uninterruptible power supply units, exposing identity, battery, and power-line status objects for the device. It reports UPS identity (model, serial number, firmware revision, VA rating), battery health (status, time on battery, runtime remaining, voltage), and multi-phase input/output voltage readings. This is a core hardware-health MIB for facilities monitoring, directly exposing battery status/runtime and power condition so an admin can detect an ongoing power outage, a failing battery, or an overloaded UPS before it shuts down connected equipment. It follows the general structure of the widely-used UPS-MIB (RFC 1628) conventions, though implemented as a proprietary Best Power extension. It is typically deployed in data centers or telecom equipment rooms protecting servers/network gear from power loss. Engineers can download the BESTPOWER-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in BESTPOWER-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Best Power UPS (uninterruptible power supply)
Monitoring Examples
An admin would poll upsBatteryStatus and upsBatteryRuntimeRemaining to confirm the UPS has sufficient battery reserve, and check upsBatteryTimeOnBattery to see whether the unit is currently running on battery due to a utility outage. Comparing upsInputPhase2/upsInputPhase3 against upsOutputPhase2 across phases would reveal an input brownout or phase imbalance the UPS is compensating for, while upsIdentUpsType and upsIdentVARating confirm the unit's capacity matches the connected load.
What Can Be Monitored
- battery status and runtime remaining
- time on battery
- input/output voltage per phase
- UPS identity/model/firmware
- battery voltage
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| Gauge | |
| IpAddress | |
| enterprises |
From RFC1213-MIB
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| bestPower | 1.3.6.1.4.1.2947 | |||
| bestLink | 1.3.6.1.4.1.2947.1 | |||
| NTF upsTrapPowerFail | 1.3.6.1.4.1.2947.1.0.1 | WARNING: Utility power not available. | ||
| NTF upsTrapPowerRestored | 1.3.6.1.4.1.2947.1.0.2 | INFORMATION: Utility power has been restored. | ||
| NTF upsTrapUPSOnBattery | 1.3.6.1.4.1.2947.1.0.3 | WARNING: The UPS has switched to battery backup power. | ||
| NTF upsTrapUPSNotOnBattery | 1.3.6.1.4.1.2947.1.0.4 | INFORMATION: The UPS is not on battery power. | ||
| NTF upsTrapLowRuntime | 1.3.6.1.4.1.2947.1.0.5 | SEVERE: The runtime remaining on battery power is very short, and the UPS will soon shut down. | ||
| NTF upsTrapUPSCanRunOnBattery | 1.3.6.1.4.1.2947.1.0.6 | INFORMATION: The UPS has returned from a low runtime condition. | ||
| NTF upsTrapNearLowBattery | 1.3.6.1.4.1.2947.1.0.7 | SEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to the load. | ||
| NTF upsTrapHighBattery | 1.3.6.1.4.1.2947.1.0.8 | WARNING: The battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance. | ||
| NTF upsTrapBatteryOK | 1.3.6.1.4.1.2947.1.0.9 | INFORMATION: The UPS has returned from a near low or high battery condition. | ||
| NTF upsTrapLowBattery | 1.3.6.1.4.1.2947.1.0.10 | SEVERE: The UPS will run for approximately 2 minutes more and then put itself to sleep to prevent a complete discharge of the batteries. | ||
| NTF upsTrapCheckBattery | 1.3.6.1.4.1.2947.1.0.11 | SEVERE: The UPS has failed a scheduled or manual battery test. | ||
| NTF upsTrapReplaceBattery | 1.3.6.1.4.1.2947.1.0.12 | SEVERE: One or more UPS batteries need to be replaced. | ||
| NTF upsTrapCheckInverter | 1.3.6.1.4.1.2947.1.0.13 | SEVERE: The UPS has failed a scheduled or manual inverter test. | ||
| NTF upsTrapBatteriesDisconnected | 1.3.6.1.4.1.2947.1.0.14 | WARNING: The UPS battery voltage is either too low or missing to start up. | ||
| NTF upsTrapOutputOverload | 1.3.6.1.4.1.2947.1.0.15 | WARNING: The output load exceeds the UPS output capacity. | ||
