All MIBs › SYNSO-UPSMIB
Category: Power and UPS
Description: Manages SYNSO UPS configuration, battery state, output power, and alarm notifications.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is SYNSO-UPSMIB?
SYNSO-UPSMIB is a vendor MIB from SYNSO for managing its uninterruptible power supply (UPS) product line. It exposes platform and feature identification, serial number, system start time, communication port settings (UPS and modem), signal type/definition, and alarm status. This is a classic power-protection hardware monitoring MIB: it lets an administrator check whether the UPS alarm is active, how long the system has been running since last start, and basic identity/version data (platform, software, serial number) to confirm the correct unit and its operating state. It is a self-contained proprietary enterprise MIB rather than one built on a shared UPS standard such as RFC 1628 (UPS-MIB). Deployment context is data center or wiring-closet power protection, where SYNSO UPS units are polled or send traps to alert on power events, battery issues, or communication loss. Engineers can download the SYNSO-UPSMIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in SYNSO-UPSMIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- SYNSO UPS (uninterruptible power supply)
Monitoring Examples
An admin polls syupsUpsAlarm to detect an active alarm condition such as on-battery or overload, and checks syupsSystemStartTime to confirm the UPS's uptime since its last restart. syupsFeatureTable/syupsFeature enumerates the capabilities of the specific syupsPlatForm model, while synsoUpsSoftware and syupsSerialNo let an admin verify firmware version and unit identity during an audit.
What Can Be Monitored
- UPS alarm status
- system start time/uptime
- serial number/platform identity
- software/firmware version
- communication port configuration
This MIB depends on
Related MIBs
Imported Objects
From SNMPv2-SMI
| IpAddress | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| enterprises |
From SNMPv2-TC
| DisplayString |
From UPS-MIB
| upsBatteryStatus | OBJECT-TYPE |
| upsBatteryTemperature | OBJECT-TYPE |
| upsBatteryVoltage | OBJECT-TYPE |
| upsInputCurrent | OBJECT-TYPE |
| upsInputFrequency | OBJECT-TYPE |
| upsInputVoltage | OBJECT-TYPE |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| synso | 1.3.6.1.4.1.9557 | |||
| synsoUpsSoftware | 1.3.6.1.4.1.9557.1 | |||
| syupsAccessControlEntry | 1.3.6.1.4.1.9557.1.6.3.1 | not-accessible | An access control entry. | |
| INT syupsAccessControlIndex | 1.3.6.1.4.1.9557.1.6.3.1.1 | INTEGER | read-only | The entry number of a access control setting. |
| STR syupsAccessControlOperator | 1.3.6.1.4.1.9557.1.6.2 | DisplayString | read-write | The operator which is used to operate on the access control table. There are three commands: 1. 'ADD: community' indicates to add a new entry to the access control list. 2. 'REPLACE: x, community' indicates to replace the x-th entry in the table with the new settings. 3. 'DELETE:n1, n2' indicates to delete the entries from number n1 to number n2 from the access control table. |
| STR syupsAccessControlSetting | 1.3.6.1.4.1.9557.1.6.3.1.2 | DisplayString | read-only | A string containing the community name. |
| syupsAccessControlTable | 1.3.6.1.4.1.9557.1.6.3 | not-accessible | A list of access control entries. Only entries in this list can have access to the agent. | |
| NTF syupsBadBattery | 1.3.6.1.4.1.9557.1.7.7 | The battery is bad. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| syupsBasicSetting | 1.3.6.1.4.1.9557.1.1 | |||
