| OID symbolic | OID numeric | Type | Access | Description |
| carel | 1.3.6.1.4.1.9839 | | | |
| systm | 1.3.6.1.4.1.9839.1 | | | |
| I32 agentRelease | 1.3.6.1.4.1.9839.1.1 | Integer32 | read-only | Release of the Agent. |
| I32 agentCode | 1.3.6.1.4.1.9839.1.2 | Integer32 | read-only | Code of the Agent. 2=pCOWeb. |
| instruments | 1.3.6.1.4.1.9839.2 | | | |
| pCOWebInfo | 1.3.6.1.4.1.9839.2.0 | | | |
| pCOStatusgroup | 1.3.6.1.4.1.9839.2.0.10 | | | |
| I32 pCOId1_Status | 1.3.6.1.4.1.9839.2.0.10.1 | Integer32 | read-only | Status of pCOId1. 0=Offline, 1=Init, 2=Online |
| pCOErrorsNumbergroup | 1.3.6.1.4.1.9839.2.0.11 | | | |
| I32 pCOId1_ErrorsNumber | 1.3.6.1.4.1.9839.2.0.11.1 | Integer32 | read-only | Number of Communication Errors from pCOId1 to pCOWeb. |
| dap4_alMIB | 1.3.6.1.4.1.9839.2.1 | | | This is the MIB module for the dap4_al device. |
| digitalObjects | 1.3.6.1.4.1.9839.2.1.1 | | | |
| I32 dehum_on | 1.3.6.1.4.1.9839.2.1.1.1 | Integer32 | read-only | Dehumidify mode is running |
| I32 hum_on | 1.3.6.1.4.1.9839.2.1.1.2 | Integer32 | read-only | Humidifier is running |
| I32 engy_on | 1.3.6.1.4.1.9839.2.1.1.3 | Integer32 | read-only | Energy saver is running |
| I32 cool_inhibit | 1.3.6.1.4.1.9839.2.1.1.4 | Integer32 | read-only | Cooling inhibit from Zone Master |
| I32 heat_held | 1.3.6.1.4.1.9839.2.1.1.5 | Integer32 | read-only | Heat inhibited due to alarm condition |
| I32 humidifier_inhibit | 1.3.6.1.4.1.9839.2.1.1.6 | Integer32 | read-only | Humidifier stopped due to alarm |
| I32 dehum_inhibit | 1.3.6.1.4.1.9839.2.1.1.7 | Integer32 | read-only | Dehum is inhibited |
| I32 rht_during_dehum | 1.3.6.1.4.1.9839.2.1.1.8 | Integer32 | read-only | reheat during dehum |
| I32 floor_wtr_alm | 1.3.6.1.4.1.9839.2.1.1.9 | Integer32 | read-only | Water under floor alarm |
| I32 air_flow_alm | 1.3.6.1.4.1.9839.2.1.1.10 | Integer32 | read-only | No air flow alarm |
| I32 filter_alm | 1.3.6.1.4.1.9839.2.1.1.11 | Integer32 | read-only | Dirty filter from digital input |
| I32 humidifier_alm | 1.3.6.1.4.1.9839.2.1.1.12 | Integer32 | read-only | Alarm from humidifier digital input |
| I32 firestat_alm | 1.3.6.1.4.1.9839.2.1.1.13 | Integer32 | read-only | Temperature of return air above firestat alarm set point |
| I32 shortcycle_alm | 1.3.6.1.4.1.9839.2.1.1.14 | Integer32 | read-only | One or more comps has short cycled |
| I32 humidity_fail | 1.3.6.1.4.1.9839.2.1.1.15 | Integer32 | read-only | Sensor is out of range |
| I32 ret_air_fail | 1.3.6.1.4.1.9839.2.1.1.16 | Integer32 | read-only | Sensor is out of range |
| I32 maint_alm | 1.3.6.1.4.1.9839.2.1.1.17 | Integer32 | read-only | Maintenance Schedule Due alarm |
| I32 c1_hp_alm | 1.3.6.1.4.1.9839.2.1.1.18 | Integer32 | read-only | High pressure alarm |
| I32 c1_lp_alm | 1.3.6.1.4.1.9839.2.1.1.19 | Integer32 | read-only | Low pressure alarm |
