| OID symbolic | OID numeric | Type | Access | Description |
| INT alarmEnableLeak | 1.3.6.1.4.1.39829.1.7.210 | INTEGER | read-write | Enable leak detection. |
| INT alarmEnableLevel | 1.3.6.1.4.1.39829.1.7.211 | INTEGER | read-write | Enable low liquid level. |
| INT alarmMaxEnableFi | 1.3.6.1.4.1.39829.1.7.161 | INTEGER | read-write | Enable Facility In Max Alarm level. |
| INT alarmMaxEnableFlow | 1.3.6.1.4.1.39829.1.7.193 | INTEGER | read-write | Enable Flow Max Alarm level. |
| INT alarmMaxEnableFo | 1.3.6.1.4.1.39829.1.7.169 | INTEGER | read-write | Enable Facility Out Max Alarm level. |
| INT alarmMaxEnablePressureFacility | 1.3.6.1.4.1.39829.1.7.209 | INTEGER | read-write | Enable Facility Pressure Max Alarm level. |
| INT alarmMaxEnablePressureServer | 1.3.6.1.4.1.39829.1.7.201 | INTEGER | read-write | Enable Server Pressure Max Alarm level. |
| INT alarmMaxEnableSi | 1.3.6.1.4.1.39829.1.7.177 | INTEGER | read-write | Enable Server In Max Alarm level. |
| INT alarmMaxEnableSo | 1.3.6.1.4.1.39829.1.7.185 | INTEGER | read-write | Enable Server Out Max Alarm level. |
| INT alarmMaxFi | 1.3.6.1.4.1.39829.1.7.160 | INTEGER | read-write | Set Facility In Max Alarm level. |
| INT alarmMaxFlow | 1.3.6.1.4.1.39829.1.7.192 | INTEGER | read-write | Set Flow Max Alarm level. |
| INT alarmMaxFo | 1.3.6.1.4.1.39829.1.7.168 | INTEGER | read-write | Set Facility Out Max Alarm level. |
| INT alarmMaxPressureFacility | 1.3.6.1.4.1.39829.1.7.208 | INTEGER | read-write | Set Facility Pressure Max Alarm level. |
| INT alarmMaxPressureServer | 1.3.6.1.4.1.39829.1.7.200 | INTEGER | read-write | Set Server Pressure Max Alarm level. |
| INT alarmMaxSi | 1.3.6.1.4.1.39829.1.7.176 | INTEGER | read-write | Set Server In Max Alarm level. |
| INT alarmMaxSo | 1.3.6.1.4.1.39829.1.7.184 | INTEGER | read-write | Set Server Out Max Alarm level. |
| INT alarmMinEnableFi | 1.3.6.1.4.1.39829.1.7.159 | INTEGER | read-write | Enable Facility In Min Alarm level. |
| INT alarmMinEnableFlow | 1.3.6.1.4.1.39829.1.7.191 | INTEGER | read-write | Enable Flow Min Alarm level. |
| INT alarmMinEnableFo | 1.3.6.1.4.1.39829.1.7.167 | INTEGER | read-write | Enable Facility Out Min alarm level. |
| INT alarmMinEnablePressureFacility | 1.3.6.1.4.1.39829.1.7.207 | INTEGER | read-write | Enable Facility Pressure Min Alarm level. |
| INT alarmMinEnablePressureServer | 1.3.6.1.4.1.39829.1.7.199 | INTEGER | read-write | Enable Server Pressure Min Alarm level. |
| INT alarmMinEnableSi | 1.3.6.1.4.1.39829.1.7.175 | INTEGER | read-write | Enable Server In Min Alarm level. |
| INT alarmMinEnableSo | 1.3.6.1.4.1.39829.1.7.183 | INTEGER | read-write | Enable Server Out Min Alarm level. |