| INT syupsBasicSignalDefinition | 1.3.6.1.4.1.9557.1.1.5 | INTEGER | read-only | The signal definitions for the basic signaling UPS. The value can be the following bit combinations: SG_POWER_FAILURE_ENABLE 0x01 SG_BATTERY_LOW_ENABLE 0x02 SG_SHUTDOWN_ENABLE 0x04 SG_POWER_FAILURE_VOLTHIGH 0x10 SG_BATTERY_LOW_VOLTHIGH 0x20 SG_SHUTDOWN_VOLTHIGH 0x40 SG_POWER_FAILURE_ENABLE, SG_BATTERY_LOW_ENABLE, and SG_SHUTDOWN_ENABLE indicate whether the signals for a power failure , a low battery condition, and the UPS shutdown are enabled. SG_POWER_FAILURE_VOLTHIGH, SG_BATTERY_LOW_VOLTHIGH, and SG_SHUTDOWN_VOLTHIGH indicate whether the voltage level for these signals are high or low. |
| INT syupsBatteryReplaceDate | 1.3.6.1.4.1.9557.1.2.4 | INTEGER | read-write | The last battery replacement date. It represents the number of days elapsed since January 1, 1901. |
| INT syupsCommandDelay | 1.3.6.1.4.1.9557.1.3.2.1.17 | INTEGER | read-write | How long the event must last before executing the external command file. |
| INT syupsCommandEnable | 1.3.6.1.4.1.9557.1.3.2.1.16 | INTEGER | read-write | Whether to execute the external command file when the event occurs. A 1 indicates enable, a 0 indicates disable. |
| STR syupsCommandFile | 1.3.6.1.4.1.9557.1.3.2.1.18 | DisplayString | read-write | The external command file which will be executed when the event occurs. |
| INT syupsConfigBatteryVoltage | 1.3.6.1.4.1.9557.1.2.3 | INTEGER | read-only | The nominal battery voltage. |
| syupsCoworker | 1.3.6.1.4.1.9557.1.6 | |||
| syupsDataEntry | 1.3.6.1.4.1.9557.1.4.7.1 | not-accessible | An entry representing a record in the data log file. | |
| INT syupsDataIndex | 1.3.6.1.4.1.9557.1.4.7.1.1 | INTEGER | read-only | The record number of a data entry. |
| INT syupsDataNumRecords | 1.3.6.1.4.1.9557.1.4.6 | INTEGER | read-only | The total number of records in the data log file. |
| STR syupsDataRecord | 1.3.6.1.4.1.9557.1.4.7.1.2 | DisplayString | read-only | The string containing a data entry. |
| INT syupsDataRecordInterval | 1.3.6.1.4.1.9557.1.4.4 | INTEGER | read-write | The number of minutes to wait between each recording to the data log file. |
| syupsDataTable | 1.3.6.1.4.1.9557.1.4.7 | not-accessible | A list of data entries. Each entry represents a record in the data log file. | |
| INT syupsEmailDelay | 1.3.6.1.4.1.9557.1.3.2.1.9 | INTEGER | read-write | How long the event must last before emailing users. |
| INT syupsEmailEnable | 1.3.6.1.4.1.9557.1.3.2.1.8 | INTEGER | read-write | Whether to email users when the event occurs. A 1 indicates enable, a 0 indicates disable. |
| STR syupsEmailMessage | 1.3.6.1.4.1.9557.1.3.2.1.10 | DisplayString | read-write | The additional message which will be sent when the event occurs. |
| STR syupsEmailUsers | 1.3.6.1.4.1.9557.1.3.2.1.11 | DisplayString | read-write | Who will receive the mail when the event occurs. |
| INT syupsEnableAutoSave | 1.3.6.1.4.1.9557.1.2.8 | INTEGER | read-write | Setting it to 1, the agent will try to save all files opened by applications before shutting down the operation system. Setting it to 0 will disable the auto save feature. |
| syupsEventAction | 1.3.6.1.4.1.9557.1.3 | |||
| syupsEventActionEntry | 1.3.6.1.4.1.9557.1.3.2.1 | not-accessible | An entry containing information applicable to a particular event action. | |
| syupsEventActionTable | 1.3.6.1.4.1.9557.1.3.2 | not-accessible | A list of event action entries. The number of entries is given by the value of syupsNoEventActionEntries. | |
| syupsEventEntry | 1.3.6.1.4.1.9557.1.4.3.1 | not-accessible | An entry representing a record in the event log file. | |
| INT syupsEventId | 1.3.6.1.4.1.9557.1.3.2.1.1 | INTEGER | read-only | The event ID. |
| INT syupsEventIndex | 1.3.6.1.4.1.9557.1.4.3.1.1 | INTEGER | read-only | The record number of an event entry. |
| INT syupsEventNumRecords | 1.3.6.1.4.1.9557.1.4.2 | INTEGER | read-only | The total number of records in the event log file. |