| I32 c2_hp_alm | 1.3.6.1.4.1.9839.2.1.1.20 | Integer32 | read-only | High pressure alarm |
| I32 c2_lp_alm | 1.3.6.1.4.1.9839.2.1.1.21 | Integer32 | read-only | Low pressure alarm |
| I32 smoke_alm | 1.3.6.1.4.1.9839.2.1.1.22 | Integer32 | read-only | Smoke detected from digital input |
| I32 wtr_flow_alm | 1.3.6.1.4.1.9839.2.1.1.23 | Integer32 | read-only | No water flow alarm |
| I32 disch_air_fail | 1.3.6.1.4.1.9839.2.1.1.24 | Integer32 | read-only | Sensor is out of range |
| I32 ra_tmp_hi_alm | 1.3.6.1.4.1.9839.2.1.1.25 | Integer32 | read-only | Temperature of return air above alarm set point |
| I32 ra_tmp_lo_alm | 1.3.6.1.4.1.9839.2.1.1.26 | Integer32 | read-only | Temperature of return air below alarm set point |
| I32 hum_hi_alm | 1.3.6.1.4.1.9839.2.1.1.27 | Integer32 | read-only | Humidity above alarm set point |
| I32 hum_lo_alm | 1.3.6.1.4.1.9839.2.1.1.28 | Integer32 | read-only | Humidity below alarm set point |
| I32 fan_overload | 1.3.6.1.4.1.9839.2.1.1.29 | Integer32 | read-only | Fan overload |
| I32 stdby_pump_on | 1.3.6.1.4.1.9839.2.1.1.30 | Integer32 | read-only | Standby pump on: Check primary pump -Optional alarm. Pump failure input signal required |
| I32 cust_msg_sw1 | 1.3.6.1.4.1.9839.2.1.1.31 | Integer32 | read-only | Custom alarm #1 -Optional alarm. External alarm input required. Factory programmed custom message required |
| I32 cust_msg_sw2 | 1.3.6.1.4.1.9839.2.1.1.32 | Integer32 | read-only | Custom alarm #2 -Optional alarm. External alarm input required. Factory programmed custom message required |
| I32 cust_msg_sw3 | 1.3.6.1.4.1.9839.2.1.1.33 | Integer32 | read-only | Custom alarm #3 -Optional alarm. External alarm input required. Factory programmed custom message required |
| I32 cust_msg_sw4 | 1.3.6.1.4.1.9839.2.1.1.34 | Integer32 | read-only | Custom alarm #4 -Optional alarm. External alarm input required. Factory programmed custom message required |
| I32 humsw_inhibit | 1.3.6.1.4.1.9839.2.1.1.35 | Integer32 | read-only | Humidifier stopped due to custom alarm switch |
| I32 heat_inhibit | 1.3.6.1.4.1.9839.2.1.1.36 | Integer32 | read-only | Heat inhibited due to custom switch alarm condition |
| I32 rht_hum_inhibit | 1.3.6.1.4.1.9839.2.1.1.37 | Integer32 | read-only | Reheat and humidification inhibited from operation |
| I32 disch_tmp_lo_alm | 1.3.6.1.4.1.9839.2.1.1.38 | Integer32 | read-only | Temperature of discharge air below alarm set point |
| I32 override_alm | 1.3.6.1.4.1.9839.2.1.1.39 | Integer32 | read-only | Manual override: Check bypass switches - Standard alarm. Manual override switch is on |
| I32 condensation_alm | 1.3.6.1.4.1.9839.2.1.1.40 | Integer32 | read-only | High condensation from digital input |
| I32 unit_in_standby | 1.3.6.1.4.1.9839.2.1.1.41 | Integer32 | read-only | Unit in standby, all functions held off - Optional alarm. Control input signal required Factory setting required |
