| OID symbolic | OID numeric | Type | Access | Description |
| aii | 1.3.6.1.4.1.539 | | | |
| INT aislcdinAlarmSeverity | 1.3.6.1.4.1.539.24.1.1.5 | INTEGER | read-write | Severity of the point's alarm state, or notReported(5)
if the point does not generate an alarm. |
| STR aislcdinAlarmStateText | 1.3.6.1.4.1.539.24.1.1.7 | DisplayString | read-write | Textual description of the point's alarm state.
Maximum length is 80 characters. |
| INT aislcdinCurrentInput | 1.3.6.1.4.1.539.24.1.1.8 | INTEGER | read-only | The current input to the point. |
| INT aislcdinCurrentState | 1.3.6.1.4.1.539.24.1.1.10 | INTEGER | read-only | The point's current alarm state, or normal(5). |
| STR aislcdinCurrentStateText | 1.3.6.1.4.1.539.24.1.1.11 | DisplayString | read-only | Textual description of the point's current state.
This is either aislcdinNormalStateText or
aislcdinAlarmStateText. |
| INT aislcdinDebounceValue | 1.3.6.1.4.1.539.24.1.1.21 | INTEGER | read-write | Number of 100 msec intervals to wait
for the input to stop bouncing. |
| STR aislcdinDescription | 1.3.6.1.4.1.539.24.1.1.2 | DisplayString | read-write | Textual description of the point.
Maximum length is 80 characters. |
| STR aislcdinLastChangeTime | 1.3.6.1.4.1.539.24.1.1.9 | DisplayString | read-only | Textual representation of the time of the most recent
input change. 24-hour format: YYYY-MM-DD HH:MM:SS. |
| INT aislcdinNormalInput | 1.3.6.1.4.1.539.24.1.1.4 | INTEGER | read-write | Input that corresponds to the point's normal state. |
| STR aislcdinNormalStateText | 1.3.6.1.4.1.539.24.1.1.6 | DisplayString | read-write | Textual description of the point's normal state.
Maximum length is 80 characters. |
| NUM aislcdinPointNumber | 1.3.6.1.4.1.539.24.1.1.1 | PositiveInteger | read-only | Input point number to which this table row applies. |
| STR aislcdintl1AccessID | 1.3.6.1.4.1.539.24.1.1.12 | DisplayString | read-write | Unique TL1 access identifier for this point.
Maximum length is 22 characters. |
| INT aislcdintl1AccessIDType | 1.3.6.1.4.1.539.24.1.1.14 | INTEGER | read-write | Identifies the point as either an equipment(1) alarm condition
or an environmental(2) alarm. |
| STR aislcdintl1AlarmMessage | 1.3.6.1.4.1.539.24.1.1.20 | DisplayString | read-write | Textual description of the alarm, used only when
aislcdintl1AccessIDType is environmental(2).
Maximum length is 40 characters. |
| STR aislcdintl1AlarmType | 1.3.6.1.4.1.539.24.1.1.19 | DisplayString | read-write | String indicating the type of alarm, used only
when aislcdintl1AccessIDType is environmental(2).
Maximum length is 10 characters. |
| STR aislcdintl1ConditionDescription | 1.3.6.1.4.1.539.24.1.1.18 | DisplayString | read-write | Textual description of the alarm condition, used only
when aislcdintl1AccessIDType is equipment(1).
Maximum length is 64 characters. |
| STR aislcdintl1ConditionType | 1.3.6.1.4.1.539.24.1.1.17 | DisplayString | read-write | String indicating the type of alarm condition, used
only when aislcdintl1AccessIDType is equipment(1).
