| OID symbolic | OID numeric | Type | Access | Description |
| powerware | 1.3.6.1.4.1.534 | | | |
| product | 1.3.6.1.4.1.534.6 | | | |
| dataCenter | 1.3.6.1.4.1.534.6.7 | | | |
| environmentalMonitor | 1.3.6.1.4.1.534.6.7.1 | | | |
| insObjects | 1.3.6.1.4.1.534.6.7.1.1 | | | |
| rmIdent | 1.3.6.1.4.1.534.6.7.1.1.1 | | | |
| STR insIdentManufacturer | 1.3.6.1.4.1.534.6.7.1.1.1.1 | DisplayString | read-only | The name of the RackMonitor manufacturer. |
| STR insIdentModel | 1.3.6.1.4.1.534.6.7.1.1.1.2 | DisplayString | read-only | The RackMonitor Model designation. |
| STR insIdentAgentSoftwareVersion | 1.3.6.1.4.1.534.6.7.1.1.1.3 | DisplayString | read-only | The RackMonitor software/firmware version. This variable may or
may not have the same value as
upsIdentUPSSoftwareVersion in some implementations. |
| STR insIdentName | 1.3.6.1.4.1.534.6.7.1.1.1.4 | DisplayString | read-write | A string identifying the RackMonitor. This object should be
set by the administrator. |
| rmConfig | 1.3.6.1.4.1.534.6.7.1.1.2 | | | |
| INT rmConfigMibVersion | 1.3.6.1.4.1.534.6.7.1.1.2.1 | INTEGER | read-only | The version of MIB spec. |
| rmConfigNetwork | 1.3.6.1.4.1.534.6.7.1.1.2.2 | | | |
| IP rmConfigIpAddress | 1.3.6.1.4.1.534.6.7.1.1.2.2.1 | IpAddress | read-write | The ip address that NMS can identify the managed
device |
| IP rmConfigGateway | 1.3.6.1.4.1.534.6.7.1.1.2.2.2 | IpAddress | read-write | The default gateway that allow device managed
through routers |
| IP rmConfigSubnetMask | 1.3.6.1.4.1.534.6.7.1.1.2.2.3 | IpAddress | read-write | Internet address subnet mask |
| rmConfigDateTime | 1.3.6.1.4.1.534.6.7.1.1.2.3 | | | |
| STR rmConfigDate | 1.3.6.1.4.1.534.6.7.1.1.2.3.1 | DisplayString | read-write | The date in Environmental Rack Monitor, format is (dd/mm/yyyy) |
| STR rmConfigTime | 1.3.6.1.4.1.534.6.7.1.1.2.3.2 | DisplayString | read-write | The time in Environmental Rack Monitor, format is (hh:mm:ss) |
| INT rmConfigTimeFromNtp | 1.3.6.1.4.1.534.6.7.1.1.2.3.3 | INTEGER | read-write | Enable/disable update of the date and time from the NTP server. |
| IP rmConfigNtpIpAddress | 1.3.6.1.4.1.534.6.7.1.1.2.3.4 | IpAddress | read-write | NTP IP address. |
| INT rmConfigNtpTimeZone | 1.3.6.1.4.1.534.6.7.1.1.2.3.5 | INTEGER | read-write | Enable/disable update of the date and time from the NTP server. |
| INT rmConfigDayLightSaving | 1.3.6.1.4.1.534.6.7.1.1.2.3.6 | INTEGER | read-write | Enable/disable daylight saving for NTP time, if enabled, the time
obtained from the NTP will be set one hour in advance to reflect daylight saving status. |
| rmConfigLog | 1.3.6.1.4.1.534.6.7.1.1.2.4 | | | |
| INT rmConfigHistoryLogFrequency | 1.3.6.1.4.1.534.6.7.1.1.2.4.1 | INTEGER | read-write | The frequency of the history log update. The value
is in seconds |
| INT rmConfigExtHistoryLogFrequency | 1.3.6.1.4.1.534.6.7.1.1.2.4.2 | INTEGER | read-write | The frequency of the extended history log update.