| I32 cw_sns_fail | 1.3.6.1.4.1.9839.2.1.1.42 | Integer32 | read-only | Sensor is out of range |
| I32 humsw_chk_cyl | 1.3.6.1.4.1.9839.2.1.1.43 | Integer32 | read-only | Humidifier stopped due to custom alarm switch |
| I32 bms_cooling_inhibit | 1.3.6.1.4.1.9839.2.1.1.44 | Integer32 | read-write | Cooling operation inhibited by BMS |
| I32 bms_heat_inhibit | 1.3.6.1.4.1.9839.2.1.1.45 | Integer32 | read-write | Heat inhibited due to bms |
| I32 bms_humidifier_inhibit | 1.3.6.1.4.1.9839.2.1.1.46 | Integer32 | read-write | Humidifier operation inhibited by BMS |
| I32 bms_dehum_inhibit | 1.3.6.1.4.1.9839.2.1.1.47 | Integer32 | read-write | Dehumidify mode inhibited by bms |
| I32 fan_inhibit_bms | 1.3.6.1.4.1.9839.2.1.1.48 | Integer32 | read-write | Inhibit fan by bms |
| I32 hum_expect | 1.3.6.1.4.1.9839.2.1.1.49 | Integer32 | read-only | Reduces control humidity cycling |
| I32 usashr_f_c | 1.3.6.1.4.1.9839.2.1.1.50 | Integer32 | read-write | Temperature Mode 0=_C 1=_F |
| I32 lead_comp | 1.3.6.1.4.1.9839.2.1.1.52 | Integer32 | read-only | Lead compressor select 0= C1, 1= C2 |
| I32 wtrvlv_dir | 1.3.6.1.4.1.9839.2.1.1.53 | Integer32 | read-only | Water valve direct or reverse acting |
| I32 ups_on_alm | 1.3.6.1.4.1.9839.2.1.1.54 | Integer32 | read-only | Alarm: UPS power on: Check main power -Optional alarm. External alarm input required |
| I32 pwrup_alm | 1.3.6.1.4.1.9839.2.1.1.55 | Integer32 | read-only | Loss of power requires manual reset of alarm |
| I32 seetag_cust_alm1 | 1.3.6.1.4.1.9839.2.1.1.56 | Integer32 | read-only | Local alarm #1: See tag inside door =Optional alarm. External alarm input required |
| I32 seetag_cust_alm2 | 1.3.6.1.4.1.9839.2.1.1.57 | Integer32 | read-only | Local alarm #2: See tag inside door =Optional alarm. External alarm input required |
| I32 seetag_cust_alm3 | 1.3.6.1.4.1.9839.2.1.1.58 | Integer32 | read-only | Local alarm #3: See tag inside door =Optional alarm. External alarm input required |
| I32 seetag_cust_alm4 | 1.3.6.1.4.1.9839.2.1.1.59 | Integer32 | read-only | Local alarm #4: See tag inside door =Optional alarm. External alarm input required |
| I32 shortcycle_alm_en | 1.3.6.1.4.1.9839.2.1.1.60 | Integer32 | read-only | Enable short cycle alarm of the compressors |
| I32 superv_off | 1.3.6.1.4.1.9839.2.1.1.61 | Integer32 | read-only | Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off; 0: On |
| I32 bms_heartbeat | 1.3.6.1.4.1.9839.2.1.1.62 | Integer32 | read-only | Bms heartbeat - pCO looks for update every 10 minutes |
| analogObjects | 1.3.6.1.4.1.9839.2.1.2 | | | |
| I32 ret_air_tmp | 1.3.6.1.4.1.9839.2.1.2.1 | Integer32 | read-only | Temperature of return air |
| I32 minmax_24hr_retair_maximum | 1.3.6.1.4.1.9839.2.1.2.2 | Integer32 | read-only | Maximum Return air temp in last 24hrs |
| I32 minmax_24hr_retair_minumum | 1.3.6.1.4.1.9839.2.1.2.3 | Integer32 | read-only | Minimum Return air temp in last 24hrs |
