All MIBs › DELL-SNMP-UPS-MIB
Category: Vendor: Dell
Description: Manages Dell UPS power configuration, battery status, and alarm notifications.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is DELL-SNMP-UPS-MIB?
DELL-SNMP-UPS-MIB is a Dell proprietary MIB (enterprise OID 674, based on the shared Eaton/MGE-derived UPS management framework) reporting status on Dell-branded UPS devices. Its objects cover product identification (display name, description, vendor, version, build number, URL, network name), a global status object with timestamp/timeout/refresh-rate settings and a trap-generation flag, physical identification (family name, serial number, converter type, reference number), and output power metrics — instant/peak headroom (with peak timestamp), peak/present/cumulative consumption (with timestamps). As a hardware-status MIB it lets an administrator watch a Dell UPS's global status and output power consumption trend. It is deployed on Dell-branded UPS devices. Engineers can download the DELL-SNMP-UPS-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in DELL-SNMP-UPS-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Dell-branded UPS devices
Monitoring Examples
A facilities team monitors productStatusGlobalStatus alongside physicalOutputPresentConsumption to catch a Dell UPS reporting a degraded status or unexpected load increase.
What Can Be Monitored
- UPS global status and output power consumption
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| enterprises |
From SNMPv2-TC
| DisplayString | |
| TimeStamp |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| dell | 1.3.6.1.4.1.674 | |||
| upsdell | 1.3.6.1.4.1.674.10902 | |||
| hardware | 1.3.6.1.4.1.674.10902.2 | |||
| productID | 1.3.6.1.4.1.674.10902.2.100 | |||
| STR productIDDisplayName | 1.3.6.1.4.1.674.10902.2.100.1 | DisplayString | read-only | Name of this product for display purposes. |
| STR productIDDescription | 1.3.6.1.4.1.674.10902.2.100.2 | DisplayString | read-only | A short description of this product. |
| STR productIDVendor | 1.3.6.1.4.1.674.10902.2.100.3 | DisplayString | read-only | The name of the product manufacturer. |
| STR productIDVersion | 1.3.6.1.4.1.674.10902.2.100.4 | DisplayString | read-only | The version of this product. |
| STR productIDBuildNumber | 1.3.6.1.4.1.674.10902.2.100.5 | DisplayString | read-only | The software build number of the product populating the MIB. |
| STR productIDURL | 1.3.6.1.4.1.674.10902.2.100.6 | DisplayString | read-only | The URL of the web-based application to manage this device, should the device provide one. |
| STR productIDDeviceNetworkName | 1.3.6.1.4.1.674.10902.2.100.7 | DisplayString | read-only | Operating system specific computer name if product SNMP service is hosted. |
| productStatus | 1.3.6.1.4.1.674.10902.2.110 | |||
| INT productStatusGlobalStatus | 1.3.6.1.4.1.674.10902.2.110.1 | INTEGER | read-only | Current status of the product. This is a rollup for the entire product including any monitored devices. The status is intended to give initiative to an SNMP monitor to get further data when this status is abnormal. |
| INT productStatusLastGlobalStatus | 1.3.6.1.4.1.674.10902.2.110.2 | INTEGER | read-only | The status before the current status which induced an initiative to issue a global status change trap. |