The value is in seconds |
| INT rmConfigConfigurationLog | 1.3.6.1.4.1.534.6.7.1.1.2.4.3 | INTEGER | read-write | Enable/Disable Environmental Rack Monitor parameters change logging. |
| INT rmConfigDhcpStatue | 1.3.6.1.4.1.534.6.7.1.1.2.5 | INTEGER | read-write | Enable or Disable DHCP/BootP capability |
| INT rmConfigPingStatue | 1.3.6.1.4.1.534.6.7.1.1.2.6 | INTEGER | read-write | Enable or Disable Ping Echo capability |
| INT rmConfigTftpStatue | 1.3.6.1.4.1.534.6.7.1.1.2.7 | INTEGER | read-write | Enable or Disable TFTP network upgrade capability |
| rmConfigTelnet | 1.3.6.1.4.1.534.6.7.1.1.2.8 | | | |
| INT rmConfigTelnetStatue | 1.3.6.1.4.1.534.6.7.1.1.2.8.1 | INTEGER | read-write | Enable or Disable telnet access |
| INT rmConfigTelnetPortNumber | 1.3.6.1.4.1.534.6.7.1.1.2.8.2 | INTEGER | read-write | Setting the server port for telnet. |
| rmConfigHttp | 1.3.6.1.4.1.534.6.7.1.1.2.9 | | | |
| INT rmConfigHttpStatue | 1.3.6.1.4.1.534.6.7.1.1.2.9.1 | INTEGER | read-write | Enable or Disable HTTP access |
| INT rmConfigHttpPortNumber | 1.3.6.1.4.1.534.6.7.1.1.2.9.2 | INTEGER | read-write | Setting the server port of HTTP. |
| INT rmConfigHttpSecurity | 1.3.6.1.4.1.534.6.7.1.1.2.9.3 | INTEGER | read-write | Enable/Disable HTTP access for read-only users |
| rmConfigSnmp | 1.3.6.1.4.1.534.6.7.1.1.2.10 | | | |
| INT rmConfigSnmpStatue | 1.3.6.1.4.1.534.6.7.1.1.2.10.1 | INTEGER | read-write | Enable or Disable SNMP access |
| INT rmConfigSnmpPortNumber | 1.3.6.1.4.1.534.6.7.1.1.2.10.2 | INTEGER | read-write | Setting the server port for SNMP. |
| rmConfigControl | 1.3.6.1.4.1.534.6.7.1.1.2.11 | | | |
| INT rmConfigResetToDefault | 1.3.6.1.4.1.534.6.7.1.1.2.11.1 | INTEGER | read-write | Reset all parameters of Environmental Rack Monitor to default values |
| INT rmConfigRestart | 1.3.6.1.4.1.534.6.7.1.1.2.11.2 | INTEGER | read-write | Restart rm |
| rmConfigTrap | 1.3.6.1.4.1.534.6.7.1.1.2.12 | | | |
| INT rmConfigTrapRetryCount | 1.3.6.1.4.1.534.6.7.1.1.2.12.1 | INTEGER | read-write | The count of repeat traps to send to NMS before trap
acknowledge received. |
| INT rmConfigTrapRetryTime | 1.3.6.1.4.1.534.6.7.1.1.2.12.2 | INTEGER | read-write | The time between retry traps sent to NMS. |
| INT rmConfigTrapAckSignature | 1.3.6.1.4.1.534.6.7.1.1.2.12.3 | INTEGER | read-write | The signature of trap acknowledge. |
| INT rmConfigPollRate | 1.3.6.1.4.1.534.6.7.1.1.2.13 | INTEGER | read-write | The frequency that the Rack Monitor will read from sensors
(unit : second). |
| rmConfigTrapsReceiversTable | 1.3.6.1.4.1.534.6.7.1.1.2.14 | | not-accessible | A list of managers to send traps to. The number of
entries is given by the value of rmConfigNumTrapReceivers |
| rmConfigTrapsReceiversEntry | 1.3.6.1.4.1.534.6.7.1.1.2.14.1 | | not-accessible | The managers to send traps to. |
| INT trapsIndex | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.1 | INTEGER | read-only | The index to a trap receiver entry. |
| IP trapsReceiverAddr | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.2 | IpAddress | read-write | The IP address of the manager to send a trap to. |
| INT receiverSeverityLevel | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.4 | INTEGER | read-write | The severity level of traps to be received by this manager. |
| STR receiverDescription | 1.3.6.1.4.1.534.6.7.1.1.2.14.1.5 | DisplayString | read-write | Description of trap receivers |
| rmConfigAccessControlTable | 1.3.6.1.4.1.534.6.7.1.1.2.15 | | not-accessible | A list of managers which can access rm with private
community string. |
| rmConfigAccessControlEntry | 1.3.6.1.4.1.534.6.7.1.1.2.15.1 | | not-accessible | The managers. |
| INT accessIndex | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.1 | INTEGER | read-only | The index to a access control entry. |
| IP accessControlAddr | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.2 | IpAddress | read-write | The IP address of the manager to access RackMonitor |