| NTF upsTrapUPSNoLongerOverloaded | 1.3.6.1.4.1.2947.1.0.16 | INFORMATION: The UPS has returned from an output overload condition. | ||
| NTF upsTrapLowAcOut | 1.3.6.1.4.1.2947.1.0.17 | SEVERE: The output load has exceeded the UPS output capacity, and the UPS has shut down. | ||
| NTF upsTrapCircuitBreakerWarning | 1.3.6.1.4.1.2947.1.0.18 | SEVERE: To much load equipment has been connected to the UPS and has has caused excess current draw from the output. | ||
| NTF upsTrapCircuitBreakerOK | 1.3.6.1.4.1.2947.1.0.19 | INFORMATION: The UPS has returned from a circuit breaker warning condition. | ||
| NTF upsTrapCircuitBreakerShdn | 1.3.6.1.4.1.2947.1.0.20 | SEVERE: The UPS has shut down due to an extended excess of current draw from the output. | ||
| NTF upsTrapBypassOn | 1.3.6.1.4.1.2947.1.0.21 | SEVERE: The Bypass is presently engaged on the UPS. | ||
| NTF upsTrapUPSOnline | 1.3.6.1.4.1.2947.1.0.22 | INFORMATION: The UPS has returned from an on bypass condition. | ||
| NTF upsTrapSiteWiringFault | 1.3.6.1.4.1.2947.1.0.23 | SEVERE: The UPS has found a problem in your wall outlet. | ||
| NTF upsTrapCheckFan | 1.3.6.1.4.1.2947.1.0.24 | SEVERE: The fan on the UPS has stopped . | ||
| NTF upsTrapHighUPSTemp | 1.3.6.1.4.1.2947.1.0.25 | SEVERE: The internal temperature inside the UPS is too hot. | ||
| NTF upsTrapTempOK | 1.3.6.1.4.1.2947.1.0.26 | INFORMATION: The UPS has returned from a high ambient temp condition. | ||
| NTF upsTrapHighHSTemp | 1.3.6.1.4.1.2947.1.0.27 | SEVERE: The Inverter heatsink assembly inside the UPS is too hot . | ||
| NTF upsTrapHSTempOK | 1.3.6.1.4.1.2947.1.0.28 | INFORMATION: The UPS has returned from a high heatsink temp condition. | ||
| NTF upsTrapHighXFMRTemp | 1.3.6.1.4.1.2947.1.0.29 | SEVERE: The temperature of the main transformer inside the UPS is too hot . | ||
| NTF upsTrapHighPFMTemp | 1.3.6.1.4.1.2947.1.0.30 | SEVERE: The temperature of the PFM module inside the UPS is too hot. | ||
| NTF upsTrapProbeMissing | 1.3.6.1.4.1.2947.1.0.31 | SEVERE: One or all of the temperature probes has been disconnected on the UPS. | ||
| NTF upsTrapProbeReconnected | 1.3.6.1.4.1.2947.1.0.32 | INFORMATION: The UPS has returned from a probe missing condition. | ||
| NTF upsTrapCheckPowerSupply | 1.3.6.1.4.1.2947.1.0.33 | SEVERE: The internal DC supply voltages are attenuated or missing. | ||
| NTF upsTrapTapRegulatorFault | 1.3.6.1.4.1.2947.1.0.34 | SEVERE: The UPS detected a possible failure in the tap changer (open or welded relay, etc.) | ||
| NTF upsTrapRelayFailure | 1.3.6.1.4.1.2947.1.0.35 | SEVERE: There is a hardware problem inside the UPS. | ||
| NTF upsTrapCheckFuse | 1.3.6.1.4.1.2947.1.0.36 | SEVERE: The failure of one or more fuses has been detected. | ||
| NTF upsTrapCheckMOV | 1.3.6.1.4.1.2947.1.0.37 | SEVERE: One or more MOVs have failed due to a voltage surge. | ||
| NTF upsTrapMemoryError | 1.3.6.1.4.1.2947.1.0.38 | SEVERE: The UPS has lost the programmed settings in the memory of the logic board. | ||
| NTF upsTrapCallService | 1.3.6.1.4.1.2947.1.0.39 | SEVERE: A hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance. | ||
| NTF upsTrapManualAlarmBeeperTestInitiated | 1.3.6.1.4.1.2947.1.0.40 | INFORMATION: A manual test of the alarm beeper is being performed on the UPS. | ||
| NTF upsTrapManualAlarmBeeperTestAborted | 1.3.6.1.4.1.2947.1.0.41 | INFORMATION: The test of UPS has completed. | ||
| NTF upsTrapScheduledTestInProgress | 1.3.6.1.4.1.2947.1.0.42 | INFORMATION: A test is in progress. | ||
| NTF upsTrapScheduledTestFailed | 1.3.6.1.4.1.2947.1.0.43 | SEVERE: The last test performed failed. | ||
| NTF upsTrapCommunicationLost | 1.3.6.1.4.1.2947.1.0.44 | SEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress. | ||
| NTF upsTrapCommunicationRestored | 1.3.6.1.4.1.2947.1.0.45 | INFORMATION: Communication with the UPS has been restored. | ||
| NTF upsTrapUPSGoingDown | 1.3.6.1.4.1.2947.1.0.46 | WARNING: The ups has been given shutdown command by the management station. | ||