| INT alarmMinFi | 1.3.6.1.4.1.39829.1.7.158 | INTEGER | read-write | Set Facility In Min Alarm level. |
| INT alarmMinFlow | 1.3.6.1.4.1.39829.1.7.190 | INTEGER | read-write | Set Flow Min Alarm level. |
| INT alarmMinFo | 1.3.6.1.4.1.39829.1.7.166 | INTEGER | read-write | Set Facility Out Min alarm level. |
| INT alarmMinPressureFacility | 1.3.6.1.4.1.39829.1.7.206 | INTEGER | read-write | Set Facility Pressure Min Alarm level. |
| INT alarmMinPressureServer | 1.3.6.1.4.1.39829.1.7.198 | INTEGER | read-write | Set Server Pressure Min Alarm level. |
| INT alarmMinSi | 1.3.6.1.4.1.39829.1.7.174 | INTEGER | read-write | Set Server In Min Alarm level. |
| INT alarmMinSo | 1.3.6.1.4.1.39829.1.7.182 | INTEGER | read-write | Set Server Out Min Alarm level. |
| NTF alarmNotify | 1.3.6.1.4.1.39829.1.0.500 | | | Trap alarm notification information for the SNMP Manager (obsolete). |
| asetek | 1.3.6.1.4.1.39829 | | | |
| cduCntlGroup | 1.3.6.1.4.1.39829.1.8.6 | | | |
| cduCompliances | 1.3.6.1.4.1.39829.1.8.10 | | | |
| cduCompliancesRev2 | 1.3.6.1.4.1.39829.1.8.13 | | | |
| cduEventGroup | 1.3.6.1.4.1.39829.1.8.11 | | | |
| cduMeasGroup | 1.3.6.1.4.1.39829.1.8.3 | | | |
| cduMeasGroupRev2 | 1.3.6.1.4.1.39829.1.8.4 | | | |
| cduNetGroup | 1.3.6.1.4.1.39829.1.8.5 | | | |
| cduNotifyGroup | 1.3.6.1.4.1.39829.1.8.8 | | | |
| cduProdGroup | 1.3.6.1.4.1.39829.1.8.1 | | | |
| cduSetupGroup | 1.3.6.1.4.1.39829.1.8.2 | | | |
| cduTrapGroup | 1.3.6.1.4.1.39829.1.8.9 | | | |
| cduTrapGroupRev2 | 1.3.6.1.4.1.39829.1.8.12 | | | |
| cduUnitGroup | 1.3.6.1.4.1.39829.1.8.7 | | | |
| controller | 1.3.6.1.4.1.39829.1.5 | | | |
| GAU controllerOut | 1.3.6.1.4.1.39829.1.3.111 | Gauge | read-only | The controller output. |
| STR controllerOutAlpha | 1.3.6.1.4.1.39829.1.5.87 | DisplayString | read-write | Controller Out Alpha - damping factor of output. |
| STR date | 1.3.6.1.4.1.39829.1.1.3 | DisplayString | read-only | Software revision date. |
| GAU deltaOutMax | 1.3.6.1.4.1.39829.1.5.83 | Gauge | read-write | Maximum delta output from controller. |
| STR description | 1.3.6.1.4.1.39829.1.1.5 | DisplayString | read-write | RackCDU description. |
| STR eventDescription | 1.3.6.1.4.1.39829.1.9.1 | DisplayString | read-only | Text which provide the user with a corrective action in case of a
warning or alarm trap.
IMPORTANT: Must only be used in traps! Any other use of this object is
invalid. |
| eventDescriptors | 1.3.6.1.4.1.39829.1.9 | | | |
| INT eventValue | 1.3.6.1.4.1.39829.1.9.2 | INTEGER | read-only | Event value placeholder sent with generic traps where the unit of the
value can be different.