| I32 temp_setpoint | 1.3.6.1.4.1.9839.2.1.2.4 | Integer32 | read-write | Temperature setpoint |
| I32 temp_deadband | 1.3.6.1.4.1.9839.2.1.2.5 | Integer32 | read-write | Amount from setpoint before a comp is staged on |
| I32 humidity_ain_offs | 1.3.6.1.4.1.9839.2.1.2.6 | Integer32 | read-only | Humidity Sensor Calibration |
| I32 return_ain_offs | 1.3.6.1.4.1.9839.2.1.2.7 | Integer32 | read-only | Return Temperature Sensor Calibration |
| I32 cw_tmp | 1.3.6.1.4.1.9839.2.1.2.8 | Integer32 | read-only | Temperature of chilled water |
| I32 disch_air_tmp | 1.3.6.1.4.1.9839.2.1.2.9 | Integer32 | read-only | Temperature of discharge air |
| I32 discharge_ain_offs | 1.3.6.1.4.1.9839.2.1.2.10 | Integer32 | read-only | Discharge Temperature Sensor Calibration - Optional discharge air temperature sensor required (B9) |
| I32 cw_ain_offs | 1.3.6.1.4.1.9839.2.1.2.11 | Integer32 | read-only | Chilled Water Temperature Sensor Calibration - Optional chilled water temperature sensor required (B10) |
| I32 engsaver_setpoint | 1.3.6.1.4.1.9839.2.1.2.12 | Integer32 | read-write | Temperature setpoint where chilled water will is requested |
| I32 opt1_analog | 1.3.6.1.4.1.9839.2.1.2.13 | Integer32 | read-only | Value of the analog input |
| I32 opt2_analog | 1.3.6.1.4.1.9839.2.1.2.14 | Integer32 | read-only | Value of the analog input |
| I32 opt3_analog | 1.3.6.1.4.1.9839.2.1.2.15 | Integer32 | read-only | Value of the analog input |
| I32 opt4_analog | 1.3.6.1.4.1.9839.2.1.2.16 | Integer32 | read-only | Value of the analog input |
| I32 opt_sns_1_y1 | 1.3.6.1.4.1.9839.2.1.2.17 | Integer32 | read-only | Analog Sensor 1 Minimum Value |
| I32 opt_sns_1_y2 | 1.3.6.1.4.1.9839.2.1.2.18 | Integer32 | read-only | Analog Sensor 1 Maximum Value |
| I32 opt_sns_1_ain_offs | 1.3.6.1.4.1.9839.2.1.2.19 | Integer32 | read-only | Analog Sensor 1 Calibration |
| I32 opt_sns_2_y1 | 1.3.6.1.4.1.9839.2.1.2.20 | Integer32 | read-only | Analog Sensor 2 Minimum Value |
| I32 opt_sns_2_y2 | 1.3.6.1.4.1.9839.2.1.2.21 | Integer32 | read-only | Analog Sensor 2 Maximum Value |
| I32 opt_sns_2_ain_offs | 1.3.6.1.4.1.9839.2.1.2.22 | Integer32 | read-only | Analog Sensor 2 Calibration |
| I32 opt_sns_3_y1 | 1.3.6.1.4.1.9839.2.1.2.23 | Integer32 | read-only | Analog Sensor 3 Minimum Value |
| I32 opt_sns_3_y2 | 1.3.6.1.4.1.9839.2.1.2.24 | Integer32 | read-only | Analog Sensor 3 Maximum Value |
| I32 opt_sns_3_ain_offs | 1.3.6.1.4.1.9839.2.1.2.25 | Integer32 | read-only | Analog Sensor 3 Calibration |
| I32 opt_sns_4_y1 | 1.3.6.1.4.1.9839.2.1.2.26 | Integer32 | read-only | Analog Sensor 4 Minimum Value |
| I32 opt_sns_4_y2 | 1.3.6.1.4.1.9839.2.1.2.27 | Integer32 | read-only | Analog Sensor 4 Maximum Value |
| I32 opt_sns_4_ain_offs | 1.3.6.1.4.1.9839.2.1.2.28 | Integer32 | read-only | Analog Sensor 4 Calibration |
| integerObjects | 1.3.6.1.4.1.9839.2.1.3 | | | |