| NTF upsTrapUPSTurnedOff | 1.3.6.1.4.1.2947.1.0.47 | INFORMATION: The ups has been turned off by the management station. | ||
| NTF upsTrapUPSSleeping | 1.3.6.1.4.1.2947.1.0.48 | INFORMATION: The UPS has entered in 'sleep' mode. Power to the load has been cut off. | ||
| NTF upsTrapUPSWokeUp | 1.3.6.1.4.1.2947.1.0.49 | INFORMATION: The UPS woke up from 'sleep' mode. Power to the load has been restored. | ||
| NTF upsTrapUPSRebooted | 1.3.6.1.4.1.2947.1.0.50 | INFORMATION: The UPS is rebooted. | ||
| NTF upsTrapEmergencyPowerOFF | 1.3.6.1.4.1.2947.1.0.51 | SEVERE: The Emergency Power OFF feature has been activiated at the RS-232 port on the UPS. | ||
| NTF upsTrapHistLogWarn | 1.3.6.1.4.1.2947.1.0.52 | WARNING: The ups history log buffer is almost full. | ||
| NTF upsTrapEventLogWarn | 1.3.6.1.4.1.2947.1.0.53 | WARNING: The ups event log buffer is almost full. | ||
| NTF upsTrapUPSFail | 1.3.6.1.4.1.2947.1.0.54 | SEVERE: A critical fault has been detected inside the UPS. Power to the load has been shut off. | ||
| upsIdent | 1.3.6.1.4.1.2947.1.1 | |||
| STR upsIdentUpsName | 1.3.6.1.4.1.2947.1.1.1 | DisplayString | read-only | An ID string identifying the Family of UPS. |
| STR upsIdentModel | 1.3.6.1.4.1.2947.1.1.2 | DisplayString | read-only | The UPS model name (example: 'FE500VA'). |
| STR upsIdentVARating | 1.3.6.1.4.1.2947.1.1.3 | DisplayString | read-only | The capacity rating of the UPS expressed in VoltAmperes(VA). |
| INT upsIdentUpsType | 1.3.6.1.4.1.2947.1.1.4 | INTEGER | read-only | Type of UPS. |
| STR upsIdentUpsSerialNumber | 1.3.6.1.4.1.2947.1.1.5 | DisplayString | read-only | A unique identification number provided by the factory. |
| STR upsIdentUpsIdentification | 1.3.6.1.4.1.2947.1.1.6 | DisplayString | read-write | A string entered by the administrator to provide a unique name for the UPS. |
| STR upsIdentFirmwareRevision | 1.3.6.1.4.1.2947.1.1.7 | DisplayString | read-only | The firmware revision of the UPS. |
| STR upsIdentDateOfManufacture | 1.3.6.1.4.1.2947.1.1.8 | DisplayString | read-write | The date when the UPS was manufactured in mm/dd/yyyy format. |
| upsBattery | 1.3.6.1.4.1.2947.1.2 | |||
| INT upsBatteryStatus | 1.3.6.1.4.1.2947.1.2.1 | INTEGER | read-only | The status of the inverter . |
| INT upsBatteryTimeOnBattery | 1.3.6.1.4.1.2947.1.2.2 | INTEGER | read-only | The elapsed time in seconds since the UPS has switched to battery power. |
| INT upsBatteryRuntimeRemaining | 1.3.6.1.4.1.2947.1.2.3 | INTEGER | read-only | The remaining time in minutes that the UPS will be able to run on battery power. |
| INT upsBatteryVoltage | 1.3.6.1.4.1.2947.1.2.4 | INTEGER | read-only | The UPS battery voltage expressed in 1/10 VDC. |
| INT upsBatteryCurrent | 1.3.6.1.4.1.2947.1.2.5 | INTEGER | read-only | The battery current expressed in 1/10 ADC. |
| INT upsBatteryTemperature | 1.3.6.1.4.1.2947.1.2.6 | INTEGER | read-only | The internal UPS temperature expressed in 1/10 degree C. |
| STR upsBatteryLastReplaceDate | 1.3.6.1.4.1.2947.1.2.7 | DisplayString | read-write | The date when the UPS system's batteries were last replaced in mm/dd/yyyy format. When the UPS batteries are replaced, this value should be reset by the administrator. |
| upsInput | 1.3.6.1.4.1.2947.1.3 | |||
| INT upsInputPhase | 1.3.6.1.4.1.2947.1.3.1 | INTEGER | read-only | The AC input phase. |
| INT upsInputFrequency | 1.3.6.1.4.1.2947.1.3.2 | INTEGER | read-only | The utility line frequency in 1/10 Hz. |
| INT upsInputVoltage | 1.3.6.1.4.1.2947.1.3.3 | INTEGER | read-only | The utility line voltage in 1/10 VAC. |
| INT upsInputCurrent | 1.3.6.1.4.1.2947.1.3.4 | INTEGER | read-only | The utility line current in 1/10 Ampere AC. |
| INT upsInputPower | 1.3.6.1.4.1.2947.1.3.5 | INTEGER | read-only | The utility line power in 1/10 Watts. |
| upsInputPhase2 | 1.3.6.1.4.1.2947.1.3.6 | |||