| INT accessControlMode | 1.3.6.1.4.1.534.6.7.1.1.2.15.1.4 | INTEGER | read-write | Access type, only read/Write access type can change parameter
of RackMonitor |
| INT rmConfigTemperatureUnit | 1.3.6.1.4.1.534.6.7.1.1.2.16 | INTEGER | read-write | The temperature unit of the system, can be Celsius or Fahrenheit |
| INT rmConfigDateFormat | 1.3.6.1.4.1.534.6.7.1.1.2.17 | INTEGER | read-write | The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy |
| sensorMonitor | 1.3.6.1.4.1.534.6.7.1.1.3 | | | |
| INT smSensorNumber | 1.3.6.1.4.1.534.6.7.1.1.3.1 | INTEGER | read-only | The number of sensors that can be monitored. |
| smSensorTable | 1.3.6.1.4.1.534.6.7.1.1.3.2 | | not-accessible | A list of sensor devices to be monitored. |
| smSensorEntry | 1.3.6.1.4.1.534.6.7.1.1.3.2.1 | | not-accessible | The sensor device. |
| INT smDeviceIndex | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.1 | INTEGER | read-only | The index to a sensor device entry. |
| INT smDeviceStatus | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.2 | INTEGER | read-only | The device type plugged into RackMonitor. |
| INT smDeviceTemperature | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.3 | INTEGER | read-only | The temperature of sensor on device RackMonitor, the unit is 0.1 degree. |
| INT smDeviceTemperatureAlarm | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.4 | INTEGER | read-only | The status of temperature sensor on device RackMonitor. |
| INT smDeviceHumidity | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.5 | INTEGER | read-only | The humidity of sensor on device RackMonitor, the unit is 0.1%. |
| INT smDeviceHumidityAlarm | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.6 | INTEGER | read-only | The device type plugged into RackMonitor. |
| INT smAlarm1 | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.7 | INTEGER | read-only | The device type plugged into RackMonitor. |
| INT smAlarm2 | 1.3.6.1.4.1.534.6.7.1.1.3.2.1.8 | INTEGER | read-only | The device type plugged into RackMonitor. |
| sensorConfig | 1.3.6.1.4.1.534.6.7.1.1.4 | | | |
| INT scSensorNumber | 1.3.6.1.4.1.534.6.7.1.1.4.1 | INTEGER | read-only | The number of sensors that can be plugged into RackMonitor. |
| scSensorTable | 1.3.6.1.4.1.534.6.7.1.1.4.2 | | not-accessible | A list of sensor devices to be configured. |
| scSensorEntry | 1.3.6.1.4.1.534.6.7.1.1.4.2.1 | | not-accessible | The sensor device. |
| INT scDeviceIndex | 1.3.6.1.4.1.534.6.7.1.1.4.2.1.1 | INTEGER | read-only | The index to a sensor device entry. |
| STR scDeviceName | 1.3.6.1.4.1.534.6.7.1.1.4.2.1.2 | DisplayString | read-write | The name of the sensor device for identification. |
| INT scDeviceState | 1.3.6.1.4.1.534.6.7.1.1.4.2.1.3 | INTEGER | read-write | The setup of sensor device type. |
| scSensor1 | 1.3.6.1.4.1.534.6.7.1.1.4.3 | | | |
| STR scSensor1DeviceName | 1.3.6.1.4.1.534.6.7.1.1.4.3.1 | DisplayString | read-write | The name of sensor device. |
| INT scSensor1DeviceState | 1.3.6.1.4.1.534.6.7.1.1.4.3.2 | INTEGER | read-write | The setup of sensor device type. |
| scSensor1Temperature | 1.3.6.1.4.1.534.6.7.1.1.4.3.3 | | | |
| STR scSensor1TemperatureName | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.1 | DisplayString | read-write | The temperature sensor name. |
| INT scSensor1TemperatureLowWarning | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.2 | INTEGER | read-write | The set point to trigger low warning alarm. |
| INT scSensor1TemperatureLowCritical | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.3 | INTEGER | read-write | The threshold to trigger low critical alarm. |
| INT scSensor1TemperatureHighWarning | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.4 | INTEGER | read-write | The threshold to trigger high warning alarm. |
| INT scSensor1TemperatureHighCritical | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.5 | INTEGER | read-write | The threshold to trigger high critical alarm. |
| INT scSensor1TemperatureHysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.6 | INTEGER | read-write | The set value to prevent too many alarms when temperature is hovering around the