IMPORTANT: Must only be used in traps! Any other use of this object is
invalid |
| NTF facilityFlowAlarm | 1.3.6.1.4.1.39829.1.0.525 | | | Facility flow alarm. |
| NTF facilityFlowWarning | 1.3.6.1.4.1.39829.1.0.512 | | | Facility flow warning. |
| NTF facilityPressureAlarm | 1.3.6.1.4.1.39829.1.0.521 | | | Facility pressure alarm. |
| NTF facilityPressureWarning | 1.3.6.1.4.1.39829.1.0.508 | | | Facility pressure warning. |
| NTF facilityReturnAlarm | 1.3.6.1.4.1.39829.1.0.518 | | | Facility return temperature alarm. |
| NTF facilityReturnWarning | 1.3.6.1.4.1.39829.1.0.505 | | | Facility return temperature warning. |
| NTF facilitySupplyAlarm | 1.3.6.1.4.1.39829.1.0.517 | | | Facility supply temperature alarm. |
| NTF facilitySupplyWarning | 1.3.6.1.4.1.39829.1.0.504 | | | Facility supply temperature warning. |
| GAU flowFacility | 1.3.6.1.4.1.39829.1.3.109 | Gauge | read-only | The flow of the cooleant on the facility side. |
| INT fluidHeatCapacity | 1.3.6.1.4.1.39829.1.6.70 | INTEGER | read-write | Heat Capacity of the liquid coolant utilized in the facility loop. |
| STR gainDifferential | 1.3.6.1.4.1.39829.1.5.82 | DisplayString | read-write | Differential gain in PID controller. |
| STR gainIntegral | 1.3.6.1.4.1.39829.1.5.81 | DisplayString | read-write | Integral gain in PID controller. |
| STR gainProportional | 1.3.6.1.4.1.39829.1.5.80 | DisplayString | read-write | Proportional gain in PID controller. |
| IP gateway | 1.3.6.1.4.1.39829.1.4.97 | IpAddress | read-write | Gateway of ControlBox. |
| GAU harnessVersion | 1.3.6.1.4.1.39829.1.6.72 | Gauge | read-write | Must be set to the harness version utilized by the RackCDU. The harness
version may affect the functionality of the RackCDU and it it therefor
important that the versions is matched. |
| GAU heatAverageFactor | 1.3.6.1.4.1.39829.1.6.71 | Gauge | read-write | The time frame of which the heat load is averaged. A short time frame
make the heat load sensative to small changes is temperature and flow
which results in a highly fluctuating value. A long time frame
stabilizes the value, but also results in a long response time. |
| GAU heatload | 1.3.6.1.4.1.39829.1.3.110 | Gauge | read-only | The heatload of the cooleant on the facility side. Can be averaged from
e.g. 1 to 28800 (24 hours) sec. |
| IP ipAddr | 1.3.6.1.4.1.39829.1.4.93 | IpAddress | read-write | IP address of ControlBox. |
| INT ipReboot | 1.3.6.1.4.1.39829.1.4.99 | INTEGER | read-write | IP address reboot. |
| INT ipSrc | 1.3.6.1.4.1.39829.1.4.98 | INTEGER | read-write | IP address source of ControlBox, eg. static or dhcp. |
| INT ipStoreFlash | 1.3.6.1.4.1.39829.1.4.91 | INTEGER | read-write | store settings to Flash. |
| NTF leakDetectionAlarm | 1.3.6.1.4.1.39829.1.0.523 | | | Leak detection alarm. |
| GAU limitPwmMax | 1.3.6.1.4.1.39829.1.5.84 | Gauge | read-write | Maximum PWM output. |
| GAU limitPwmMin | 1.3.6.1.4.1.39829.1.5.85 | Gauge | read-write | Minimum PWM output. |
| NTF liquidLevelAlarm | 1.3.6.1.4.1.39829.1.0.524 | | | Low liquid level alarm. |
| measurements | 1.3.6.1.4.1.39829.1.3 | | | |
| INT modeOfOperation | 1.3.6.1.4.1.39829.1.4.92 | INTEGER | read-write | Mode of operation of ControlBox, can be agent or master. |
| STR name | 1.3.6.1.4.1.39829.1.1.1 | DisplayString | read-write | Product name. |
| IP netMask | 1.3.6.1.4.1.39829.1.4.96 | IpAddress | read-write | Netmask of ControlBox. |
| network | 1.3.6.1.4.1.39829.1.4 | | | |
| notifications | 1.3.6.1.4.1.39829.1.7 | | | |
| INT notifyEnabled | 1.3.6.1.4.1.39829.1.2.1.1.2 | INTEGER | read-write | Indicates if this notify entry is enabled or not. |
