Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Set Facility Pressure Min Warning level.
What is warningMinPressureFacility?
This read-write pressure threshold triggers warnings if facility-side pressure drops below configured values. It detects potential leaks in return lines allowing corrective maintenance. Setting to 10 warns if facility pressure falls below 10 psi.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.39829.1.7.202 snmpwalk -v2c -c public <target> ASETEK-RACKCDU-SMI-V1-MIB-V16::warningMinPressureFacility
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.39829.1.7.202.1 snmpget -v2c -c public <target> ASETEK-RACKCDU-SMI-V1-MIB-V16::warningMinPressureFacility.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.39829.1.7.202.1 i <value>
Start monitoring Asetek RackCDU liquid cooling distribution units with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ASETEK-RACKCDU-SMI-V1-MIB-V16::warningMinPressureFacility OID value, configure state conditions and alerts, and monitor any Asetek RackCDU liquid cooling distribution units from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.39829 | asetek | ASETEK-RACKCDU-SMI-V1-MIB-V16 |
| 1.3.6.1.4.1.39829.1 | rackCDU | ASETEK-RACKCDU-SMI-V1-MIB-V16 |
| 1.3.6.1.4.1.39829.1.7 | notifications | ASETEK-RACKCDU-SMI-V1-MIB-V16 |
| 1.3.6.1.4.1.39829.1.7.202 | warningMinPressureFacility | ASETEK-RACKCDU-SMI-V1-MIB-V16 |