| I32 disch_air_lo_sp | 1.3.6.1.4.1.9839.2.1.3.1 | Integer32 | read-write | Lower Limit alarm of discharge air temp |
| I32 humidity_dis | 1.3.6.1.4.1.9839.2.1.3.2 | Integer32 | read-only | Relative humidity displayed as xx% |
| I32 stages_on | 1.3.6.1.4.1.9839.2.1.3.3 | Integer32 | read-only | Cooling Stages On, DX only |
| I32 heaters_on | 1.3.6.1.4.1.9839.2.1.3.4 | Integer32 | read-only | Number of heat stages running |
| I32 minmax_24hr_hum_maximum | 1.3.6.1.4.1.9839.2.1.3.5 | Integer32 | read-only | Maximum humidity in last 24hrs |
| I32 minmax_24hr_hum_minumum | 1.3.6.1.4.1.9839.2.1.3.6 | Integer32 | read-only | Minimum humidity in last 24hrs |
| I32 comp_duty | 1.3.6.1.4.1.9839.2.1.3.7 | Integer32 | read-only | Cooling Utilization Over Last Hour -Percentage of cooling is used in the last hour of operation; this point applies to DX unit. |
| I32 heat_duty | 1.3.6.1.4.1.9839.2.1.3.8 | Integer32 | read-only | Heating Utilization Over Last Hour -Percentage of heating is used in the last hour of operation |
| I32 hum_duty | 1.3.6.1.4.1.9839.2.1.3.9 | Integer32 | read-only | Humidifier Utilization Over Last Hour -Percentage of humidifier is used in the last hour of operation |
| I32 c1_hours_h | 1.3.6.1.4.1.9839.2.1.3.10 | Integer32 | read-only | Compressor 1 Runtime -This point applies to DX unit with one compressor -high |
| I32 c1_hours_l | 1.3.6.1.4.1.9839.2.1.3.11 | Integer32 | read-only | Compressor 1 Runtime -This point applies to DX unit with one compressor -low |
| I32 c2_hours_h | 1.3.6.1.4.1.9839.2.1.3.12 | Integer32 | read-only | Compressor 2 Runtime -This point applies to DX unit with dual compressor - high |
| I32 c2_hours_l | 1.3.6.1.4.1.9839.2.1.3.13 | Integer32 | read-only | Compressor 2 Runtime -This point applies to DX unit with dual compressor - low |
| I32 ht1_hours_h | 1.3.6.1.4.1.9839.2.1.3.14 | Integer32 | read-only | Heater 1 Runtime - high |
| I32 ht1_hours_l | 1.3.6.1.4.1.9839.2.1.3.15 | Integer32 | read-only | Heater 1 Runtime - low |
| I32 current_second | 1.3.6.1.4.1.9839.2.1.3.16 | Integer32 | read-only | Current second |
| I32 current_minute | 1.3.6.1.4.1.9839.2.1.3.17 | Integer32 | read-only | Current minute |
| I32 current_hour | 1.3.6.1.4.1.9839.2.1.3.18 | Integer32 | read-only | Current hour |
| I32 current_day | 1.3.6.1.4.1.9839.2.1.3.19 | Integer32 | read-only | Current day |
| I32 current_month | 1.3.6.1.4.1.9839.2.1.3.20 | Integer32 | read-only | Current month |
| I32 current_year | 1.3.6.1.4.1.9839.2.1.3.21 | Integer32 | read-only | Current year |
| I32 firestat_sp | 1.3.6.1.4.1.9839.2.1.3.22 | Integer32 | read-write | Alarm settting of return air temp to determine there is a fire |
| I32 hum_hi_sp | 1.3.6.1.4.1.9839.2.1.3.23 | Integer32 | read-write | Humidity upper limit alarm |
| I32 ret_air_hi_sp | 1.3.6.1.4.1.9839.2.1.3.24 | Integer32 | read-write | Upper limit alarm of return air temp |
