| OID symbolic | OID numeric | Type | Access | Description |
| INE agentInetPortNumber | 1.3.6.1.4.1.13742.7.0.0.12 | InetPortNumber | accessible-for-notify | The UDP port number used for accessing
the SNMP agent on the device.
Examples:
If the associated device MIB (PX2-MIB, EMD-MIB) has deviceCascadeType set to portForwarding, then
master: 50500
slave 1:50501
slave 2: 50502
......
If cascading mode is not portForwarding and default (Standard) ports are being used, then
port: 161 |
| assetManagement | 1.3.6.1.4.1.13742.7.1.7 | | | |
| assetManagementEntry | 1.3.6.1.4.1.13742.7.1.7.1.1 | | not-accessible | An entry containing tag information and LED state for a rack unit. |
| assetManagementGroup | 1.3.6.1.4.1.13742.7.2.2.2 | | | A collection of objects providing the ability to control the
asset management strip. |
| assetManagementLogEntry | 1.3.6.1.4.1.13742.7.3.2.1 | | not-accessible | An entry in the asset management log table. |
| assetManagementLogTable | 1.3.6.1.4.1.13742.7.3.2 | | not-accessible | A ring buffer containing asset management events. |
| assetManagementTable | 1.3.6.1.4.1.13742.7.1.7.1 | | not-accessible | A list of asset management extries containing tag information and LED state.
The number of entries is given by the value of rackUnitCount. |
| assetManager | 1.3.6.1.4.1.13742.7 | | | |
| assetStrip | 1.3.6.1.4.1.13742.7.1.6 | | | |
| I32 assetStripCascadePosition | 1.3.6.1.4.1.13742.7.1.7.1.1.13 | Integer32 | read-only | This is the position of the asset Strip
in a cascaded chain. Numbered in ascending
order starting with the asset strip
connected to the device (EMX/PX).
For non-cascaded asset strips, value = 1 |
| assetStripConfigurationEntry | 1.3.6.1.4.1.13742.7.1.6.1.1 | | not-accessible | An entry containing configuration objects for a particular asset management strip unit. |
| assetStripConfigurationTable | 1.3.6.1.4.1.13742.7.1.6.1 | | not-accessible | A list of configuration entries. The number of
entries is given by the value of assetStripCount. |
| I32 assetStripCount | 1.3.6.1.4.1.13742.7.1.1 | Integer32 | read-only | The number of asset management strip units supported. |
| RGB assetStripDefaultLEDColorConnected | 1.3.6.1.4.1.13742.7.1.6.1.1.15 | RGBCOLOR | read-write | Default color of all LEDs (RGB) when a tag is connected
during automatic operation; in binary format. |
| STR assetStripDefaultLEDColorConnectedStr | 1.3.6.1.4.1.13742.7.1.6.1.1.16 | DisplayString | read-write | Default color of all LEDs (RGB) when a tag is connected
during automatic operation; string with 3 hex octets |
| RGB assetStripDefaultLEDColorDisconnected | 1.3.6.1.4.1.13742.7.1.6.1.1.17 | RGBCOLOR | read-write | Default color of all LEDs (RGB) when no tag is connected
during automatic operation; in binary format. |
| STR assetStripDefaultLEDColorDisconnectedStr | 1.3.6.1.4.1.13742.7.1.6.1.1.18 | DisplayString | read-write | Default color of all LEDs (RGB) when no tag is connected
during automatic operation; string with 3 hex octets |
| NTF assetStripFirmwareUpdate | 1.3.6.1.4.1.13742.7.0.4 | | | Asset strip firmware update state change. |
| ASS assetStripFirmwareUpdateState | 1.3.6.1.4.1.13742.7.0.0.6 | AssetStripFirmwareUpdateStateEnumeration | accessible-for-notify | The new asset strip firmware update state. |
| I32 assetStripID | 1.3.6.1.4.1.13742.7.1.6.1.1.1 | Integer32 | not-accessible | A unique value for each asset strip. Its value
ranges between 1 and the value of assetStripCount. |
| STR assetStripName | 1.3.6.1.4.1.13742.7.1.6.1.1.4 | DisplayString | read-write | Asset management strip name. |
| I32 assetStripNumber | 1.3.6.1.4.1.13742.7.0.0.4 | Integer32 | accessible-for-notify | A unique value for each asset strip. Its value
ranges between 1 and the value of assetStripCount. |
| I32 assetStripNumberOfRackUnits | 1.3.6.1.4.1.13742.7.1.7.1.1.15 | Integer32 | read-only | For non-cascaded asset strips, value = rackUnitCount
For cascaded asset strips, it is the number of rack units in the asset Strip.