| INT upsInputP2 | 1.3.6.1.4.1.2947.1.3.6.1 | INTEGER | read-only | The AC input phase. |
| INT upsInputFrequency2 | 1.3.6.1.4.1.2947.1.3.6.2 | INTEGER | read-only | The utility line frequency in 1/10 Hz. |
| INT upsInputVoltage2 | 1.3.6.1.4.1.2947.1.3.6.3 | INTEGER | read-only | The utility line voltage in 1/10 VAC. |
| INT upsInputCurrent2 | 1.3.6.1.4.1.2947.1.3.6.4 | INTEGER | read-only | The utility line current in 1/10 Ampere AC. |
| INT upsInputPower2 | 1.3.6.1.4.1.2947.1.3.6.5 | INTEGER | read-only | The utility line power in 1/10 Watts. |
| upsInputPhase3 | 1.3.6.1.4.1.2947.1.3.7 | |||
| INT upsInputP3 | 1.3.6.1.4.1.2947.1.3.7.1 | INTEGER | read-only | The AC input phase. |
| INT upsInputFrequency3 | 1.3.6.1.4.1.2947.1.3.7.2 | INTEGER | read-only | The utility line frequency in 1/10 Hz. |
| INT upsInputVoltage3 | 1.3.6.1.4.1.2947.1.3.7.3 | INTEGER | read-only | The utility line voltage in 1/10 VAC. |
| INT upsInputCurrent3 | 1.3.6.1.4.1.2947.1.3.7.4 | INTEGER | read-only | The utility line current in 1/10 Ampere AC. |
| INT upsInputPower3 | 1.3.6.1.4.1.2947.1.3.7.5 | INTEGER | read-only | The utility line power in 1/10 Watts. |
| upsOutput | 1.3.6.1.4.1.2947.1.4 | |||
| INT upsOutputStatus | 1.3.6.1.4.1.2947.1.4.1 | INTEGER | read-only | The current state of the UPS. If the UPS is unable to determine its state, this variable is set to unknown(1). |
| INT upsOutputPhase | 1.3.6.1.4.1.2947.1.4.2 | INTEGER | read-only | The output phase. |
| INT upsOutputFrequency | 1.3.6.1.4.1.2947.1.4.3 | INTEGER | read-only | The output frequency of the UPS expressed in 1/10 Hz. |
| INT upsOutputVoltage | 1.3.6.1.4.1.2947.1.4.4 | INTEGER | read-only | The output voltage of the UPS expressed in 1/10 VAC. |
| NUM upsOutputCurrent | 1.3.6.1.4.1.2947.1.4.5 | NonNegativeInteger | read-only | The output current of the UPS expressed in 1/10 AC Amperes. |
| NUM upsOutputTruePower | 1.3.6.1.4.1.2947.1.4.6 | NonNegativeInteger | read-only | The true output power of the UPS expressed in 1/10 Watts. |
| NUM upsOutputApparentPower | 1.3.6.1.4.1.2947.1.4.7 | NonNegativeInteger | read-only | The apparent output power of the UPS expressed in 1/10 VoltAmperes(VA). |
| INT upsOutputPowerFactor | 1.3.6.1.4.1.2947.1.4.8 | INTEGER | read-only | The output powerfactor of the UPS expressed in +/- 1/10 units deviating from 1. |
| INT upsOutputPercentLoad | 1.3.6.1.4.1.2947.1.4.9 | INTEGER | read-only | The percentage of the total UPS power capacity being used expressed in % of 100. |
| upsOutputPhase2 | 1.3.6.1.4.1.2947.1.4.10 | |||
| INT upsOutputP2 | 1.3.6.1.4.1.2947.1.4.10.1 | INTEGER | read-only | The output phase. |
| INT upsOutputFrequency2 | 1.3.6.1.4.1.2947.1.4.10.2 | INTEGER | read-only | The output frequency of the UPS expressed in 1/10 Hz. |
| INT upsOutputVoltage2 | 1.3.6.1.4.1.2947.1.4.10.3 | INTEGER | read-only | The output voltage of the UPS expressed in 1/10 VAC. |
| NUM upsOutputCurrent2 | 1.3.6.1.4.1.2947.1.4.10.4 | NonNegativeInteger | read-only | The output current of the UPS expressed in 1/10 AC Amperes. |
| NUM upsOutputTruePower2 | 1.3.6.1.4.1.2947.1.4.10.5 | NonNegativeInteger | read-only | The true output power of the UPS expressed in 1/10 Watts. |
| NUM upsOutputApparentPower2 | 1.3.6.1.4.1.2947.1.4.10.6 | NonNegativeInteger | read-only | The apparent output power of the UPS expressed in 1/10 VoltAmperes(VA). |
| INT upsOutputPowerFactor2 | 1.3.6.1.4.1.2947.1.4.10.7 | INTEGER | read-only | The output powerfactor of the UPS expressed in +\- 1/10 units deviating from 1. |
| upsOutputPhase3 | 1.3.6.1.4.1.2947.1.4.11 | |||
| INT upsOutputP3 | 1.3.6.1.4.1.2947.1.4.11.1 | INTEGER | read-only | The output phase. |
| INT upsOutputFrequency3 | 1.3.6.1.4.1.2947.1.4.11.2 | INTEGER | read-only | The output frequency of the UPS expressed in 1/10 Hz. |