set threshold. |
| INT scSensor1TemperatureCalibration | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.7 | INTEGER | read-write | The set value to get the correct temperature according to the reference temperature. |
| INT scSensor1TemperatureLowWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.8 | INTEGER | read-write | Enable/Disable the set point to trigger low warning alarm. |
| INT scSensor1TemperatureLowCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.9 | INTEGER | read-write | Enable/Disable the set point to trigger low critical alarm. |
| INT scSensor1TemperatureHighWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.10 | INTEGER | read-write | Enable/Disable the set point to trigger high warning alarm. |
| INT scSensor1TemperatureHighCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.3.11 | INTEGER | read-write | Enable/disable the set point to trigger high critical alarm. |
| scSensor1Humidity | 1.3.6.1.4.1.534.6.7.1.1.4.3.4 | | | |
| STR scSensor1HumdityName | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.1 | DisplayString | read-write | The humidity sensor name. |
| INT scSensor1HumidityLowWarning | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.2 | INTEGER | read-write | The set point to trigger low warning alarm. |
| INT scSensor1HumidityLowCritical | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.3 | INTEGER | read-write | The threshold to trigger low critical alarm. |
| INT scSensor1HumidityHighWarning | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.4 | INTEGER | read-write | The threshold to trigger high warning alarm. |
| INT scSensor1HumidityHighCritical | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.5 | INTEGER | read-write | The threshold to trigger high critical alarm. |
| INT scSensor1HumidityHysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.6 | INTEGER | read-write | The set value to prevent too many alarms when Humidity is hovering around the
set threshold. |
| INT scSensor1HumidityCalibration | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.7 | INTEGER | read-write | The set value to get the correct temperature according to your reference temperature. |
| INT scSensor1HumidityLowWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.8 | INTEGER | read-write | Enable/Disable the set point to trigger low warning alarm. |
| INT scSensor1HumidityLowCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.9 | INTEGER | read-write | Enable/Disable the set point to trigger low critical alarm. |
| INT scSensor1HumidityHighWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.10 | INTEGER | read-write | Enable/Disable the set point to trigger high warning alarm. |
| INT scSensor1HumidityHighCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.3.4.11 | INTEGER | read-write | Enable/Disable the set point to trigger high critical alarm. |
| scSensor1Alarm1 | 1.3.6.1.4.1.534.6.7.1.1.4.3.5 | | | |
| STR scSensor1Alarm1Name | 1.3.6.1.4.1.534.6.7.1.1.4.3.5.1 | DisplayString | read-write | The name of alarm-1. |
| INT scSensor1Alarm1State | 1.3.6.1.4.1.534.6.7.1.1.4.3.5.2 | INTEGER | read-write | Setup the signal type to trigger alarm. |
| INT scSensor1Alarm1Hysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.3.5.3 | INTEGER | read-write | The set value to delay the alarm triggered when event occurs. |
| scSensor1Alarm2 | 1.3.6.1.4.1.534.6.7.1.1.4.3.6 | | | |
| STR scSensor1Alarm2Name | 1.3.6.1.4.1.534.6.7.1.1.4.3.6.1 | DisplayString | read-write | The name of alarm-1. |
| INT scSensor1Alarm2State | 1.3.6.1.4.1.534.6.7.1.1.4.3.6.2 | INTEGER | read-write | Setup the signal type to trigger alarm. |
| INT scSensor1Alarm2Hysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.3.6.3 | INTEGER | read-write | The set value to delay the alarm triggered when event occurs. |
| scSensor2 | 1.3.6.1.4.1.534.6.7.1.1.4.4 | | | |
| STR scSensor2DeviceName | 1.3.6.1.4.1.534.6.7.1.1.4.4.1 | DisplayString | read-write | The name of sensor device. |