Examples: 2 forAMS-M2-Z, 3 for AMS-M3-Z. |
| ASS assetStripOrientation | 1.3.6.1.4.1.13742.7.1.6.1.1.7 | AssetStripOrientationEnumeration | read-write | Is the asset strip oriented such that the connector is at the top or the bottom?
If the asset strip has a tilt sensor, then this varaible is read-only and an
to set(write) it will result in an error.
If the asset strip does not have a tilt sensor, then this variable is read-write |
| ASS assetStripState | 1.3.6.1.4.1.13742.7.1.6.1.1.3 | AssetStripStateEnumeration | read-only | Asset management strip state. |
| NTF assetStripStateChange | 1.3.6.1.4.1.13742.7.0.3 | | | The asset strip unit changed its state. |
| ASS assetStripType | 1.3.6.1.4.1.13742.7.1.6.1.1.13 | AssetStripTypeEnumeration | read-only | The asset strip type. |
| NTF assetTagConnected | 1.3.6.1.4.1.13742.7.0.1 | | | The asset tag of a rack unit was connected.
bladeTagID is empty if the asset tag is not on a blade extension. |
| NTF assetTagDisconnected | 1.3.6.1.4.1.13742.7.0.2 | | | The asset tag of a rack unit was disconnected.
bladeTagID is empty if the asset tag is not on a blade extension. |
| NTF bladeExtensionConnected | 1.3.6.1.4.1.13742.7.0.7 | | | A blade extension has been connected to the rackunit. |
| NTF bladeExtensionDisconnected | 1.3.6.1.4.1.13742.7.0.8 | | | A blade extension has been disconnected from the rackunit. |
| bladeExtensionEntry | 1.3.6.1.4.1.13742.7.1.7.2.1 | | not-accessible | An entry containing tag information for a blade server extension. |
| T/F bladeExtensionOverflow | 1.3.6.1.4.1.13742.7.1.6.1.1.12 | TruthValue | read-only | Set if the maximum number of supported tags on blade extensions is reached.
When this flag is set, new tags on blade extensions won't be discovered anymore
until other tags on blade extensions are removed. |
| NTF bladeExtensionOverflowCleared | 1.3.6.1.4.1.13742.7.0.10 | | | Free space for new tags on blade extensions is available again. |
| NTF bladeExtensionOverflowOccured | 1.3.6.1.4.1.13742.7.0.9 | | | Maximum number of supported tags on blade extension was reached.
The asset strip won't detect any new tags on blade extensions until
some are removed. |
| I32 bladeExtensionSize | 1.3.6.1.4.1.13742.7.1.7.1.1.10 | Integer32 | read-only | In case a blade extension is connected this returns the
number of slots on the extension.
If the asset strip is disconnected or no blade is connected,
then the value is 0. |
| bladeExtensionTable | 1.3.6.1.4.1.13742.7.1.7.2 | | not-accessible | A list of blade server extension entries containing tag information. |
| I32 bladeSlotID | 1.3.6.1.4.1.13742.7.1.7.2.1.1 | Integer32 | not-accessible | A unique value for each slot on a blade extension. |
| I32 bladeSlotPosition | 1.3.6.1.4.1.13742.7.1.7.2.1.3 | Integer32 | read-only | A number associated with each blade slot. It ranges
between 1 and the value of bladeExtensionSize. |
| STR bladeTagID | 1.3.6.1.4.1.13742.7.1.7.2.1.2 | DisplayString | read-only | Asset management tag attached to a blade extension at the rack unit.
Empty in case there is no tag attached. |
| STR changedParameterNewValue | 1.3.6.1.4.1.13742.7.0.0.9 | DisplayString | accessible-for-notify | The new value of the changed parameter. |
| complianceRev1 | 1.3.6.1.4.1.13742.7.2.1.1 | | | The requirements for conformance to the ASSETMANAGEMENT-MIB.
