All MIBs › LIEBERT-UPS-MIB › lcUpsControlOutputOnDelay
lcUpsControlOutputOnDelay
Module: LIEBERT-UPS-MIB
OID (symbolic): LIEBERT-UPS-MIB::lcUpsControlOutputOnDelay
OID (numeric): 1.3.6.1.4.1.476.1.1.1.1.8.2
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Setting this object causes the agent to instruct the UPS to turn on the output after the indicated number of seconds. The agent counts down the number of seconds until the event will take place. The agent issues an lcUpsOutputOnTrap when the countdown finishes. Note that different models have different clock resolutions, usually greater than 1 second. As a result, the command will only be accurate to the resolution of the UPS's clock.
The command can be cancelled by setting lcUpsControlCancelCommand to the value cancel.
What is lcUpsControlOutputOnDelay?
Setting this schedules the UPS to turn its output back on after the given number of seconds, firing an lcUpsOutputOnTrap when the countdown completes; also cancellable.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.2 snmpwalk -v2c -c public <target> LIEBERT-UPS-MIB::lcUpsControlOutputOnDelay
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.8.2.1 snmpget -v2c -c public <target> LIEBERT-UPS-MIB::lcUpsControlOutputOnDelay.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.8.2.1 i <value>
Start monitoring Liebert (Vertiv) UPS unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPS-MIB::lcUpsControlOutputOnDelay OID value, configure state conditions and alerts, and monitor any Liebert (Vertiv) UPS unit from a single console.
OID Breakdown
Upper-level ancestors (12 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.1 | liebertUps | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1 | luExtensions | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1 | luCore | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1.8 | lcUpsControl | LIEBERT-MICRO-UPS-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.1.1.1.8.2 | lcUpsControlOutputOnDelay | LIEBERT-UPS-MIB |