| I32 hum_lo_sp | 1.3.6.1.4.1.9839.2.1.3.25 | Integer32 | read-write | Humidity lower limit alarm |
| I32 ret_air_lo_sp | 1.3.6.1.4.1.9839.2.1.3.26 | Integer32 | read-write | Lower limit alarm of return air temp |
| I32 hum_deadband | 1.3.6.1.4.1.9839.2.1.3.27 | Integer32 | read-write | amount hum must change from setpoint before acting |
| I32 hum_setpoint | 1.3.6.1.4.1.9839.2.1.3.28 | Integer32 | read-write | humidity setpoint |
| I32 start_dly | 1.3.6.1.4.1.9839.2.1.3.29 | Integer32 | read-write | Time before the system starts up |
| I32 alm1_del | 1.3.6.1.4.1.9839.2.1.3.30 | Integer32 | read-only | Optional Alarm 1 Delay |
| I32 alm2_del | 1.3.6.1.4.1.9839.2.1.3.31 | Integer32 | read-only | Optional Alarm 2 Delay |
| I32 alm3_del | 1.3.6.1.4.1.9839.2.1.3.32 | Integer32 | read-only | Optional Alarm 3 Delay |
| I32 alarm1_txt | 1.3.6.1.4.1.9839.2.1.3.33 | Integer32 | read-only | Message on optional alarm screen, some also add function |
| I32 alarm2_txt | 1.3.6.1.4.1.9839.2.1.3.34 | Integer32 | read-only | Message on optional alarm screen, some also add function |
| I32 alarm3_txt | 1.3.6.1.4.1.9839.2.1.3.35 | Integer32 | read-only | Message on optional alarm screen, some also add function |
| I32 alarm4_txt | 1.3.6.1.4.1.9839.2.1.3.36 | Integer32 | read-only | Message on optional alarm screen, some also add function |
| I32 comp_sel | 1.3.6.1.4.1.9839.2.1.3.37 | Integer32 | read-only | Comps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit |
| I32 dehum_mode | 1.3.6.1.4.1.9839.2.1.3.38 | Integer32 | read-only | 0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited, 4=twocomp unlimited |
| I32 reheat_sel | 1.3.6.1.4.1.9839.2.1.3.39 | Integer32 | read-only | Number of heat stages |
| I32 hum_sel | 1.3.6.1.4.1.9839.2.1.3.40 | Integer32 | read-only | 0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod |
| I32 alm_contact_msg | 1.3.6.1.4.1.9839.2.1.3.41 | Integer32 | read-only | Text displayed on all alarm screens |
| I32 powerup_sel | 1.3.6.1.4.1.9839.2.1.3.42 | Integer32 | read-only | 0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm |
| I32 buzzer_select | 1.3.6.1.4.1.9839.2.1.3.43 | Integer32 | read-only | 0=None, 1=short beeps, 2=long beep, 3=Constant |
| I32 cw_disp | 1.3.6.1.4.1.9839.2.1.3.44 | Integer32 | read-only | % of 10volts of analog output #1 |
| I32 wtrvlv_duty | 1.3.6.1.4.1.9839.2.1.3.45 | Integer32 | read-only | Chilled Water Utilization Over Last Hour - This applies to Chilled water or Energy saver units. |
| I32 hum_hours_h | 1.3.6.1.4.1.9839.2.1.3.46 | Integer32 | read-only | Humidifier Runtime - high |
| I32 hum_hours_l | 1.3.6.1.4.1.9839.2.1.3.47 | Integer32 | read-only | Humidifier Runtime - low |
| I32 blower_hours_h | 1.3.6.1.4.1.9839.2.1.3.48 | Integer32 | read-only | Blower Runtime - high |
| I32 blower_hours_l | 1.3.6.1.4.1.9839.2.1.3.49 | Integer32 | read-only | Blower Runtime - low |
