All MIBs › LIEBERT-UPSTATION-G-UPS-MIB › lcUpsControlUnixShutdownDelay
lcUpsControlUnixShutdownDelay
Module: LIEBERT-UPSTATION-G-UPS-MIB
OID (symbolic): LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlUnixShutdownDelay
OID (numeric): 1.3.6.1.4.1.476.1.1.1.1.8.5
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Setting this object causes the agent to instruct the UPS to perform a UNIX Shutdown in the indicated number of seconds. The agent counts down the number of seconds until the event will take place. A Unix shutdown is only valid if the UPS is on Battery. During a UNIX Shutdown, the UPS will turn off the output even if the Utility comes back on line before the shutdown time arrives. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock.
The command can be cancelled by setting lcUpsControlCancelCommand to the value 'cancel'.
What is lcUpsControlUnixShutdownDelay?
Setting this read-write value schedules a coordinated Unix host shutdown in the given number of seconds, valid only while the UPS is running on battery; during the countdown the UPS will still cut output at the scheduled time even if utility power returns first, and the command can be cancelled via lcUpsControlCancelCommands.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.5 snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlUnixShutdownDelay
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.5.1 snmpget -v2c -c public <target> LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlUnixShutdownDelay.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.8.5.1 i <value>
Start monitoring Liebert UPStation G UPS management card with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlUnixShutdownDelay OID value, configure state conditions and alerts, and monitor any Liebert UPStation G UPS management card from a single console.
OID Breakdown
Upper-level ancestors (12 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.1 | liebertUps | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1 | luExtensions | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1 | luCore | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1.8 | lcUpsControl | LIEBERT-MICRO-UPS-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.1.1.1.8.5 | lcUpsControlUnixShutdownDelay | LIEBERT-UPSTATION-G-UPS-MIB |