LIEBERT-UPSTATION-D-UPS-MIB :: lcUpsControlOutputOnDelay

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsLIEBERT-UPSTATION-D-UPS-MIBlcUpsControlOutputOnDelay

lcUpsControlOutputOnDelay

Module: LIEBERT-UPSTATION-D-UPS-MIB

OID (symbolic): LIEBERT-UPSTATION-D-UPS-MIB::lcUpsControlOutputOnDelay

OID (numeric): 1.3.6.1.4.1.476.1.1.1.1.8.2

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock.

The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.

What is lcUpsControlOutputOnDelay?

Setting this to a number of seconds schedules the UPS to turn its output back on after that countdown, firing an lcUpsOutputOnTrap when it completes; the counterpart to lcUpsControlOutputOffDelay for scheduled power-up, also cancellable via lcUpsControlCancelCommands.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.2
snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-D-UPS-MIB::lcUpsControlOutputOnDelay

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.2.1
snmpget -v2c -c public <target> LIEBERT-UPSTATION-D-UPS-MIB::lcUpsControlOutputOnDelay.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.8.2.1 i <value>

Start monitoring Liebert (Vertiv) UPStation D series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-D-UPS-MIB::lcUpsControlOutputOnDelay OID value, configure state conditions and alerts, and monitor any Liebert (Vertiv) UPStation D series UPS from a single console.

OID Breakdown

Upper-level ancestors (12 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.1liebertUpsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1luExtensionsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1luCoreLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.1.8lcUpsControlLIEBERT-MICRO-UPS-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.1.1.1.8.2lcUpsControlOutputOnDelayLIEBERT-UPSTATION-D-UPS-MIB