lcUpsControlUnixShutdownDelay

Module: LIEBERT-UPSTATION-S-UPS-MIB

OID (symbolic): LIEBERT-UPSTATION-S-UPS-MIB::lcUpsControlUnixShutdownDelay

OID (numeric): 1.3.6.1.4.1.476.1.1.1.1.8.5

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock.

The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.

What is lcUpsControlUnixShutdownDelay?

This read-write integer, in seconds, when set instructs the agent to schedule a UNIX-style shutdown sequence, which is only valid while the UPS is running on battery; once triggered, the output turns off at the scheduled time even if utility power returns first. This is used to guarantee attached servers get a clean shutdown during an extended outage rather than running the battery completely flat.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.5
snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-S-UPS-MIB::lcUpsControlUnixShutdownDelay

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.5.1
snmpget -v2c -c public <target> LIEBERT-UPSTATION-S-UPS-MIB::lcUpsControlUnixShutdownDelay.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.8.5.1 i <value>

Start monitoring Liebert (Emerson) UPStation S series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-S-UPS-MIB::lcUpsControlUnixShutdownDelay OID value, configure state conditions and alerts, and monitor any Liebert (Emerson) UPStation S series UPS from a single console.

OID Breakdown

Upper-level ancestors (12 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.1liebertUpsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1luExtensionsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1luCoreLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1.8lcUpsControlLIEBERT-MICRO-UPS-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.1.1.1.8.5lcUpsControlUnixShutdownDelayLIEBERT-UPSTATION-S-UPS-MIB