Maximum length is 20 characters. |
| INT aislcdintl1NotificationCode | 1.3.6.1.4.1.539.24.1.1.15 | INTEGER | read-write | Severity of the point's alarm state. |
| T/F aislcdintl1Provisioned | 1.3.6.1.4.1.539.24.1.1.13 | TruthValue | read-write | Enable TL1 management of this point. |
| INT aislcdintl1ServiceAffecting | 1.3.6.1.4.1.539.24.1.1.16 | INTEGER | read-write | Indicates whether or not the alarm affects the functioning
of the equipment. This is only meaningful when
aislcdintl1AccessIDType is equipment(1). |
| INT aislcdinTrapEnable | 1.3.6.1.4.1.539.24.1.1.3 | INTEGER | read-write | Enable or disable alarm traps. |
| INT aislcdisc5VPowerSupplyAStatus | 1.3.6.1.4.1.539.24.7 | INTEGER | read-only | Status of the 'A' 5V power supply. |
| INT aislcdisc5VPowerSupplyBStatus | 1.3.6.1.4.1.539.24.8 | INTEGER | read-only | Status of the 'B' 5V power supply. |
| INT aislcdiscAnalogInputPowerSupplyStatus | 1.3.6.1.4.1.539.24.11 | INTEGER | read-only | Status of the analog input power supply fuse. |
| INT aislcdiscFanStatus | 1.3.6.1.4.1.539.24.6 | INTEGER | read-only | Status of the fan unit. |
| INT aislcdiscFiber1TransmitterStatus | 1.3.6.1.4.1.539.24.9 | INTEGER | read-only | Status of the first fiber port's transmitter. |
| INT aislcdiscFiber2TransmitterStatus | 1.3.6.1.4.1.539.24.10 | INTEGER | read-only | Status of the second fiber port's transmitter. |
| INT aislcdiscPowerSupplyAStatus | 1.3.6.1.4.1.539.24.4 | INTEGER | read-only | Status of the 'A' power supply. |
| INT aislcdiscPowerSupplyBStatus | 1.3.6.1.4.1.539.24.5 | INTEGER | read-only | Status of the 'B' power supply. |
| INT aislcdiscPowerSupplyStatusEx | 1.3.6.1.4.1.539.24.3 | INTEGER | read-only | Status of the power supply. okay(1) or trouble(2).
When the SLC is booted, this indicates okay(1) until
the software determines the correct status. |
| aiSLCDiscrete | 1.3.6.1.4.1.539.24 | | | MIB module for SLCs with discrete input and output points. |
| aiSLCDiscreteInputEntry | 1.3.6.1.4.1.539.24.1.1 | | not-accessible | Entry of aiSLCDiscreteInputTable. |
| aiSLCDiscreteInputTable | 1.3.6.1.4.1.539.24.1 | | not-accessible | Table of discrete input points indexed by point number.
Includes description, configuration, and status information. |
| aiSLCDiscreteOutputEntry | 1.3.6.1.4.1.539.24.2.1 | | not-accessible | Entry of aiSLCDiscreteOutputTable. |
| aiSLCDiscreteOutputTable | 1.3.6.1.4.1.539.24.2 | | not-accessible | Table of discrete input points indexed by point number.
Includes description, configuration, and status information. |
| INT aislcdoutAlarmSeverity | 1.3.6.1.4.1.539.24.2.1.10 | INTEGER | read-write | Severity of the point's alarm state, or notReported(5)
if the point does not generate an alarm. |
| INT aislcdoutAlarmStateOutput | 1.3.6.1.4.1.539.24.2.1.9 | INTEGER | read-write | Output that corresponds to the point's alarm state. |
| STR aislcdoutAlarmStateText | 1.3.6.1.4.1.539.24.2.1.12 | DisplayString | read-write | Textual description of the point's alarm state.
Maximum length is 80 characters. |
| INT aislcdoutCurrentOutput | 1.3.6.1.4.1.539.24.2.1.6 | INTEGER | not-accessible | DEPRECATED: use aislcdoutOutput. |
| INT aislcdoutCurrentState | 1.3.6.1.4.1.539.24.2.1.15 | INTEGER | read-only | The point's current alarm state, or normal(5). |
| STR aislcdoutCurrentStateText | 1.3.6.1.4.1.539.24.2.1.16 | DisplayString | read-only | Textual description of the point's current state.