This is deprecated in favor of complianceRev2 |
| complianceRev2 | 1.3.6.1.4.1.13742.7.2.1.2 | | | The requirements for conformance to the ASSETMANAGEMENT-MIB. |
| compliances | 1.3.6.1.4.1.13742.7.2.1 | | | |
| NTF compositeAssetStripCompositionChanged | 1.3.6.1.4.1.13742.7.0.11 | | | The composition of an composite asset strip changed. |
| configGroup | 1.3.6.1.4.1.13742.7.2.2.1 | | | A collection of objects representing configuration data. |
| configGroup2 | 1.3.6.1.4.1.13742.7.2.2.5 | | | A collection of objects representing configuration data. |
| configuration | 1.3.6.1.4.1.13742.7.1 | | | |
| I32 currentBladeTagCount | 1.3.6.1.4.1.13742.7.1.6.1.1.9 | Integer32 | read-only | Number of tags currently connected to blade extensions.
This may be larger than the maxBladeTagCount. In this case
an overflow occured and all tags over maxBladeTagCount are
not recognized. |
| I32 currentMainTagCount | 1.3.6.1.4.1.13742.7.1.6.1.1.8 | Integer32 | read-only | Number of tags currently connected to the main strip. |
| RGB defaultLEDColorConnected | 1.3.6.1.4.1.13742.7.1.2 | RGBCOLOR | read-write | Default color of all LEDs (RGB) when a tag is connected
during automatic operation; in binary format.
This is deprecated in favor of assetStripDefaultLEDColorConnected
For SET operations, the value will be applied to all asset strips
For GET operations, the value returned will be the value corresponding to asset strip 1 |
| STR defaultLEDColorConnectedStr | 1.3.6.1.4.1.13742.7.1.3 | DisplayString | read-write | Default color of all LEDs (RGB) when a tag is connected
during automatic operation; string with 3 hex octets
This is deprecated in favor of assetStripDefaultLEDColorConnectedStr
For SET operations, the value will be applied to all asset strips
For GET operations, the value returned will be the value corresponding to asset strip 1 |
| RGB defaultLEDColorDisconnected | 1.3.6.1.4.1.13742.7.1.4 | RGBCOLOR | read-write | Default color of all LEDs (RGB) when no tag is connected
during automatic operation; in binary format.
This is deprecated in favor of assetStripDefaultLEDColorDisConnected
For SET operations, the value will be applied to all asset strips
For GET operations, the value returned will be the value corresponding to asset strip 1 |
| STR defaultLEDColorDisconnectedStr | 1.3.6.1.4.1.13742.7.1.5 | DisplayString | read-write | Default color of all LEDs (RGB) when no tag is connected
during automatic operation; string with 3 hex octets
This is deprecated in favor of assetStripDefaultLEDColorDisconnectedStr
For SET operations, the value will be applied to all asset strips
For GET operations, the value returned will be the value corresponding to asset strip 1 |
| DEV deviceChangedParameter | 1.3.6.1.4.1.13742.7.0.0.8 | DeviceConfigurationParameterEnumeration | accessible-for-notify | Description of the parameter(s) that changed. |
| NTF deviceConfigurationChanged | 1.3.6.1.4.1.13742.7.0.5 | | | Assetstrip configuration has changed |
| IPt deviceInetAddressType | 1.3.6.1.4.1.13742.7.0.0.2 | InetAddressType | read-only | The type of address format |
| IP deviceInetIPAddress | 1.3.6.1.4.1.13742.7.0.0.3 | InetAddress | read-only | The current IP address. A value of 0.0.0.0 indicates an error
or an unset option. |
| STR deviceName | 1.3.6.1.4.1.13742.7.0.0.1 | DisplayString | read-only | The user-defined name for the Device. |
| STR deviceUserName | 1.3.6.1.4.1.13742.7.0.0.7 | DisplayString | read-only | The user currently logged in. |
| groups | 1.3.6.1.4.1.13742.7.2.2 | | | |
| RGB ledColor | 1.3.6.1.4.1.13742.7.1.7.1.1.4 | RGBCOLOR | read-write | Color of the LED (RGB) in binary format.