| STR syupsEventRecord | 1.3.6.1.4.1.9557.1.4.3.1.2 | DisplayString | read-only | The string containing an event entry. |
| syupsEventTable | 1.3.6.1.4.1.9557.1.4.3 | not-accessible | A list of event entries. Each entry represents a record in the event log file. | |
| INT syupsFeature | 1.3.6.1.4.1.9557.1.1.2.1.1 | INTEGER | read-only | The string representing a feature. |
| syupsFeatureEntry | 1.3.6.1.4.1.9557.1.1.2.1 | not-accessible | An entry representing the support information for a feature. | |
| syupsFeatureTable | 1.3.6.1.4.1.9557.1.1.2 | not-accessible | A table containing the supported features. | |
| syupsHistory | 1.3.6.1.4.1.9557.1.4 | |||
| STR syupsHistoryOperator | 1.3.6.1.4.1.9557.1.4.8 | DisplayString | read-write | The operator which is used to operate on the history file. The command format is 'Command, File, Range'. So far, Command can be PURGE, File can be EVENT or DATA, and Range can be ALL or 'mm/dd/year..mm/dd/year'. For example, 'PURGE, EVENT, ALL' tells the UPS software to purge all entries in the event log file. And 'PURGE, DATA, 03/20/1995..07/02/1995' tells the UPS software to purge the entries which are recorded form 03/20/1995 to 07/20/1995 from the event log file. |
| INT syupsLogEnable | 1.3.6.1.4.1.9557.1.3.2.1.2 | INTEGER | read-write | Whether to log the event in the log file when it occurs. A 1 indicates enable, a 0 indicates disable. |
| NTF syupsLowBattery | 1.3.6.1.4.1.9557.1.7.6 | The battery is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| INT syupsMaxDataFileLength | 1.3.6.1.4.1.9557.1.4.5 | INTEGER | read-write | The maximum length (in bytes) of the data log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length. |
| INT syupsMaxEventFileLength | 1.3.6.1.4.1.9557.1.4.1 | INTEGER | read-write | The maximum length (in bytes) of the event log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length. |
| STR syupsModemComPort | 1.3.6.1.4.1.9557.1.1.7 | DisplayString | read-write | The serial port which the UPS software use to dial out when some particular events occur. The format varies from platform to platform. For DOS program, the format is 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it is 'portNo'. For NetWare program, it is 'portType, boardNo, portNo'. For UNIX, it is 'device name'. |
| INT syupsNoAccessControl | 1.3.6.1.4.1.9557.1.6.1 | INTEGER | read-only | The total number of access control entries. |
| INT syupsNoEventActionEntries | 1.3.6.1.4.1.9557.1.3.1 | INTEGER | read-only | The number of event-action items. This variable indicates the number of rows in the event-action table. |
| INT syupsNoOutlet | 1.3.6.1.4.1.9557.1.2.5 | INTEGER | read-only | The total number of controllable outlets. |
| INT syupsNoOutlets | 1.3.6.1.4.1.9557.1.2.12 | INTEGER | read-only | The number of controllable outlets. |
| INT syupsNoSchEntries | 1.3.6.1.4.1.9557.1.5.1 | INTEGER | read-only | The total number of schedule entries. |
| INT syupsNotifyDelay | 1.3.6.1.4.1.9557.1.3.2.1.4 | INTEGER | read-write | How long the event must last before notifying users. |
| INT syupsNotifyEnable | 1.3.6.1.4.1.9557.1.3.2.1.3 | INTEGER | read-write | Whether to notify users when the event occurs. A 1 indicates enable, a 0 indicates disable. |
| STR syupsNotifyMessage | 1.3.6.1.4.1.9557.1.3.2.1.5 | DisplayString | read-write | The message which will be sent when the event occurs. |
| INT syupsNotifyPeriod | 1.3.6.1.4.1.9557.1.3.2.1.6 | INTEGER | read-write | How often (in seconds) to send the message. The -1 means once. |
| STR syupsNotifyUsers | 1.3.6.1.4.1.9557.1.3.2.1.7 | DisplayString | read-write | Who will receive the message when the event occurs. |
| INT syupsNoTrapReceiver | 1.3.6.1.4.1.9557.1.6.4 | INTEGER | read-only | The total number of trap receiver entries. |
