All MIBs › LIEBERT-UPSTATION-G-UPS-MIB › lcUpsControlOutputOffTrapDelay
lcUpsControlOutputOffTrapDelay
Module: LIEBERT-UPSTATION-G-UPS-MIB
OID (symbolic): LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlOutputOffTrapDelay
OID (numeric): 1.3.6.1.4.1.476.1.1.1.1.8.3
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: When 'lcUpsControlOutputOffDelay' reaches a value less than or equal to this object's value, an lcUpsOutputOffWarningTrap will be produced and this object will be reset to 0.
What is lcUpsControlOutputOffTrapDelay?
This read-write value sets a warning lead time: once the countdown in lcUpsControlOutputOffDelay drops to or below this value, the agent fires an lcUpsOutputOffWarningTrap and resets this object back to 0, giving downstream systems advance notice before the output actually turns off.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.3 snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlOutputOffTrapDelay
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.3.1 snmpget -v2c -c public <target> LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlOutputOffTrapDelay.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.8.3.1 i <value>
Start monitoring Liebert UPStation G UPS management card with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-G-UPS-MIB::lcUpsControlOutputOffTrapDelay OID value, configure state conditions and alerts, and monitor any Liebert UPStation G UPS management card from a single console.
OID Breakdown
Upper-level ancestors (12 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.1 | liebertUps | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1 | luExtensions | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1 | luCore | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1.8 | lcUpsControl | LIEBERT-MICRO-UPS-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.1.1.1.8.3 | lcUpsControlOutputOffTrapDelay | LIEBERT-UPSTATION-G-UPS-MIB |