| notifyEntry | 1.3.6.1.4.1.39829.1.2.1.1 | | not-accessible | Single notify entry containing notification receiver info. |
| IP notifyReceiverIPAddress | 1.3.6.1.4.1.39829.1.2.1.1.3 | IpAddress | read-write | Notification receiver IP address. |
| INT notifyReceiverNumber | 1.3.6.1.4.1.39829.1.2.1.1.1 | INTEGER | read-only | Index of notification receiver. |
| notifyTable | 1.3.6.1.4.1.39829.1.2.1 | | not-accessible | Table of settings used to setup notifications. |
| GAU pressureFacility | 1.3.6.1.4.1.39829.1.3.106 | Gauge | read-only | The pressure inside the RackCDU on the facility side. |
| GAU pressureServer | 1.3.6.1.4.1.39829.1.3.105 | Gauge | read-only | The pressure inside the RackCDU on the server side. |
| IP priDNS | 1.3.6.1.4.1.39829.1.4.94 | IpAddress | read-write | Primary DNS address of ControlBox. |
| product | 1.3.6.1.4.1.39829.1.1 | | | |
| rackCDU | 1.3.6.1.4.1.39829.1 | | | |
| STR rackNumber | 1.3.6.1.4.1.39829.1.1.4 | DisplayString | read-write | RackCDU number. |
| IP secDNS | 1.3.6.1.4.1.39829.1.4.95 | IpAddress | read-write | Secondary DNS address of ControlBox. |
| INT serverLeak | 1.3.6.1.4.1.39829.1.3.107 | INTEGER | read-only | Boolean indication of whether the RackCDU has detected a leak in the
system. |
| INT serverLevel | 1.3.6.1.4.1.39829.1.3.108 | INTEGER | read-only | Boolean indication of whether the RackCDU has detected a low level of
cooleant. |
| NTF serverPressureAlarm | 1.3.6.1.4.1.39829.1.0.522 | | | Server pressure alarm. |
| NTF serverPressureWarning | 1.3.6.1.4.1.39829.1.0.509 | | | Server pressure warning. |
| NTF serverReturnAlarm | 1.3.6.1.4.1.39829.1.0.520 | | | Server return temperature alarm. |
| NTF serverReturnWarning | 1.3.6.1.4.1.39829.1.0.507 | | | Server return temperature warning. |
| NTF serverSupplyAlarm | 1.3.6.1.4.1.39829.1.0.519 | | | Server supply temperature alarm. |
| NTF serverSupplyWarning | 1.3.6.1.4.1.39829.1.0.506 | | | Server supply temperature warning. |
| INT setpointFacilityOut | 1.3.6.1.4.1.39829.1.5.86 | INTEGER | read-write | Setpoint for Facility Out Temperature. |
| setup | 1.3.6.1.4.1.39829.1.2 | | | |
| INT smtpTrapsAlarmEnable | 1.3.6.1.4.1.39829.1.7.152 | INTEGER | read-write | Enable SMTP Alarm traps. |
| INT smtpTrapsWarningEnable | 1.3.6.1.4.1.39829.1.7.153 | INTEGER | read-write | Enable SMTP Warning traps. |
| INT snmpTrapsAlarmEnable | 1.3.6.1.4.1.39829.1.7.150 | INTEGER | read-write | Enable SNMP Alarm traps. |
| INT snmpTrapsWarningEnable | 1.3.6.1.4.1.39829.1.7.151 | INTEGER | read-write | Enable SNMP Warning traps. |
| INT status | 1.3.6.1.4.1.39829.1.1.6 | INTEGER | read-only | The overall status of the RackCDU. Status is evaluated based on the
notification settings. If a noticiation has been disabled it will not
be included in the overall status either. |
| INT temperatureAmbient | 1.3.6.1.4.1.39829.1.3.104 | INTEGER | read-only | The temperature of the ambient air close to the RackCDU. |
| INT temperatureFacilityIn | 1.3.6.1.4.1.39829.1.3.100 | INTEGER | read-only | The temperature of the water going into the RackCDU on the Facility side
(cold). |
| INT temperatureFacilityOut | 1.3.6.1.4.1.39829.1.3.101 | INTEGER | read-only | The temperature of the water going out of the RackCDU on the Facility
side (hot). |
| INT temperatureServerIn | 1.3.6.1.4.1.39829.1.3.102 | INTEGER | read-only | The temperature of the water going into the servers node (cold). |
| INT temperatureServerOut | 1.3.6.1.4.1.39829.1.3.103 | INTEGER | read-only | The temperature of the water going out of the servers node (hot). |