| NTF syupsOffFrequency | 1.3.6.1.4.1.9557.1.7.5 | The frequency is abnormal. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| STR syupsOutletDescription | 1.3.6.1.4.1.9557.1.2.13.1.2 | DisplayString | read-write | The outlet description. |
| syupsOutletEntry | 1.3.6.1.4.1.9557.1.2.13.1 | not-accessible | An entry containing information applicable to a particular controllable outlet. | |
| INT syupsOutletIndex | 1.3.6.1.4.1.9557.1.2.13.1.1 | INTEGER | not-accessible | The outlet identifier. |
| STR syupsOutletOperator | 1.3.6.1.4.1.9557.1.2.14 | DisplayString | read-write | The operator is used to control the outlets. There are two commands: 1. 'SWITCH: OutletNo, OnOff'. The OutletNo specify the outlet. The OnOff can be 0 (off) or 1 (on). For example, 'SWITCH: 2, 1' means turning on (1) the outlet #2. 'SWITCH: 4, 0' means turning off (0) the outlet #4. 2. 'SET: OutletNo, Desc, DelayTime, Depend'. The OutletNo specify the outlet. The Desc specifies the outlet description. The DelayTime specifies the shutdown delay time for the outlet. The Depend specifies the shutdown dependent list for the outlet. For example, 'SET: 3, My Printer, 20, 192.168.1.9' means setting the description of outlet #3 to 'My Printer', the shutdown delay time to 20 seconds and the Shutdown Dependent to '192.168.1.9'. |
| STR syupsOutletParamter | 1.3.6.1.4.1.9557.1.2.6 | DisplayString | read-write | This object is not used any more. |
| INT syupsOutletShutdownDelay | 1.3.6.1.4.1.9557.1.2.13.1.3 | INTEGER | read-write | The delay time (in seconds) before turning off the outlet. Before turning off the outlet, the agent will send a shutdown command to anyone specified in the syupsOutletShutdownDepend, telling them to start their shutdown procedure. This delay time is used to allow those cmputers to be shut down safely. |
| STR syupsOutletShutdownDepend | 1.3.6.1.4.1.9557.1.2.13.1.4 | DisplayString | read-write | A string containing those who should perform their shutdown procedure before the outlet turns off. The agent will inform each one in the list to begin their shutdown procedure before it turns off the power of the outlet. |
| syupsOutletTable | 1.3.6.1.4.1.9557.1.2.13 | not-accessible | A list of outlet table entries. The number of entries is given by the value of syupsNoOutlets. | |
| INT syupsPageDelay | 1.3.6.1.4.1.9557.1.3.2.1.13 | INTEGER | read-write | How long the event must last before paging users. |
| INT syupsPageEnable | 1.3.6.1.4.1.9557.1.3.2.1.12 | INTEGER | read-write | Whether to page users when the event occurs. A 1 indicates enable, a 0 indicates disable. |
| STR syupsPageMessage | 1.3.6.1.4.1.9557.1.3.2.1.14 | DisplayString | read-write | The message which will be sent when the event occurs. |
| STR syupsPageUsers | 1.3.6.1.4.1.9557.1.3.2.1.15 | DisplayString | read-write | Who will receive the code when the event occurs. |
| STR syupsPlatForm | 1.3.6.1.4.1.9557.1.1.1 | DisplayString | read-only | The platform which the UPS software is running on. |
| INT syupsSaveConfig | 1.3.6.1.4.1.9557.1.2.11 | INTEGER | read-write | Used to inform the agnet to save the configurations. Its value indicates which group to be saved. For example, a 1 indicates group 1 (syupsBasicSetting) to be saved, a 6 1 indicates group 6 (syupsCoworker) to be saved. You have to use it to save configurations after changing settings, or the settings may be lost. |
| INT syupsSchAction | 1.3.6.1.4.1.9557.1.5.3.1.5 | INTEGER | read-only | The action of the schedule entry. It could be: General System Test (1) Quick Battery Test (2) Deep Battery Test (3) Turn On UPS (11) Turn Off UPS (21) Turn On Outlet (100+x) Turn Off Outlet (200+x) where x indicates the outlet number. |
| syupsSchedule | 1.3.6.1.4.1.9557.1.5 | |||
| syupsSchEntry | 1.3.6.1.4.1.9557.1.5.3.1 | not-accessible | A schedule entry. | |