| I32 alm4_del | 1.3.6.1.4.1.9839.2.1.3.50 | Integer32 | read-only | Optional Alarm 4 Delay |
| I32 assist_sel | 1.3.6.1.4.1.9839.2.1.3.51 | Integer32 | read-only | 0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4... |
| I32 wtrvlv_sel | 1.3.6.1.4.1.9839.2.1.3.52 | Integer32 | read-only | Water valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg |
| I32 wtrvlv_volts_sel | 1.3.6.1.4.1.9839.2.1.3.53 | Integer32 | read-only | Water valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7 |
| I32 hum_volts | 1.3.6.1.4.1.9839.2.1.3.54 | Integer32 | read-only | % of 10volts of analog output #2 |
| I32 dehum_hours_h | 1.3.6.1.4.1.9839.2.1.3.55 | Integer32 | read-only | Dehumidifier Runtime - High |
| I32 dehum_hours_l | 1.3.6.1.4.1.9839.2.1.3.56 | Integer32 | read-only | Dehumidifier Runtime - Low |
| I32 autoflush_dly | 1.3.6.1.4.1.9839.2.1.3.58 | Integer32 | read-only | Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None |
| I32 y4_out | 1.3.6.1.4.1.9839.2.1.3.59 | Integer32 | read-only | Value sent to optional analog output#1 |
| I32 y5_out | 1.3.6.1.4.1.9839.2.1.3.60 | Integer32 | read-only | Value sent to optional analog output#2 |
| I32 air_flow | 1.3.6.1.4.1.9839.2.1.3.61 | Integer32 | read-only | Current Fan Airflow - Based on calculated Pressure Diff formula |
| I32 opt_snsr1_name | 1.3.6.1.4.1.9839.2.1.3.62 | Integer32 | read-only | Name of the sensor |
| I32 opt_sns_1_ain_type | 1.3.6.1.4.1.9839.2.1.3.63 | Integer32 | read-only | Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| I32 opt_snsr2_name | 1.3.6.1.4.1.9839.2.1.3.64 | Integer32 | read-only | Name of the sensor |
| I32 opt_sns_2_ain_type | 1.3.6.1.4.1.9839.2.1.3.65 | Integer32 | read-only | Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| I32 opt_snsr3_name | 1.3.6.1.4.1.9839.2.1.3.66 | Integer32 | read-only | Name of the sensor |
| I32 opt_sns_3_ain_type | 1.3.6.1.4.1.9839.2.1.3.67 | Integer32 | read-only | Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| I32 opt_snsr4_name | 1.3.6.1.4.1.9839.2.1.3.68 | Integer32 | read-only | Name of the sensor |
| I32 opt_sns_4_ain_type | 1.3.6.1.4.1.9839.2.1.3.69 | Integer32 | read-only | Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170} |
| I32 cw_fan_speed_bms | 1.3.6.1.4.1.9839.2.1.3.70 | Integer32 | read-write | CW Fan speed (%) sent via BMS |
| I32 dx_fan_speed_bms | 1.3.6.1.4.1.9839.2.1.3.71 | Integer32 | read-write | DX Fan speed (%) sent via BMS |
| I32 fan_speed_max | 1.3.6.1.4.1.9839.2.1.3.72 | Integer32 | read-write | Maximum Fan speed (% of output) modulation. |
| I32 fan_speed_min | 1.3.6.1.4.1.9839.2.1.3.73 | Integer32 | read-write | Minimum Fan speed (% of output) modulation from pressure. |
| I32 fan_pr_sp | 1.3.6.1.4.1.9839.2.1.3.74 | Integer32 | read-write | Fan pressure setpoint (0.01 inches of water) |
| I32 fan_pr_band | 1.3.6.1.4.1.9839.2.1.3.75 | Integer32 | read-write | Fan pressure band (0.01 inches of water) |