| traps | 1.3.6.1.4.1.39829.1.0 | | | |
| units | 1.3.6.1.4.1.39829.1.6 | | | |
| STR version | 1.3.6.1.4.1.39829.1.1.2 | DisplayString | read-only | Software version. |
| INT warningMaxEnableFi | 1.3.6.1.4.1.39829.1.7.157 | INTEGER | read-write | Enable Facility In Max Warning level. |
| INT warningMaxEnableFlow | 1.3.6.1.4.1.39829.1.7.189 | INTEGER | read-write | Enable Flow Max Warning level. |
| INT warningMaxEnableFo | 1.3.6.1.4.1.39829.1.7.165 | INTEGER | read-write | Enable Facility Out Max Warning level. |
| INT warningMaxEnablePressureFacility | 1.3.6.1.4.1.39829.1.7.205 | INTEGER | read-write | Enable Facility Pressure Max Warning level. |
| INT warningMaxEnablePressureServer | 1.3.6.1.4.1.39829.1.7.197 | INTEGER | read-write | Enable Server Pressure Max Warning level. |
| INT warningMaxEnableSi | 1.3.6.1.4.1.39829.1.7.173 | INTEGER | read-write | Enable Server In Max Warning level. |
| INT warningMaxEnableSo | 1.3.6.1.4.1.39829.1.7.181 | INTEGER | read-write | Enable Server Out Max Warning level. |
| INT warningMaxFi | 1.3.6.1.4.1.39829.1.7.156 | INTEGER | read-write | Set Facility In Max Warning level. |
| INT warningMaxFlow | 1.3.6.1.4.1.39829.1.7.188 | INTEGER | read-write | Set Flow Max Warning level. |
| INT warningMaxFo | 1.3.6.1.4.1.39829.1.7.164 | INTEGER | read-write | Set Facility Out Max Warning level. |
| INT warningMaxPressureFacility | 1.3.6.1.4.1.39829.1.7.204 | INTEGER | read-write | Set Facility Pressure Max Warning level. |
| INT warningMaxPressureServer | 1.3.6.1.4.1.39829.1.7.196 | INTEGER | read-write | Set Server Pressure Max Warning level. |
| INT warningMaxSi | 1.3.6.1.4.1.39829.1.7.172 | INTEGER | read-write | Set Server In Max Warning level. |
| INT warningMaxSo | 1.3.6.1.4.1.39829.1.7.180 | INTEGER | read-write | Set Server Out Max Warning level. |
| INT warningMinEnableFi | 1.3.6.1.4.1.39829.1.7.155 | INTEGER | read-write | Enable Facility In Min Warning level. |
| INT warningMinEnableFlow | 1.3.6.1.4.1.39829.1.7.187 | INTEGER | read-write | Enable Flow Min Warning level. |
| INT warningMinEnableFo | 1.3.6.1.4.1.39829.1.7.163 | INTEGER | read-write | Enable Facility Out Min Warning level. |
| INT warningMinEnablePressureFacility | 1.3.6.1.4.1.39829.1.7.203 | INTEGER | read-write | Enable Facility Pressure Min Warning level. |
| INT warningMinEnablePressureServer | 1.3.6.1.4.1.39829.1.7.195 | INTEGER | read-write | Enable Server Pressure Min Warning level. |
| INT warningMinEnableSi | 1.3.6.1.4.1.39829.1.7.171 | INTEGER | read-write | Enable Server In Min Warning level. |
| INT warningMinEnableSo | 1.3.6.1.4.1.39829.1.7.179 | INTEGER | read-write | Enable Server Out Min Warning level. |
| INT warningMinFi | 1.3.6.1.4.1.39829.1.7.154 | INTEGER | read-write | Set Facility In Min Warning level. |
| INT warningMinFlow | 1.3.6.1.4.1.39829.1.7.186 | INTEGER | read-write | Set Flow Min Warning level. |
| INT warningMinFo | 1.3.6.1.4.1.39829.1.7.162 | INTEGER | read-write | Set Facility Out Min Warning level. |
| INT warningMinPressureFacility | 1.3.6.1.4.1.39829.1.7.202 | INTEGER | read-write | Set Facility Pressure Min Warning level. |
| INT warningMinPressureServer | 1.3.6.1.4.1.39829.1.7.194 | INTEGER | read-write | Set Server Pressure Min Warning level. |
| INT warningMinSi | 1.3.6.1.4.1.39829.1.7.170 | INTEGER | read-write | Set Server In Min Warning level. |
| INT warningMinSo | 1.3.6.1.4.1.39829.1.7.178 | INTEGER | read-write | Set Server Out Min Warning level. |
| NTF warningNotify | 1.3.6.1.4.1.39829.1.0.501 | | | Trap warning notification information for the SNMP Manager (obsolete). |