| INT syupsSchIndex | 1.3.6.1.4.1.9557.1.5.3.1.1 | INTEGER | read-only | The entry number of a schedule setting. |
| STR syupsSchOperator | 1.3.6.1.4.1.9557.1.5.2 | DisplayString | read-write | The operator which is used to operate on the schedule table. There are three commands: 1. 'ADD: action, mm/dd/yyyy, hh:mm:ss, week_day, repeat' indicates to add a new entry to the schedule list. 2. 'REPLACE: i, action, mm/dd/yyyy, hh:mm:ss, week_day, repeat' indicates to replace the i-th entry in the table with the new settings. 3. 'DELETE:n1, n2' indicates to delete the entries ranging from number n1 to number n2 from the schedule table. 'action' could be the following: General System Test (1) Quick Battery Test (2) Deep Battery Test (3) Turn On UPS (11) Turn Off UPS (21) Turn On Outlet (100+x) Turn Off Outlet (200+x) where x indicates the outlet number. 'mm/dd/year' and 'hh:mm:ss' specify the action's starting time. 'repeat' indicates the frequency of the action, it could be Once(1), Daily(2), Weekly(3) and Monthly(4). 'week_day' indicating the day of week is meaningful only when the repeat is set to Weekly, and it could be Sun(0), Mon(1), ..., and Sat(6). For example, '1, 07/08/1994, 15:30:00, 0, 4' indicates that the UPS will do a General System Test at 3:30 PM every month from July 8, 1994. '203, 06/20/1995, 07:00:00, 0, 1' indicates that the UPS will turn off outlet #3 at 7 o'clock on June 20, 1995 and do it only once. |
| INT syupsSchRepeat | 1.3.6.1.4.1.9557.1.5.3.1.6 | INTEGER | read-only | It indicates the frequency of the action, it could be Once(1), Daily(2), Weekly(3) and Monthly(4). |
| STR syupsSchStartDate | 1.3.6.1.4.1.9557.1.5.3.1.2 | DisplayString | read-only | The starting date (mm/dd/yyyy) of the schedule entry. |
| STR syupsSchStartTime | 1.3.6.1.4.1.9557.1.5.3.1.3 | DisplayString | read-only | The starting time (hh:mm:ss) of the schedule entry. |
| syupsSchTable | 1.3.6.1.4.1.9557.1.5.3 | not-accessible | A list of schedule entries. | |
| INT syupsSchWeekDay | 1.3.6.1.4.1.9557.1.5.3.1.4 | INTEGER | read-only | The starting day of week for the schedule entry. It could be Sun(0), Mon(1), ..., and Sat(6). It is used when syupsSchRepeat is set to weekly. |
| STR syupsScopeSettings | 1.3.6.1.4.1.9557.1.4.9 | DisplayString | read-write | The string contains the settings for UPS Scope Chart, including Value Original Point, Value Unit, Time Unit, Time Interval, and Display Items. The format for the settings string is '%d, %d, %d, %d, %d'. Display Items can be any one or any combination of the following items: SCOPE_INPUT_VOLT 0x0001 SCOPE_OUTPUT_VOLT 0x0010 SCOPE_INPUT_FREQ 0x0100 SCOPE_OUTPUT_FREQ 0x1000 |
| STR syupsSerialNo | 1.3.6.1.4.1.9557.1.2.2 | DisplayString | read-only | The serial number of the UPS connected to the UPS software. |
| INT syupsShutdownDelay | 1.3.6.1.4.1.9557.1.3.2.1.20 | INTEGER | read-write | How long the event must last before shutting down the system. |
| STR syupsShutdownDepend | 1.3.6.1.4.1.9557.1.2.7 | DisplayString | read-write | A string containing those who should perform their shutdown procedure before the UPS turns off. The agent will inform each one in the list to begin their shutdown procedure before it turns off the power of the UPS. |
| INT syupsShutdownEnable | 1.3.6.1.4.1.9557.1.3.2.1.19 | INTEGER | read-write | Whether to shut down the system when the event occurs. A 1 indicates enable, a 0 indicates disable. |
| INT syupsShutdownOsDelay | 1.3.6.1.4.1.9557.1.2.9 | INTEGER | read-write | The delay time before shutting down the operation system. When it is necessary to shut down the operation system, the agent will run the specified command file and try to save all files opened by applications before shutting down the OS. This delay time is used to do such things. |