| TIM productStatusTimeStamp | 1.3.6.1.4.1.674.10902.2.110.3 | TimeStamp | read-only | The last time that the SNMP table geometries changed and/or attribute data was significantly updated. This is to be used by management applications to trigger a refresh of data acquired from the MIB. |
| INT productStatusGetTimeOut | 1.3.6.1.4.1.674.10902.2.110.4 | INTEGER | read-only | Suggested time out value in milliseconds for how long the SNMP getter should wait while attempting to poll the product SNMP service. |
| INT productStatusRefreshRate | 1.3.6.1.4.1.674.10902.2.110.5 | INTEGER | read-only | Rate in seconds at which the SNMP service cached data is being updated. |
| INT productStatusGeneratingTrapFlag | 1.3.6.1.4.1.674.10902.2.110.6 | INTEGER | read-only | Indicates if this SNMP sub-agent is capable of and/or is generating SNMP Traps. This variable can take the following values: 1 True, this service is capable of sending traps and is the originator of SNMP traps generated for the devices represented in this MIB and is currently generating traps. 2 False, this service not capable of sending traps and is not the originator of any SNMP traps generated for the devices represented in this MIB. 3 Disabled, this service is capable of sending traps and is the originator of SNMP traps for the devices represented in this MIB, but traps are currently disabled. |
| physical | 1.3.6.1.4.1.674.10902.2.120 | |||
| physicalIdent | 1.3.6.1.4.1.674.10902.2.120.1 | |||
| STR physicalIdentFamilyName | 1.3.6.1.4.1.674.10902.2.120.1.1 | DisplayString | read-only | UPS Family name. |
| STR physicalIdentSerialNumber | 1.3.6.1.4.1.674.10902.2.120.1.2 | DisplayString | read-only | UPS Serial number. |
| INT physicalIdentConverterType | 1.3.6.1.4.1.674.10902.2.120.1.3 | INTEGER | read-only | UPS type. |
| STR physicalIdentReferenceNumber | 1.3.6.1.4.1.674.10902.2.120.1.4 | DisplayString | read-only | Technical Reference of UPS firmware. |
| physicalOutput | 1.3.6.1.4.1.674.10902.2.120.2 | |||
| INT physicalOutputInstantHeadroom | 1.3.6.1.4.1.674.10902.2.120.2.1 | INTEGER | read-only | This is the present amount of watt capacity remaining before overload. |
| INT physicalOutputPeakHeadroom | 1.3.6.1.4.1.674.10902.2.120.2.2 | INTEGER | read-only | Statistical value holding the lowest value that Instantaneous Headroom Watts was ever set too since the last time this statistic was reset. |
| TIM physicalOutputPeakHeadroomTimestamp | 1.3.6.1.4.1.674.10902.2.120.2.3 | TimeStamp | read-only | Time and date stamp of the last time the Peak Headroom Watts value was updated. |
| INT physicalOutputPeakConsumption | 1.3.6.1.4.1.674.10902.2.120.2.4 | INTEGER | read-only | Statistical value of the maximum RMS Watts the UPS has seen since the last time this statistic was reset. |
| TIM physicalOutputPeakConsumptionTimestamp | 1.3.6.1.4.1.674.10902.2.120.2.5 | TimeStamp | read-only | Time and date stamp of the last time the Peak Consumption Watts value was updated. |
| INT physicalOutputPresentConsumption | 1.3.6.1.4.1.674.10902.2.120.2.6 | INTEGER | read-only | Derived by averaging the watt second consumption over the past hour. Use an array of 60 words to store the average watt seconds consumed over the last minute then after you have a full hours worth of data in the 60 word array, average those values to get your Present KWH Consumption meter. Then every minute after that update the oldest value in the array, average again and update the meter. Value is 0 until the minimum 1 hour of data has been accumulated. |