| INT upsOutputVoltage3 | 1.3.6.1.4.1.2947.1.4.11.3 | INTEGER | read-only | The output voltage of the UPS expressed in 1/10 VAC. |
| NUM upsOutputCurrent3 | 1.3.6.1.4.1.2947.1.4.11.4 | NonNegativeInteger | read-only | The output current of the UPS expressed in 1/10 AC Amperes. |
| NUM upsOutputTruePower3 | 1.3.6.1.4.1.2947.1.4.11.5 | NonNegativeInteger | read-only | The true output power of the UPS expressed in 1/10 Watts. |
| NUM upsOutputApparentPower3 | 1.3.6.1.4.1.2947.1.4.11.6 | NonNegativeInteger | read-only | The apparent output power of the UPS expressed in 1/10 VoltAmperes = (VA). |
| INT upsOutputPowerFactor3 | 1.3.6.1.4.1.2947.1.4.11.7 | INTEGER | read-only | The output powerfactor of the UPS expressed in +/- 1/10 units deviating from 1. |
| upsConfig | 1.3.6.1.4.1.2947.1.5 | |||
| INT upsConfigLowRuntimeSetpoint | 1.3.6.1.4.1.2947.1.5.1 | INTEGER | read-write | This setpoint controls when the UPS will initiate a Low Runtime Alarm. |
| INT upsConfigDelayBeforeRestart | 1.3.6.1.4.1.2947.1.5.2 | INTEGER | read-write | The delay in seconds after utility line power returns before the UPS will turn on. This value is used in conjunction with TurnUPSOff, RebootUPS, and the Scheduled Shutdown objects. |
| INT upsConfigDelayBeforeShutdown | 1.3.6.1.4.1.2947.1.5.3 | INTEGER | read-write | The delay in seconds that the UPS waits before executing an off command upon request of an external device. |
| upsConfigTest | 1.3.6.1.4.1.2947.1.5.4 | |||
| INT upsConfigTestLevel | 1.3.6.1.4.1.2947.1.5.4.1 | INTEGER | read-write | This is the level of the System Test. |
| INT upsConfigDaysBetweenTests | 1.3.6.1.4.1.2947.1.5.4.3 | INTEGER | read-write | The number of days between Tests. |
| INT upsConfigBatteryTestDuration | 1.3.6.1.4.1.2947.1.5.4.4 | INTEGER | read-write | The number of seconds the UPS must run on battery power during a battery test. |
| upsConfigScheduleTable | 1.3.6.1.4.1.2947.1.5.5 | not-accessible | The table to schedule shutting down the ups. | |
| upsConfigScheduleEntry | 1.3.6.1.4.1.2947.1.5.5.1 | not-accessible | The entries for each day. | |
| INT upsConfigScheduleIndex | 1.3.6.1.4.1.2947.1.5.5.1.1 | INTEGER | read-only | The index of scheduled events. |
| INT upsConfigScheduleShutdownDay | 1.3.6.1.4.1.2947.1.5.5.1.2 | INTEGER | read-write | The weekday on which the UPS should shut down. |
| STR upsConfigScheduleShutdownTime | 1.3.6.1.4.1.2947.1.5.5.1.3 | DisplayString | read-write | The time that the process of shutting down the UPS will be initiated |
| INT upsConfigScheduleRestartDay | 1.3.6.1.4.1.2947.1.5.5.1.4 | INTEGER | read-write | The weekday on which the UPS should restart |
| STR upsConfigScheduleRestartTime | 1.3.6.1.4.1.2947.1.5.5.1.5 | DisplayString | read-write | The time the UPS will restart in hh:mm:ss format. |
| upsConfigbestLink | 1.3.6.1.4.1.2947.1.5.8 | |||
| INT bestLinkHistoryLogFrequency | 1.3.6.1.4.1.2947.1.5.8.1 | INTEGER | read-write | The frequency of updating the history log in minutes. |
| INT bestLinkRefreshFrequency | 1.3.6.1.4.1.2947.1.5.8.2 | INTEGER | read-write | The frequency of saving configuration,history and event log data in non-volatile memory. If the value is set to 0, then saving data is disabled. |
| IP bestLinkNetId | 1.3.6.1.4.1.2947.1.5.8.3 | IpAddress | read-write | The IP address of the device. Setting this parameter causes BestLink to reboot. |
| IP bestLinkGateway | 1.3.6.1.4.1.2947.1.5.8.4 | IpAddress | read-write | The gateway address for the network BestLink is connected to. |
| IP bestLinkNetMask | 1.3.6.1.4.1.2947.1.5.8.5 | IpAddress | read-write | The net mask of the device. |
| STR bestLinkSysDate | 1.3.6.1.4.1.2947.1.5.8.6 | DisplayString | read-write | The system date of the device. The date is in mm/dd/yyyy format. The range of system date is from 1/1/1980 to 12/31/2037. |
| STR bestLinkSysTime | 1.3.6.1.4.1.2947.1.5.8.7 | DisplayString | read-write | The system time of the device. The time is in hh:mm:ss format. |