| INT syupsShutdownUpsDelay | 1.3.6.1.4.1.9557.1.2.10 | INTEGER | read-write | The delay time before shutting down the UPS. Before shutting down the operation system, the agent will send a command to tell the UPS to shut down. This delay time is used to allow the agent to shut down the operation system safely. |
| INT syupsSignalType | 1.3.6.1.4.1.9557.1.1.4 | INTEGER | read-write | The signaling method between the UPS and software. When the basicSignal used, the UPS changes the voltage level of some specific pins to notify the software of what critical event occurs. Usually, the UPS will inform software when a power failure or a low battery condition occurs. On the other hand, the software can change the voltage signal of a specific pin to ask the UPS to shut down (turn off). When the smartSignal used, the UPS asks like a standard communication device (such as mouse or modem). That means the UPS and software communicate with each other using a pre-defined protocol. The protocol should include at least the following commands: - query the power status of the UPS - query the power data of the UPS - command the UPS to shut down |
| STR syupsSupportInfo | 1.3.6.1.4.1.9557.1.1.2.1.2 | DisplayString | read-only | The string containing the support information for a feature. |
| INT syupsSystemStartTime | 1.3.6.1.4.1.9557.1.1.3 | INTEGER | read-only | The time that the UPS software starts. It is the number of seconds elapsed since 00:00:00, January 1, 1970. |
| NTF syupsTrapOverCurrent | 1.3.6.1.4.1.9557.1.7.2 | The current is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| NTF syupsTrapOverTemperature | 1.3.6.1.4.1.9557.1.7.1 | The battery temperature is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| NTF syupsTrapOverVoltage | 1.3.6.1.4.1.9557.1.7.3 | The voltage is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| syupsTrapReceiverEntry | 1.3.6.1.4.1.9557.1.6.6.1 | not-accessible | An trap receiver entry. | |
| INT syupsTrapReceiverIndex | 1.3.6.1.4.1.9557.1.6.6.1.1 | INTEGER | read-only | The entry number of a trap receiver setting. |
| STR syupsTrapReceiverOperator | 1.3.6.1.4.1.9557.1.6.5 | DisplayString | read-write | The operator which is used to operate on the trap receiver table. There are three commands: 1. 'ADD: ipAddress' indicates to add a new entry to the trap receiver list. 2. 'REPLACE: x, ipAddress' indicates to replace the x-th entry in the table with the new settings. 3. 'DELETE:n1, n2' indicates to delete the entries from number n1 to number n2 from the trap receiver table. |
| STR syupsTrapReceiverSetting | 1.3.6.1.4.1.9557.1.6.6.1.2 | DisplayString | read-only | A string containing a trap receiver's IP address. |
| syupsTrapReceiverTable | 1.3.6.1.4.1.9557.1.6.6 | not-accessible | A list of trap receiver entries. When an important event occurs, the agent will send traps to all the entries in the list. | |
| syupsTraps | 1.3.6.1.4.1.9557.1.7 | |||
| NTF syupsTrapUnderVoltage | 1.3.6.1.4.1.9557.1.7.4 | The voltage is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present. | ||
| INT syupsUpsAlarm | 1.3.6.1.4.1.9557.1.2.1 | INTEGER | read-only | It is used internally. Each bit indicates a critical event, such as input bad, on battery, communications lost, ...,etc. |
| STR syupsUpsComPort | 1.3.6.1.4.1.9557.1.1.6 | DisplayString | read-write | The serial port which the UPS software use to communicate with the UPS. The format varies from platform to platform. For DOS program, the format is 'portNo, portAddress, portIRQ' (e.g. '1, 0x2f8, 3' for COM2). For Windows program, it is 'portNo'. For NetWare program, it is 'portType, boardNo, portNo'. For UNIX, it is 'device name'. |
| syupsUpsExtension | 1.3.6.1.4.1.9557.1.2 |
RFC description
Monitors Synso UPS software status including battery conditions, power input metrics, and system uptime tracking.