| INT physicalOutputCumulativeConsumption | 1.3.6.1.4.1.674.10902.2.120.2.7 | INTEGER | read-only | 64 bit meter value that is derived by reading the Present KWH Consumption meter once per hour and adding it to the last value of this meter. Value accumulates until it is reset from the LCD or via the SHUT protocol or the meter rolls over. |
| TIM physicalOutputCumulativeConsumptionTimestamp | 1.3.6.1.4.1.674.10902.2.120.2.8 | TimeStamp | read-only | Time and date stamp of last time this meter value was reset. |
| INT physicalOutputVA | 1.3.6.1.4.1.674.10902.2.120.2.9 | INTEGER | read-only | Output VA. |
| physicalRectifier | 1.3.6.1.4.1.674.10902.2.120.3 | |||
| INT physicalRectifierPosVoltage | 1.3.6.1.4.1.674.10902.2.120.3.1 | INTEGER | read-only | DC bus positive voltage. |
| INT physicalRectifierNegVoltage | 1.3.6.1.4.1.674.10902.2.120.3.2 | INTEGER | read-only | DC bus negative voltage. |
| physicalUPS | 1.3.6.1.4.1.674.10902.2.120.4 | |||
| TIM physicalUPSDateTime | 1.3.6.1.4.1.674.10902.2.120.4.1 | TimeStamp | read-only | Real Time Clock with Date and Time. |
| STR physicalUPSAlarmsStatus | 1.3.6.1.4.1.674.10902.2.120.4.2 | DisplayString | read-only | List of traps that are in active mode. This list is coded in ASCI format and each trap number is separated by a coma (ex: 1,5,23,77). Only odd traps are listed. |
| INT physicalUPSRuntimeToShutdown | 1.3.6.1.4.1.674.10902.2.120.4.3 | INTEGER | read-only | Number of seconds remaining until UPS will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect. |
| INT physicalUPSOutpoutSwitchable | 1.3.6.1.4.1.674.10902.2.120.4.4 | INTEGER | read-only | Parameter to enable or not remote UPS commands coming from all communication ports. |
| physicalBattery | 1.3.6.1.4.1.674.10902.2.120.5 | |||
| INT physicalBatteryABMStatus | 1.3.6.1.4.1.674.10902.2.120.5.1 | INTEGER | read-only | Advanced Battery Monitoring satus. |
| INT physicalBatteryTestStatus | 1.3.6.1.4.1.674.10902.2.120.5.2 | INTEGER | read-only | Battery test satus. |
| INT physicalBatterySecondsRemaining | 1.3.6.1.4.1.674.10902.2.120.5.3 | INTEGER | read-only | Battery remaining time calculated by the autonometer. |
| physicalLoadSegment | 1.3.6.1.4.1.674.10902.2.120.6 | |||
| INT physicalLoadSegment1ShutdownAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.1 | INTEGER | read-only | Number of seconds remaining until load segment 1 will switch off. -1 if no shutdown countdown is in effect. |
| INT physicalLoadSegment1StartupAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.2 | INTEGER | read-only | Number of seconds remaining until load segment 1 will switch on. -1 if no startup countdown is in effect. |
| INT physicalLoadSegment2ShutdownAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.3 | INTEGER | read-only | Number of seconds remaining until load segment 2 will switch off. -1 if no shutdown countdown is in effect. |
| INT physicalLoadSegment2StartupAfterDelay | 1.3.6.1.4.1.674.10902.2.120.6.4 | INTEGER | read-only | Number of seconds remaining until load segment 2 will switch on. -1 if no startup countdown is in effect. |
| INT physicalLoadSegment1RuntimeToShutdown | 1.3.6.1.4.1.674.10902.2.120.6.5 | INTEGER | read-only | Number of seconds remaining until load segment 1 will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect. |