| INT scSensor2DeviceState | 1.3.6.1.4.1.534.6.7.1.1.4.4.2 | INTEGER | read-write | The setup of sensor device type. |
| scSensor2Temperature | 1.3.6.1.4.1.534.6.7.1.1.4.4.3 | | | |
| STR scSensor2TemperatureName | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.1 | DisplayString | read-write | The temperature sensor name. |
| INT scSensor2TemperatureLowWarning | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.2 | INTEGER | read-write | The set point to trigger low warning alarm. |
| INT scSensor2TemperatureLowCritical | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.3 | INTEGER | read-write | The threshold to trigger low critical alarm. |
| INT scSensor2TemperatureHighWarning | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.4 | INTEGER | read-write | The threshold to trigger high warning alarm. |
| INT scSensor2TemperatureHighCritical | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.5 | INTEGER | read-write | The threshold to trigger high critical alarm. |
| INT scSensor2TemperatureHysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.6 | INTEGER | read-write | The set value to prevent too many alarms when temperature is hovering around the
set threshold. |
| INT scSensor2TemperatureCalibration | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.7 | INTEGER | read-write | The set value to get the correct temperature according to your reference temperature. |
| INT scSensor2TemperatureLowWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.8 | INTEGER | read-write | Enable/Disable the set point to trigger low warning alarm. |
| INT scSensor2TemperatureLowCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.9 | INTEGER | read-write | Enable/Disable the set point to trigger low critical alarm. |
| INT scSensor2TemperatureHighWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.10 | INTEGER | read-write | Enable/Disable the set point to trigger high warning alarm. |
| INT scSensor2TemperatureHighCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.3.11 | INTEGER | read-write | Enable/Disable the set point to trigger high critical alarm. |
| scSensor2Humidity | 1.3.6.1.4.1.534.6.7.1.1.4.4.4 | | | |
| STR scSensor2HumdityName | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.1 | DisplayString | read-write | The humidity sensor name. |
| INT scSensor2HumidityLowWarning | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.2 | INTEGER | read-write | The set point to trigger low warning alarm. |
| INT scSensor2HumidityLowCritical | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.3 | INTEGER | read-write | The threshold to trigger low critical alarm. |
| INT scSensor2HumidityHighWarning | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.4 | INTEGER | read-write | The threshold to trigger high warning alarm. |
| INT scSensor2HumidityHighCritical | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.5 | INTEGER | read-write | The threshold to trigger high critical alarm. |
| INT scSensor2HumidityHysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.6 | INTEGER | read-write | The set value to prevent too many alarms when Humidity is hovering around the
set threshold. |
| INT scSensor2HumidityCalibration | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.7 | INTEGER | read-write | The set value to get the correct temperature according to the reference temperature. |
| INT scSensor2HumidityLowWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.8 | INTEGER | read-write | Enable/Disable the set point to trigger low warning alarm. |
| INT scSensor2HumidityLowCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.9 | INTEGER | read-write | Enable/Disable the set point to trigger low critical alarm. |
| INT scSensor2HumidityHighWarningStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.10 | INTEGER | read-write | Enable/Disable the set point to trigger high warning alarm. |
| INT scSensor2HumidityHighCriticalStatus | 1.3.6.1.4.1.534.6.7.1.1.4.4.4.11 | INTEGER | read-write | Enable/Disable the set point to trigger high critical alarm. |