| STR bestLinkTftpFileName | 1.3.6.1.4.1.2947.1.5.8.8 | DisplayString | read-write | The tftp file name that contains the software upgrade image. |
| IP bestLinkTftpHost | 1.3.6.1.4.1.2947.1.5.8.9 | IpAddress | read-write | The tftp host IP address from where to get the image. |
| INT bestLinkFlashEEPROM | 1.3.6.1.4.1.2947.1.5.8.10 | INTEGER | read-write | Saves the history log, eventlog, and configuration data to non-volatile memory. |
| IP bestLinkPrimaryTimeServer | 1.3.6.1.4.1.2947.1.5.8.11 | IpAddress | read-write | The primary time server is responsible for sending the correct time to the UPS. |
| IP bestLinkSecondaryTimeServer | 1.3.6.1.4.1.2947.1.5.8.12 | IpAddress | read-write | The secondary time server responsible for sending the correct time to the UPS. |
| STR bestLinkSoftwareVersion | 1.3.6.1.4.1.2947.1.5.8.13 | DisplayString | read-only | The version of BestLink software. |
| upsConfigTrapsReceivers | 1.3.6.1.4.1.2947.1.5.9 | |||
| upsConfigTrapsReceiversTable | 1.3.6.1.4.1.2947.1.5.9.1 | not-accessible | A list of managers to send traps to. | |
| upsConfigTrapsReceiversEntry | 1.3.6.1.4.1.2947.1.5.9.1.1 | not-accessible | The managers to send traps to. | |
| INT trapsIndex | 1.3.6.1.4.1.2947.1.5.9.1.1.1 | INTEGER | read-only | The index to a trap receiver entry. |
| IP trapsReceiverAddr | 1.3.6.1.4.1.2947.1.5.9.1.1.2 | IpAddress | read-write | The IP address of the manager to send a trap to. |
| STR receiverCommunityString | 1.3.6.1.4.1.2947.1.5.9.1.1.3 | DisplayString | read-write | The community name to use in the trap when sent to the manager. |
| INT severityLevel | 1.3.6.1.4.1.2947.1.5.9.1.1.4 | INTEGER | read-write | The severity threshold of traps to send to the manager. Traps are labeled by severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager. |
| INT receiverAccept | 1.3.6.1.4.1.2947.1.5.9.1.1.5 | INTEGER | read-write | An entry will become active if yes, otherwise it will be disabled. |
| upsConfigRegisteredShutdownClients | 1.3.6.1.4.1.2947.1.5.10 | |||
| upsRegisteredShutdownClientsTable | 1.3.6.1.4.1.2947.1.5.10.1 | not-accessible | A list of registered shutdown client table entries. The table contains zero, one, or many rows at any moment, depending upon the number of Netwatch clients registered with BestLink | |
| upsRegisteredShutdownClientsEntry | 1.3.6.1.4.1.2947.1.5.10.1.1 | not-accessible | An entry containing information applicable to a particular registered shutdown client. | |
| NUM upsRegisteredShutdownClientsIndex | 1.3.6.1.4.1.2947.1.5.10.1.1.1 | PositiveInteger | read-only | An index of alarm entries in the RegisteredShutdownClientsTable. |
| IP upsRegisteredShutdownClientsIPAddress | 1.3.6.1.4.1.2947.1.5.10.1.1.2 | IpAddress | read-only | The IP Address of the registered shutdown client |
| INT upsRegisteredShutdownClientsTotalNumberOf | 1.3.6.1.4.1.2947.1.5.10.2 | INTEGER | read-only | The total number of registered shutdown clients. |
| upsControl | 1.3.6.1.4.1.2947.1.6 | |||
| INT upsControlTurnOffUPS | 1.3.6.1.4.1.2947.1.6.1 | INTEGER | read-write | Setting this variable to UpsOff(2) causes the UPS to shut off. When the UPS is in the off state, the UPS will remain off until the ON/OFF switch is manually toggled. Setting this variable to cancelUpsOff(1) allows for a method to cancel the upsOff(2) command to the UPS that is still pending, or will make an attempt to restart a UPS that has been shutdown, provided that BestLink is powered by some other means. Setting this variable to rebootUps(3) causes the UPS to shut off and turn back on. Setting this variable to cancelrebootUps(4) allows for a method to cancel the rebootUps(3) command to the UPS that is still pending, or will make an attempt to restart a UPS that has been shutdown, provided that BestLink is powered by some other means. |