This is either aislcdoutNonAlarmStateText or
aislcdoutAlarmStateText. |
| STR aislcdoutDescription | 1.3.6.1.4.1.539.24.2.1.2 | DisplayString | read-write | Textual description of the point.
Maximum length is 80 characters. |
| STR aislcdoutEnergizeExpression | 1.3.6.1.4.1.539.24.2.1.17 | DisplayString | read-write | String that describes when this output goes into the
energized state, as a function of a discrete input (or
analog input for AIscout2).
For AIscout, an integer >= 1 represents a discrete
input, and '~' complements the input state.
For AIscout2, this expression is a combination of analog
and discrete inputs. Analog inputs are preceded by an 'A'
and discrete inputs by a 'D'. The complement '~' works
on a group of inputs. Also, multiple inputs may be specified
as a comma separated list (1,3,5) or a hyphenated range (1-5).
The expression is a combination of up to three ORs and as many
ANDs as desired (i.e. a sum of 3 products).
An empty string indicates manual control of the output point.
AIscout examples:
'15' -- energize the output when input 15 is alarmed
(and deenergize when the input is normal).
'~8' -- energize the output when input 8 is normal
(and deenergize when the input is alarmed).
AIscout2 examples:
'AH1,3,5' -- energize if the high alarm is active on analog
inputs 1, 3 and 5.
'~AH1-2&AL3' -- energize if analog inputs 1 and 2 are normal
(not in the alarm state) AND analog input 3 is
in the low alarm state.
'AH*|AL*|D*' -- energize if ANY analog is alarmed OR any
discrete input is alarmed. |
| STR aislcdoutLastChangeTime | 1.3.6.1.4.1.539.24.2.1.14 | DisplayString | read-only | Textual representation of the time of the most recent
output change. 24-hour format: YYYY-MM-DD HH:MM:SS. |
| INT aislcdoutMomentaryTimeout | 1.3.6.1.4.1.539.24.2.1.5 | INTEGER | read-write | If zero, the output will stay in the alarm state until
it is returned to the normal state by some other event.
If nonzero, this defines the time interval for
momentary operation described in aislcdoutOutput.
Maximum is 99.9 seconds. |
| STR aislcdoutNonAlarmStateText | 1.3.6.1.4.1.539.24.2.1.11 | DisplayString | read-write | Textual description of the point's non-alarm state.
Maximum length is 80 characters. |
| INT aislcdoutNormalOutput | 1.3.6.1.4.1.539.24.2.1.4 | INTEGER | not-accessible | DEPRECATED: use aislcdoutAlarmStateOutput. |
| INT aislcdoutOutput | 1.3.6.1.4.1.539.24.2.1.13 | INTEGER | read-write | On a read operation, this is the current output of the point.
On a write operation when the output is controlled
by aislcdoutEnergizeExpression, the write is rejected.
Otherwise on a write operation, when set to
de-energized, the output immediately assumes this
state. When set to energized, the state of the
output goes to the energized state, unless the
output is already waiting for its
aislcdoutMomentaryTimeout interval to elapse. |
| INT aislcdoutOutputEnable | 1.3.6.1.4.1.539.24.2.1.3 | INTEGER | read-write | Enable or disable this point. When the
point is disabled, the output is immediately
de-energized and remains so regardless of the
values of other objects in this row.
When the point is enabled, output is immediately
set to its non-alarm state and operates according
to the values of the other objects in this row. |
| NUM aislcdoutPointNumber | 1.3.6.1.4.1.539.24.2.1.1 | PositiveInteger | read-only | Output point number to which this table row applies. |
| STR aislcdouttl1AccessID | 1.3.6.1.4.1.539.24.2.1.7 | DisplayString | read-write | Unique TL1 access identifier for this point.
Maximum length is 22 characters. |
| INT aislcdoutTrapEnable | 1.3.6.1.4.1.539.24.2.1.8 | INTEGER | read-write | Enable or disable traps. If enabled, a trap
is sent whenever the point changes state. |