Setting this value automatically switches the ledOperationMode to manual. |
| STR ledColorStr | 1.3.6.1.4.1.13742.7.1.7.1.1.5 | DisplayString | read-write | Color of the LED (RGB) in string format.
It contains 3 hex octets for the RGB colors.
Setting this value automatically switches the ledOperationMode to manual. |
| ASS ledMode | 1.3.6.1.4.1.13742.7.1.7.1.1.3 | AssetManagementLEDModeEnumeration | read-write | Mode of the LED (on, off, fastBlink,slowBlink).
Setting this value automatically switches the ledOperationMode to manual. |
| ASS ledOperationMode | 1.3.6.1.4.1.13742.7.1.7.1.1.2 | AssetManagementLEDOperationModeEnumeration | read-write | Operation mode of the LED (manual or automatic, based on tag connection). |
| log | 1.3.6.1.4.1.13742.7.3 | | | |
| I32 logAssetStripNumber | 1.3.6.1.4.1.13742.7.3.2.1.4 | Integer32 | read-only | A unique value for each asset strip. Its value
ranges between 1 and the value of assetStripCount. |
| ASS logAssetStripState | 1.3.6.1.4.1.13742.7.3.2.1.9 | AssetStripStateEnumeration | read-only | Asset management strip state. |
| logConfiguration | 1.3.6.1.4.1.13742.7.3.1 | | | |
| I32 logEventCount | 1.3.6.1.4.1.13742.7.3.1.4 | Integer32 | read-only | The total number of logged events. |
| LOG logEventType | 1.3.6.1.4.1.13742.7.3.2.1.3 | LogEventTypeEnumeration | read-only | The type of this log entry. |
| logGroup | 1.3.6.1.4.1.13742.7.2.2.6 | | | A collection of objects representing log data. |
| I32 logIndex | 1.3.6.1.4.1.13742.7.3.2.1.1 | Integer32 | not-accessible | The index of an entry in the log ring buffer. Its value
ranges between 1 and logSize. |
| STR logParentBladeID | 1.3.6.1.4.1.13742.7.3.2.1.10 | DisplayString | read-only | In case the tag is attached to a blade extension,
this indicates the tagID of the extension.
Empty in case there is no tag attached or the tag
is attached on the main strip. |
| I32 logRackUnitNumber | 1.3.6.1.4.1.13742.7.3.2.1.5 | Integer32 | read-only | A unique value for each rack unit. Its value
ranges between 1 and the value of rackUnitCount.
It corresponds with rackUnitID, the fixed ordinal
index of each rack unit. |
| I32 logRackUnitPosition | 1.3.6.1.4.1.13742.7.3.2.1.6 | Integer32 | read-only | A number associated with each rack unit. Its value
depends on the rack unit numbering mode. It ranges
between 1 and the value of rackUnitCount.
If the asset strip is disconnected, then the value is 0. |
| I32 logSizeEx | 1.3.6.1.4.1.13742.7.3.1.1 | Integer32 | read-only | The number of entries in the asset management log table. |
| I32 logSlotNumber | 1.3.6.1.4.1.13742.7.3.2.1.7 | Integer32 | read-only | A unique value for each slot on a blade extension.
Value of 0 indicates a tag on the main strip.
If the asset strip is disconnected, the value is 0 as well.
Use logEventType to distinguish the validity. |
| STR logTagID | 1.3.6.1.4.1.13742.7.3.2.1.8 | DisplayString | read-only | Asset management tag attached to the rack unit.