| scSensor2Alarm1 | 1.3.6.1.4.1.534.6.7.1.1.4.4.5 | | | |
| STR scSensor2Alarm1Name | 1.3.6.1.4.1.534.6.7.1.1.4.4.5.1 | DisplayString | read-write | The name of alarm-1. |
| INT scSensor2Alarm1State | 1.3.6.1.4.1.534.6.7.1.1.4.4.5.2 | INTEGER | read-write | Setup the signal type to trigger alarm. |
| INT scSensor2Alarm1Hysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.4.5.3 | INTEGER | read-write | The set value to delay the alarm triggered when event occurs. |
| scSensor2Alarm2 | 1.3.6.1.4.1.534.6.7.1.1.4.4.6 | | | |
| STR scSensor2Alarm2Name | 1.3.6.1.4.1.534.6.7.1.1.4.4.6.1 | DisplayString | read-write | The name of alarm-1. |
| INT scSensor2Alarm2State | 1.3.6.1.4.1.534.6.7.1.1.4.4.6.2 | INTEGER | read-write | Setup the signal type to trigger alarm. |
| INT scSensor2Alarm2Hysteresis | 1.3.6.1.4.1.534.6.7.1.1.4.4.6.3 | INTEGER | read-write | The set value to delay the alarm triggered when event occurs. |
| rmTraps | 1.3.6.1.4.1.534.6.7.1.2 | | | |
| NTF rmCommunicationRestored | 1.3.6.1.4.1.534.6.7.1.2.0.1 | | | INFORMATION: Communication between RackMonitor and sensor had established. |
| NTF rmCommunicationLost | 1.3.6.1.4.1.534.6.7.1.2.0.2 | | | WARNING: Communication between RackMonitor and sensor had lost. |
| NTF rmAlarm1Inactive | 1.3.6.1.4.1.534.6.7.1.2.0.3 | | | INFORMATION: Alarm1 of sensor had return from active state. |
| NTF rmAlarm1Active | 1.3.6.1.4.1.534.6.7.1.2.0.4 | | | WARNING: Alarm1 has become active. |
| NTF rmAlarm2Inactive | 1.3.6.1.4.1.534.6.7.1.2.0.5 | | | INFORMATION: Alarm2 of sensor has returned to normal state. |
| NTF rmAlarm2Active | 1.3.6.1.4.1.534.6.7.1.2.0.6 | | | WARNING: Alarm2 had became active. |
| NTF rmTemperatureNotHighWarning | 1.3.6.1.4.1.534.6.7.1.2.0.7 | | | INFORMATION: The temperature of sensor had return from High warning to normal. |
| NTF rmTemperatureHighWarning | 1.3.6.1.4.1.534.6.7.1.2.0.8 | | | WARNING: The temperature of sensor was higher than High warning set point. |
| NTF rmTemperatureNotLowWarning | 1.3.6.1.4.1.534.6.7.1.2.0.9 | | | INFORMATION: The temperature of sensor had return from low warning to normal. |
| NTF rmTemperatureLowWarning | 1.3.6.1.4.1.534.6.7.1.2.0.10 | | | WARNING: The temperature of sensor was lower than low warning set point. |
| NTF rmTemperatureNotHighCritical | 1.3.6.1.4.1.534.6.7.1.2.0.11 | | | INFORMATION: The temperature of sensor lower than high critical set point. |
| NTF rmTemperatureHighCritical | 1.3.6.1.4.1.534.6.7.1.2.0.12 | | | CRITICAL: The temperature of sensor was higher than high critical set point. |
| NTF rmTemperatureNotLowCritical | 1.3.6.1.4.1.534.6.7.1.2.0.13 | | | INFORMATION: The temperature of sensor was higher than low critical set point. |
| NTF rmTemperatureLowCritical | 1.3.6.1.4.1.534.6.7.1.2.0.14 | | | CRITICAL: The temperature of sensor was lower than low critical set point. |
| NTF rmHumidityNotHighWarning | 1.3.6.1.4.1.534.6.7.1.2.0.15 | | | INFORMATION: The humidity of sensor had return from High warning to normal. |
| NTF rmHumidityHighWarning | 1.3.6.1.4.1.534.6.7.1.2.0.16 | | | WARNING: The humidity of sensor was higher than High warning set point. |
| NTF rmHumidityNotLowWarning | 1.3.6.1.4.1.534.6.7.1.2.0.17 | | | INFORMATION: The humidity of sensor had return from low warning to normal. |
| NTF rmHumidityLowWarning | 1.3.6.1.4.1.534.6.7.1.2.0.18 | | | WARNING: The humidity of sensor was lower than low warning set point. |
| NTF rmHumidityNotHighCritical | 1.3.6.1.4.1.534.6.7.1.2.0.19 | | | INFORMATION: The humidity of sensor lower than high critical set point. |
| NTF rmHumidityHighCritical | 1.3.6.1.4.1.534.6.7.1.2.0.20 | | | CRITICAL: The humidity of sensor was higher than high critical set point. |
| NTF rmHumidityNotLowCritical | 1.3.6.1.4.1.534.6.7.1.2.0.21 | | | INFORMATION: The humidity of sensor was higher than low critical set point. |
| NTF rmHumidityLowCritical | 1.3.6.1.4.1.534.6.7.1.2.0.22 | | | CRITICAL: The humidity of sensor was lower than low critical set point. |