| I32 fan_af_max | 1.3.6.1.4.1.9839.2.1.3.76 | Integer32 | read-write | Maximum air flow limit of setpoint from BMS or valve modulation. |
| I32 fan_af_min | 1.3.6.1.4.1.9839.2.1.3.77 | Integer32 | read-write | Minimum air flow limit of setpoint from BMS or valve modulation. |
| I32 fan_kfactor | 1.3.6.1.4.1.9839.2.1.3.78 | Integer32 | read-write | Fan K Factor |
| I32 num_fans | 1.3.6.1.4.1.9839.2.1.3.79 | Integer32 | read-write | Number of fans installed in this unit |
| I32 ht2_hours_h | 1.3.6.1.4.1.9839.2.1.3.81 | Integer32 | read-only | Heater 2 Runtime - high |
| I32 ht2_hours_l | 1.3.6.1.4.1.9839.2.1.3.82 | Integer32 | read-only | Heater 2 Runtime - low |
| I32 ht3_hours_h | 1.3.6.1.4.1.9839.2.1.3.83 | Integer32 | read-only | Heater 3 Runtime - high |
| I32 ht3_hours_l | 1.3.6.1.4.1.9839.2.1.3.84 | Integer32 | read-only | Heater 3 Runtime - low |
| I32 engy_hours_h | 1.3.6.1.4.1.9839.2.1.3.85 | Integer32 | read-only | Energy Saver Runtime - This optional point applies to energy saver units only -high |
| I32 engy_hours_l | 1.3.6.1.4.1.9839.2.1.3.86 | Integer32 | read-only | Energy Saver Runtime - This optional point applies to energy saver units only - low |
| I32 cw_hours_h | 1.3.6.1.4.1.9839.2.1.3.87 | Integer32 | read-only | Chilled Water Runtime - This applies to chilled water units only - high |
| I32 cw_hours_l | 1.3.6.1.4.1.9839.2.1.3.88 | Integer32 | read-only | Chilled Water Runtime - This applies to chilled water units only - low |
| I32 c3_hours_h | 1.3.6.1.4.1.9839.2.1.3.89 | Integer32 | read-only | Compressor 3 Runtime - This applies when unit has four stages tandem compressors - high |
| I32 c3_hours_l | 1.3.6.1.4.1.9839.2.1.3.90 | Integer32 | read-only | Compressor 3 Runtime - This applies when unit has four stages tandem compressors - low |
| I32 c4_hours_l | 1.3.6.1.4.1.9839.2.1.3.91 | Integer32 | read-only | Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - high |
| I32 c4_hours_h | 1.3.6.1.4.1.9839.2.1.3.92 | Integer32 | read-only | Compressor 4 Runtime - This applies when unit has four stages tandem compressors. - low |
| I32 cond_hours_h | 1.3.6.1.4.1.9839.2.1.3.93 | Integer32 | read-only | Condenser Runtime - high |
| I32 cond_hours_l | 1.3.6.1.4.1.9839.2.1.3.94 | Integer32 | read-only | Condenser Runtime - low |
| I32 dx_fan_speed | 1.3.6.1.4.1.9839.2.1.3.95 | Integer32 | read-only | Fan speed (% of output) when compressor cooling. |
| I32 cw_fan_speed | 1.3.6.1.4.1.9839.2.1.3.96 | Integer32 | read-only | Fan speed (% of output) when cold water cooling. |
| I32 fan_af_dx_sp | 1.3.6.1.4.1.9839.2.1.3.97 | Integer32 | read-only | Fan air flow setpoint for DX unit (cfm) |
| I32 fan_af_cw_sp | 1.3.6.1.4.1.9839.2.1.3.98 | Integer32 | read-only | Fan air flow setpoint for CW unit (cfm) |
| I32 zm_airflow_sp | 1.3.6.1.4.1.9839.2.1.3.99 | Integer32 | read-write | Zone Airflow Setpoint kcfm |