Empty in case there is no tag attached. |
| U32 logTimeStamp | 1.3.6.1.4.1.13742.7.3.2.1.2 | Unsigned32 | read-only | The time of the log entry in seconds relative to
January 1, 1970 00:00 UTC. |
| I32 maxBladeTagCount | 1.3.6.1.4.1.13742.7.1.6.1.1.11 | Integer32 | read-only | Maximum number of blade tags supported. |
| I32 maxMainTagCount | 1.3.6.1.4.1.13742.7.1.6.1.1.10 | Integer32 | read-only | Maximum number of tags on the main asset strip. |
| I32 newestLogID | 1.3.6.1.4.1.13742.7.3.1.3 | Integer32 | read-only | The index of the newest entry in the log table. |
| I32 numberOfComponentAssetStrips | 1.3.6.1.4.1.13742.7.1.6.1.1.14 | Integer32 | read-only | The number of components building a
composite asset strip. |
| I32 oldestLogID | 1.3.6.1.4.1.13742.7.3.1.2 | Integer32 | read-only | The index of the oldest entry in the log table. |
| I32 oldNumberOfComponentAssetStrips | 1.3.6.1.4.1.13742.7.0.0.11 | Integer32 | accessible-for-notify | The old number of components building a
composite asset strip. |
| NTF rackUnitConfigurationChanged | 1.3.6.1.4.1.13742.7.0.6 | | | Assetstrip configuration has changed |
| I32 rackUnitCount | 1.3.6.1.4.1.13742.7.1.6.1.1.2 | Integer32 | read-write | The number of rack-units for the asset management. |
| I32 rackUnitID | 1.3.6.1.4.1.13742.7.1.7.1.1.1 | Integer32 | not-accessible | A unique value for each rack unit. Its value
ranges between 1 and the value of rackUnitCount. |
| STR rackUnitName | 1.3.6.1.4.1.13742.7.1.7.1.1.12 | DisplayString | read-write | Name for a specific rackunit, may be feeely chosen. |
| I32 rackUnitNumber | 1.3.6.1.4.1.13742.7.0.0.5 | Integer32 | accessible-for-notify | A unique value for each rack unit. Its value
ranges between 1 and the value of rackUnitCount.
It corresponds with rackUnitID, the fixed ordinal
index of each rack unit. |
| RAC rackUnitNumberingMode | 1.3.6.1.4.1.13742.7.1.6.1.1.5 | RackUnitNumberingModeEnumeration | read-write | The rack unit nmbering mode for this asset strip. |
| I32 rackUnitNumberingOffset | 1.3.6.1.4.1.13742.7.1.6.1.1.6 | Integer32 | read-write | The offset (starting value) for rack Unit Numbering;
This takes care of the case in which the asset strip
is monitoring not all the assets but a subset of it,
starting from racknumberingOffset. For example, the
asset strip may be monitoring assets from 10 through 26;
default value is 1 |
| I32 rackUnitPosition | 1.3.6.1.4.1.13742.7.1.7.1.1.8 | Integer32 | read-only | A number associated with each rack unit. Its value
depends on the rack unit numbering mode. It ranges
between 1 and the value of rackUnitCount.
If the asset strip is disconnected, then the value is 0. |
| I32 rackUnitRelativePosition | 1.3.6.1.4.1.13742.7.1.7.1.1.14 | Integer32 | read-only | This is the relative position of the rackUnit
within the assetStrip. For cascaded asset
strips such as the AMS-M2-Z and AMS-M3-Z,
it is numbered in ascending order starting
with the rackunit closest to the
asset strip edge with the connector.
For non-cascaded asset strips, value = 1 |
| RAC rackUnitType | 1.3.6.1.4.1.13742.7.1.7.1.1.9 | RackUnitTypeEnumeration | read-only | Type of the connected tag (single server or blade extension).
If the asset strip is disconnected, then the value is unknown.
If the asset tag is disconnected, then the value is none. |
| raritan | 1.3.6.1.4.1.13742 | | | This MIB describes the SNMP functions of the
asset management capable products from Raritan Computer. |
| I32 slotNumber | 1.3.6.1.4.1.13742.7.0.0.10 | Integer32 | accessible-for-notify | A unique value for each slot on a blade extension.
Value of 0 indicates a tag on the main strip. |
| STR tagFamily | 1.3.6.1.4.1.13742.7.1.7.1.1.7 | DisplayString | read-only | Family of the asset management tag attached to the rack unit.
Empty in case there is no tag attached. |
| STR tagID | 1.3.6.1.4.1.13742.7.1.7.1.1.6 | DisplayString | read-only | Asset management tag attached to the rack unit.
Empty in case there is no tag attached. |
| trapInformation | 1.3.6.1.4.1.13742.7.0.0 | | | |
| trapInformationGroup | 1.3.6.1.4.1.13742.7.2.2.4 | | | A collection of objects providing information in the traps. |
| traps | 1.3.6.1.4.1.13742.7.0 | | | |
| trapsGroup | 1.3.6.1.4.1.13742.7.2.2.3 | | | A collection of traps. |