| INT upsControlActivateUpsScheduling | 1.3.6.1.4.1.2947.1.6.4 | INTEGER | read-write | Setting this variable to On(2) causes the UPS to activate the scheduling parameters that have been previously configured within the upsConfigDailyShutdownScheduleTable and the upsConfigWeeklyShutdownScheduleTable. Setting this variable to Off(1) suspends all currently configured schedules. |
| upsTest | 1.3.6.1.4.1.2947.1.7 | |||
| INT upsManualTests | 1.3.6.1.4.1.2947.1.7.1 | INTEGER | read-write | Setting this variable to any value other than (1) causes the UPS to perform a manual test or abort a particular test in progress. |
| upsAlarm | 1.3.6.1.4.1.2947.1.8 | |||
| GAU upsAlarmsPresent | 1.3.6.1.4.1.2947.1.8.1 | Gauge | read-only | The present number of active alarm conditions. |
| INT upsLastKnownAlarm | 1.3.6.1.4.1.2947.1.8.2 | INTEGER | read-only | A unique identifier for an alarm condition. This value must remain constant. Value 'noAlarm(37)' will be returned if no Alarm has occured till the point of GET operation. |
| upsAlarmTable | 1.3.6.1.4.1.2947.1.8.3 | not-accessible | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is initially empty at agent startup. The agent creates a row in the table each time a condition is detected and deletes that row when that condition no longer pertains. The agent creates the first row with upsAlarmIndex equal to 1, and increments the value of upsAlarmIndex each time a new row is created. | |
| upsAlarmEntry | 1.3.6.1.4.1.2947.1.8.3.1 | not-accessible | An entry containing information applicable to a particular alarm. | |
| NUM upsAlarmIndex | 1.3.6.1.4.1.2947.1.8.3.1.1 | PositiveInteger | read-only | An index of alarm entries in the alarm log. |
| INT upsAlarmName | 1.3.6.1.4.1.2947.1.8.3.1.2 | INTEGER | read-only | A unique identifier for an alarm condition. This value must remain constant. |
| STR upsAlarmTime | 1.3.6.1.4.1.2947.1.8.3.1.3 | DisplayString | read-only | The time that the alarm occurred in hh:mm:ss format. |
| upsWellKnownAlarms | 1.3.6.1.4.1.2947.1.8.4 | |||
| INT upsAlarmOnBattery | 1.3.6.1.4.1.2947.1.8.4.1 | INTEGER | read-only | The UPS is drawing power from the batteries. |
| INT upsAlarmLowRuntime | 1.3.6.1.4.1.2947.1.8.4.2 | INTEGER | read-only | The remaining battery runtime is less than or equal to the upsConfigLowRuntimeSetpoint. |
| INT upsAlarmNearLowBattery | 1.3.6.1.4.1.2947.1.8.4.3 | INTEGER | read-only | The battery voltage on the UPS has reached a value where the inverter will not be able to function very much longer. |
| INT upsAlarmLowBattery | 1.3.6.1.4.1.2947.1.8.4.4 | INTEGER | read-only | The battery voltage on the UPS has reached a value where the inverter has stopped providing output power to the connected load equipment. The UPS has shutdown to protect the batteries from complete discharge. |
| INT upsAlarmHighBattery | 1.3.6.1.4.1.2947.1.8.4.5 | INTEGER | read-only | The battery charger voltage on the UPS has reached a value that is too high for safe battery maintenance. |
| INT upsAlarmCheckBattery | 1.3.6.1.4.1.2947.1.8.4.6 | INTEGER | read-only | The periodic battery test has failed. A manual test of the batteries needs to be performed to determine which battery\batteries need replaced. |
| INT upsAlarmReplaceBattery | 1.3.6.1.4.1.2947.1.8.4.7 | INTEGER | read-only | One or more batteries have been determined to require replacement. Compatibility: Fortress II |
| INT upsAlarmCheckInverter | 1.3.6.1.4.1.2947.1.8.4.8 | INTEGER | read-only | The inverter has failed the automatic system test. |
| INT upsAlarmBatteriesDisconnected | 1.3.6.1.4.1.2947.1.8.4.9 | INTEGER | read-only | The UPS has detected that the DC voltage needed to start up is too low or missing. |
| INT upsAlarmOutputOverload | 1.3.6.1.4.1.2947.1.8.4.10 | INTEGER | read-only | The output load exceeds the UPS output capacity. |
| INT upsAlarmLowAcOut | 1.3.6.1.4.1.2947.1.8.4.11 | INTEGER | read-only | The output load has exceeded the UPS output capacity, and the UPS has shut down. |