| INT physicalLoadSegment2RuntimeToShutdown | 1.3.6.1.4.1.674.10902.2.120.6.6 | INTEGER | read-only | Number of seconds remaining until load segment 2 will receive a ShutdownAfterDelay command. 2147483647 if no countdown is in effect. |
| physicalEnvironment | 1.3.6.1.4.1.674.10902.2.120.7 | |||
| INT physicalEnvironmentSensorPresent | 1.3.6.1.4.1.674.10902.2.120.7.1 | INTEGER | read-only | Informations, if there is Environment Measurement Probe connected. |
| STR physicalEnvironmentSensorName | 1.3.6.1.4.1.674.10902.2.120.7.2 | DisplayString | read-only | User name of EMP. |
| physicalEnvironmentValues | 1.3.6.1.4.1.674.10902.2.120.7.3 | |||
| INT physicalEnvironmentValuesTemperatureUnit | 1.3.6.1.4.1.674.10902.2.120.7.3.1 | INTEGER | read-only | Temperature unit setting. |
| INT physicalEnvironmentValuesTemperature | 1.3.6.1.4.1.674.10902.2.120.7.3.2 | INTEGER | read-only | Current temperature value in 0.1 degree Celsius. |
| INT physicalEnvironmentValuesHumidity | 1.3.6.1.4.1.674.10902.2.120.7.3.3 | INTEGER | read-only | Current humidity value in 0.1 percents. |
| INT physicalEnvironmentValuesTemperatureLow | 1.3.6.1.4.1.674.10902.2.120.7.3.4 | INTEGER | read-only | Temperature low threshhold in units of degree Celsius. |
| INT physicalEnvironmentValuesTemperatureHigh | 1.3.6.1.4.1.674.10902.2.120.7.3.5 | INTEGER | read-only | Temperature high threshhold in units of degree Celsius. |
| INT physicalEnvironmentValuesTemperatureHysteresis | 1.3.6.1.4.1.674.10902.2.120.7.3.6 | INTEGER | read-only | Temperature hysteresis in units of degree Celsius. |
| INT physicalEnvironmentValueshHumidityLow | 1.3.6.1.4.1.674.10902.2.120.7.3.7 | INTEGER | read-only | Humidity low threshhold in percents. |
| INT physicalEnvironmentValuesHumidityHigh | 1.3.6.1.4.1.674.10902.2.120.7.3.8 | INTEGER | read-only | Humidity high threshhold in percents. |
| INT physicalEnvironmentValuesHumidityHysteresis | 1.3.6.1.4.1.674.10902.2.120.7.3.9 | INTEGER | read-only | Humidity hysteresis in percents. |
| physicalEnvironmentInputTable | 1.3.6.1.4.1.674.10902.2.120.7.4 | not-accessible | The table containins dry contact inputs information. | |
| physicalEnvironmentInputEntry | 1.3.6.1.4.1.674.10902.2.120.7.4.1 | not-accessible | The description of an entry in the table. | |
| INT physicalEnvironmentInputIndex | 1.3.6.1.4.1.674.10902.2.120.7.4.1.1 | INTEGER | read-only | The input index, ranging from 1 to 2. |
| STR physicalEnvironmentInputName | 1.3.6.1.4.1.674.10902.2.120.7.4.1.2 | DisplayString | read-only | The input user-friendly name. |
| INT physicalEnvironmentInputState | 1.3.6.1.4.1.674.10902.2.120.7.4.1.3 | INTEGER | read-only | Current state of input. |
| STR physicalEnvironmentInputOpenedState | 1.3.6.1.4.1.674.10902.2.120.7.4.1.4 | DisplayString | read-only | The input opened state user-friendly name. |
| STR physicalEnvironmentInputClosedState | 1.3.6.1.4.1.674.10902.2.120.7.4.1.5 | DisplayString | read-only | The input closed state user-friendly name. |
| logical | 1.3.6.1.4.1.674.10902.2.130 | |||
| traps | 1.3.6.1.4.1.674.10902.2.140 | |||
| NTF trapInverterOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.1 | Inverter AC over voltage. | ||
| NTF trapInverterOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.2 | Inverter AC over voltage ok. | ||
| NTF trapInverterUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.3 | Inverter AC under voltage. | ||
| NTF trapInverterUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.4 | Inverter AC under voltage ok. | ||
| NTF trapBypassFrequencyOutOfRange | 1.3.6.1.4.1.674.10902.2.140.0.5 | Bypass under or over frequency. | ||
| NTF trapBypassFrequencyOutOfRangeOk | 1.3.6.1.4.1.674.10902.2.140.0.6 | Bypass under or over frequency ok. | ||
| NTF trapOnBuck | 1.3.6.1.4.1.674.10902.2.140.0.7 | On Buck / Input Voltage Reducer. | ||
| NTF trapReturnFromBuck | 1.3.6.1.4.1.674.10902.2.140.0.8 | Return from Buck. | ||
| NTF trapOnBoost | 1.3.6.1.4.1.674.10902.2.140.0.9 | On Boost / Input Voltage Booster. | ||
| NTF trapReturnFromBoost | 1.3.6.1.4.1.674.10902.2.140.0.10 | Return from Boost. | ||
| NTF trapInputOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.11 | Input AC over voltage. | ||
| NTF trapInputOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.12 | Input AC over voltage ok. | ||
| NTF trapInputUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.13 | Input AC under voltage. | ||
| NTF trapInputUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.14 | Input AC under voltage ok. | ||
| NTF trapInputFrequencyOutOfRange | 1.3.6.1.4.1.674.10902.2.140.0.15 | Input under or over frequency. | ||
| NTF trapInputFrequencyOutOfRangeOk | 1.3.6.1.4.1.674.10902.2.140.0.16 | Input under or over frequency ok. | ||
| NTF trapRemoteEmergencyPowerOff | 1.3.6.1.4.1.674.10902.2.140.0.17 | Remote emergency power off. | ||
| NTF trapReturnFromEmergencyPowerOff | 1.3.6.1.4.1.674.10902.2.140.0.18 | Return from remote emergency power off. | ||
| NTF trapLevel1Overload | 1.3.6.1.4.1.674.10902.2.140.0.19 | Output Level 1 overload. | ||
| NTF trapLevel1OverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.20 | Output Level 1 overload ok. | ||
| NTF trapLevel2Overload | 1.3.6.1.4.1.674.10902.2.140.0.21 | Level 2 overload. | ||
| NTF trapLevel2OverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.22 | Level 2 overload ok. | ||
| NTF trapLevel3Overload | 1.3.6.1.4.1.674.10902.2.140.0.23 | Level 3 overload. | ||
| NTF trapLevel3OverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.24 | Level 3 overload ok. | ||
| NTF trapPosDCLinkOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.25 | Positive DC link over voltage. | ||
| NTF trapPosDCLinkOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.26 | Positive DC link over voltage ok. | ||
| NTF trapPosDCLinkUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.27 | Positive DC link under voltage. | ||
| NTF trapPosDCLinkUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.28 | Positive DC link under voltage ok. | ||
| NTF trapNegDCLinkOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.29 | Negative DC link over voltage. | ||
| NTF trapNegDCLinkOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.30 | Negative DC link over voltage ok. | ||
| NTF trapNegDCLinkUnderVoltage | 1.3.6.1.4.1.674.10902.2.140.0.31 | Negative DC link under voltage. | ||
| NTF trapNegDCLinkUnderVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.32 | Negative DC link under voltage ok. | ||
| NTF trapRectifierFault | 1.3.6.1.4.1.674.10902.2.140.0.33 | Rectifier fault. | ||
| NTF trapRectifierOk | 1.3.6.1.4.1.674.10902.2.140.0.34 | Rectifier ok. | ||
| NTF trapInverterFault | 1.3.6.1.4.1.674.10902.2.140.0.35 | Inverter fault. | ||