| INT upsAlarmCircuitBreakerWarning | 1.3.6.1.4.1.2947.1.8.4.12 | INTEGER | read-only | To much load equipment has been connected to the UPS and has has caused excess current draw from the output. |
| INT upsAlarmCircuitBreakerShdn | 1.3.6.1.4.1.2947.1.8.4.13 | INTEGER | read-only | The UPS has shut down due to an extended excess of current draw from the output. |
| INT upsAlarmBypassOn | 1.3.6.1.4.1.2947.1.8.4.14 | INTEGER | read-only | The Bypass is presently engaged on the UPS. |
| INT upsAlarmAutoBypass | 1.3.6.1.4.1.2947.1.8.4.15 | INTEGER | read-only | The UPS has gone into the Auto Bypass mode to redirect power around the UPS circuitry. |
| INT upsAlarmSiteWiringFault | 1.3.6.1.4.1.2947.1.8.4.16 | INTEGER | read-only | The UPS has found a problem in your wall outlet. |
| INT upsAlarmCheckFan | 1.3.6.1.4.1.2947.1.8.4.17 | INTEGER | read-only | The fan on the UPS has stopped |
| INT upsAlarmHighAmbTemp | 1.3.6.1.4.1.2947.1.8.4.18 | INTEGER | read-only | The internal temperature inside the UPS is too hot. |
| INT upsAlarmHighHSTemp | 1.3.6.1.4.1.2947.1.8.4.19 | INTEGER | read-only | The Inverter heatsink assembly inside the UPS is to hot . |
| INT upsAlarmHighXFMRTemp | 1.3.6.1.4.1.2947.1.8.4.20 | INTEGER | read-only | The temperature of the main transformer inside the UPS is too hot . |
| INT upsAlarmHighPFMTemp | 1.3.6.1.4.1.2947.1.8.4.21 | INTEGER | read-only | The temperature of the PFM module inside the UPS is too hot . |
| INT upsAlarmProbeMissing | 1.3.6.1.4.1.2947.1.8.4.22 | INTEGER | read-only | One or all of the sense probes has been disconnected on the UPS. |
| INT upsAlarmCheckPowerSupply | 1.3.6.1.4.1.2947.1.8.4.23 | INTEGER | read-only | The internal DC supply voltages are attenuated or missing. |
| INT upsAlarmTapRegulator | 1.3.6.1.4.1.2947.1.8.4.24 | INTEGER | read-only | The UPS detected a possible failure in the tap changer (open or welded relay, etc.) |
| INT upsAlarmRelayFailure | 1.3.6.1.4.1.2947.1.8.4.25 | INTEGER | read-only | There is a hardware problem inside the UPS. |
| INT upsAlarmCheckFuse | 1.3.6.1.4.1.2947.1.8.4.26 | INTEGER | read-only | The failure of one or more fuses has been detected. |
| INT upsAlarmCheckMOV | 1.3.6.1.4.1.2947.1.8.4.27 | INTEGER | read-only | One or more MOVs have failed due to a voltage surge. |
| INT upsAlarmMemoryError | 1.3.6.1.4.1.2947.1.8.4.28 | INTEGER | read-only | The UPS has lost the programmed settings in the memory of the logic board. |
| INT upsAlarmCallService | 1.3.6.1.4.1.2947.1.8.4.29 | INTEGER | read-only | A hardware malfunction has occurred inside the UPS. Please consult a factory authorized service representative for assistance. |
| INT upsAlarmupsFailed | 1.3.6.1.4.1.2947.1.8.4.30 | INTEGER | read-only | A general fault in the UPS has been detected. |
| INT upsAlarmUserTest | 1.3.6.1.4.1.2947.1.8.4.31 | INTEGER | read-only | A user test of the alarm beeper is in progress. |
| INT upsAlarmTestInProgress | 1.3.6.1.4.1.2947.1.8.4.32 | INTEGER | read-only | A test is in progress. |
| INT upsAlarmDiagnosticTestFailed | 1.3.6.1.4.1.2947.1.8.4.33 | INTEGER | read-only | The result of the last diagnostic test indicates a failure. |
| INT upsAlarmEPO | 1.3.6.1.4.1.2947.1.8.4.34 | INTEGER | read-only | The Emergency Power OFF feature has been activiated at the RS-232 port on the UPS. |
| INT upsAlarmUpsOff | 1.3.6.1.4.1.2947.1.8.4.35 | INTEGER | read-only | The output of the UPS is in the off state. |
| INT upsAlarmCommunicationsLost | 1.3.6.1.4.1.2947.1.8.4.36 | INTEGER | read-only | A problem has been encountered in the communications between the agent and the UPS. |
RFC description
Best Power UPS system management including battery status, input/output power monitoring, and control.
Start monitoring Best Power UPS systems with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.