| NTF trapInverterOk | 1.3.6.1.4.1.674.10902.2.140.0.36 | Inverter ok. | ||
| NTF trapChargerFailure | 1.3.6.1.4.1.674.10902.2.140.0.37 | Charger failure. | ||
| NTF trapChargerOk | 1.3.6.1.4.1.674.10902.2.140.0.38 | Charger ok. | ||
| NTF trapEepromFailure | 1.3.6.1.4.1.674.10902.2.140.0.39 | EEPROM failure. | ||
| NTF trapEepromOk | 1.3.6.1.4.1.674.10902.2.140.0.40 | EEPROM off. | ||
| NTF trapShutdownImminent | 1.3.6.1.4.1.674.10902.2.140.0.41 | Shutdown imminent. | ||
| NTF trapShutdownImminentOver | 1.3.6.1.4.1.674.10902.2.140.0.42 | Shutdown imminent over. | ||
| NTF trapBatteryLow | 1.3.6.1.4.1.674.10902.2.140.0.43 | Battery low. | ||
| NTF trapBatteryOk | 1.3.6.1.4.1.674.10902.2.140.0.44 | Battery ok. | ||
| NTF trapOutputShortCircuit | 1.3.6.1.4.1.674.10902.2.140.0.45 | Output short circuit. | ||
| NTF trapOutputReturnFromShortCircuit | 1.3.6.1.4.1.674.10902.2.140.0.46 | Output return from short circuit. | ||
| NTF trapUtilityNotPresent | 1.3.6.1.4.1.674.10902.2.140.0.47 | Utility not present. | ||
| NTF trapUtilityPresent | 1.3.6.1.4.1.674.10902.2.140.0.48 | Utility present. | ||
| NTF trapBatteryOverVoltage | 1.3.6.1.4.1.674.10902.2.140.0.49 | Battery DC over voltage. | ||
| NTF trapBatteryOverVoltageOk | 1.3.6.1.4.1.674.10902.2.140.0.50 | Battery DC over voltage ok. | ||
| NTF trapHeatsinkOvertemperature | 1.3.6.1.4.1.674.10902.2.140.0.51 | Heatsink overtemperature. | ||
| NTF trapHeatsinkOvertemperatureOk | 1.3.6.1.4.1.674.10902.2.140.0.52 | Heatsink overtemperature ok. | ||
| NTF trapBypassNotAvailable | 1.3.6.1.4.1.674.10902.2.140.0.53 | Bypass not available. | ||
| NTF trapBypassNotAvailableOk | 1.3.6.1.4.1.674.10902.2.140.0.54 | Bypass not available ok. | ||
| NTF trapOnManualBypass | 1.3.6.1.4.1.674.10902.2.140.0.55 | On manual/ maintenance bypass. | ||
| NTF trapUPSOnBattery | 1.3.6.1.4.1.674.10902.2.140.0.57 | UPS on battery. | ||
| NTF trapUPSReturnFromBattery | 1.3.6.1.4.1.674.10902.2.140.0.58 | UPS return from battery. | ||
| NTF trapUPSOnBypass | 1.3.6.1.4.1.674.10902.2.140.0.59 | UPS on bypass. | ||
| NTF trapUPSReturnFromBypass | 1.3.6.1.4.1.674.10902.2.140.0.60 | UPS return from bypass. | ||
| NTF trapBatteryTestInProgress | 1.3.6.1.4.1.674.10902.2.140.0.61 | Battery manual or automatic test in progress. | ||
| NTF trapBatteryTestDone | 1.3.6.1.4.1.674.10902.2.140.0.62 | Battery test done. | ||
| NTF trapBatteryNeedReplacement | 1.3.6.1.4.1.674.10902.2.140.0.63 | Battery test failed, battery needs to be replaced. | ||
| NTF trapBatteryReplacementDone | 1.3.6.1.4.1.674.10902.2.140.0.64 | Battery replacement done. | ||
| NTF trapFanFailure | 1.3.6.1.4.1.674.10902.2.140.0.65 | Fan failure. | ||
| NTF trapFanOk | 1.3.6.1.4.1.674.10902.2.140.0.66 | Fan ok. | ||
| NTF trapSiteWiringFault | 1.3.6.1.4.1.674.10902.2.140.0.67 | Site wiring fault. | ||
| NTF trapSiteWiringOk | 1.3.6.1.4.1.674.10902.2.140.0.68 | Site wiring ok. | ||
| NTF trapBatteryDisconnected | 1.3.6.1.4.1.674.10902.2.140.0.69 | Batteries disconnected. | ||
| NTF trapBatteryConnected | 1.3.6.1.4.1.674.10902.2.140.0.70 | Batteries connected. | ||
| NTF trapUPSOff | 1.3.6.1.4.1.674.10902.2.140.0.71 | UPS off. | ||
| NTF trapUPSOn | 1.3.6.1.4.1.674.10902.2.140.0.72 | UPS on. | ||
| NTF trapDCLinkImbalance | 1.3.6.1.4.1.674.10902.2.140.0.73 | DC link imbalance. | ||
| NTF trapDCLinkImbalanceOk | 1.3.6.1.4.1.674.10902.2.140.0.74 | DC link imbalance ok. | ||
| NTF trapABMOn | 1.3.6.1.4.1.674.10902.2.140.0.79 | ABM state on. | ||
| NTF trapABMOff | 1.3.6.1.4.1.674.10902.2.140.0.80 | ABM state off. | ||
| NTF trapLoadSegment1Off | 1.3.6.1.4.1.674.10902.2.140.0.81 | Load segment 1 off. | ||
| NTF trapLoadSegment1On | 1.3.6.1.4.1.674.10902.2.140.0.82 | Load segment 1 on. | ||
| NTF trapLoadSegment2Off | 1.3.6.1.4.1.674.10902.2.140.0.83 | Load segment 2 off. | ||
| NTF trapLoadSegment2On | 1.3.6.1.4.1.674.10902.2.140.0.84 | Load segment 2 on. | ||
| NTF trapInHighEfficiencyMode | 1.3.6.1.4.1.674.10902.2.140.0.85 | In High Efficiency mode. | ||
| NTF trapReturnFromHighEfficiencyMode | 1.3.6.1.4.1.674.10902.2.140.0.86 | Return from High Efficiency mode. | ||
| NTF trapRectifierOverload | 1.3.6.1.4.1.674.10902.2.140.0.87 | Rectifier input over current. | ||
| NTF trapRectifierOverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.88 | Rectifier current ok. | ||
| NTF trapInverterOverload | 1.3.6.1.4.1.674.10902.2.140.0.89 | Inverter output over current. | ||
| NTF trapInverterOverloadOk | 1.3.6.1.4.1.674.10902.2.140.0.90 | Inverter output current ok. | ||
| NTF trapBypassVoltageOutOfRange | 1.3.6.1.4.1.674.10902.2.140.0.91 | Bypass AC under or over voltage. | ||
| NTF trapBypassVoltageOutOfRangeOk | 1.3.6.1.4.1.674.10902.2.140.0.92 | Bypass AC under or over voltage ok. | ||
| NTF trapServiceBattery | 1.3.6.1.4.1.674.10902.2.140.0.93 | Service battery. | ||
| NTF trapToBypassCommand | 1.3.6.1.4.1.674.10902.2.140.0.94 | UPS received command to switch on bypass. | ||
| NTF trapFromBypassCommand | 1.3.6.1.4.1.674.10902.2.140.0.95 | UPS received command to switch on inverter. | ||
| NTF trapCommunicationLost | 1.3.6.1.4.1.674.10902.2.140.0.96 | Lost communication with UPS, HID databasis is not updated. | ||
| NTF trapCommunicationRestored | 1.3.6.1.4.1.674.10902.2.140.0.97 | Communication restored with UPS, HID databasis is updated. | ||
| NTF trapEnvironComFailure | 1.3.6.1.4.1.674.10902.2.140.0.98 | Environment Probe communication failure. | ||
| NTF trapEnvironComOK | 1.3.6.1.4.1.674.10902.2.140.0.99 | Environment Probe communication restored. | ||
| NTF trapEnvironTemperatureLow | 1.3.6.1.4.1.674.10902.2.140.0.100 | Temperature is below low threshold. | ||
| NTF trapEnvironTemperatureHigh | 1.3.6.1.4.1.674.10902.2.140.0.102 | Temperature is above high threshold. | ||
| NTF trapEnvironTemperatureOK | 1.3.6.1.4.1.674.10902.2.140.0.103 | Temperature is in normal range. | ||
| NTF trapEnvironHumidityLow | 1.3.6.1.4.1.674.10902.2.140.0.104 | Humidity is below low threshold. | ||
| NTF trapEnvironHumidityHigh | 1.3.6.1.4.1.674.10902.2.140.0.106 | Humidity is above high threshold. | ||
| NTF trapEnvironHumidityOK | 1.3.6.1.4.1.674.10902.2.140.0.107 | Humidity is in normal range. | ||
| NTF trapEnvironInput1Closed | 1.3.6.1.4.1.674.10902.2.140.0.108 | Input #1 is Closed. | ||
| NTF trapEnvironInput1Open | 1.3.6.1.4.1.674.10902.2.140.0.109 | Input #1 is Open. | ||
| NTF trapEnvironInput2Closed | 1.3.6.1.4.1.674.10902.2.140.0.110 | Input #2 is Closed. | ||
| NTF trapEnvironInput2Open | 1.3.6.1.4.1.674.10902.2.140.0.111 | Input #2 is Open. |
RFC description
Dell/Eaton UPS (Uninterruptible Power Supply) MIB for monitoring UPS hardware components, battery status, load, and environmental conditions.
Start monitoring Dell-branded UPS device with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.