All MIBs › ORION-BASE-MIB
Organization: Delta Energy Systems (Switzerland) AG
Last Updated: 2012--0-4-
Category: UPS/Power
Description: Provides base SNMP management objects for Delta Energy Systems Orion UPS monitoring and control.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is ORION-BASE-MIB?
ORION-BASE-MIB (despite the short_desc mentioning UPS, the module description indicates this is actually a DC power system MIB for a PSC 3-based controller, likely from Delta or a related DC power vendor) provides base management objects for a DC power/energy system used to supply telecom or data center equipment. It exposes site and system identity information, software version, a real-time system clock, and both urgent and non-urgent alarm counts along with indexed alarm identifier/name/value tables. Its monitoring value is squarely in fault and hardware status: operators can watch for a mains failure alarm, track counts of urgent versus non-urgent alarms, and drill into specific alarm identifiers and their current values to diagnose power system problems before they cause an outage. It also reports dcSoftwareVersion, letting operators confirm the controller firmware version is current. It is typically deployed at telecom sites, cabinets, or data centers using DC power plants for critical equipment power. Engineers can download the ORION-BASE-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in ORION-BASE-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- DC power system controller (PSC 3-based)
- telecom/data center power plant
Monitoring Examples
An administrator would poll dcNumberUrgentAlarms and dcNumberNonUrgentAlarms for a quick health summary, then check dcMainsFailureAlarm to see if grid power has been lost. Walking the urgent alarm table by dcUrgentAlarmIdentifier and dcUrgentAlarmName while reading dcUrgentAlarmValue reveals exactly which condition (e.g., a specific rectifier or battery fault) is active. Checking dcSoftwareVersion alongside dcSystemDateTime confirms the controller's firmware and clock are correct, which matters for accurate alarm timestamping.
What Can Be Monitored
- urgent alarm count
- non-urgent alarm count
- mains failure alarm state
- specific alarm identifier and value
- system software version
- system date/time
This MIB depends on
Related MIBs
Imported Objects
From GLOBAL-REG
| modules | OBJECT-IDENTITY |
| orion | OBJECT-IDENTITY |
From SNMPv2-CONF
| MODULE-COMPLIANCE | |
| NOTIFICATION-GROUP | |
| OBJECT-GROUP |
From SNMPv2-SMI
| Gauge32 | |
| Integer32 | |
| IpAddress | |
| MODULE-IDENTITY | |
| NOTIFICATION-TYPE | |
| OBJECT-TYPE | |
| enterprises |
From SNMPv2-TC
| DisplayString |
How to Use in IPNetwork Monitor
Example using dcNumberUrgentAlarms OID:
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| orionBaseMibModule | 1.3.6.1.4.1.20246.2.1.1.2 | MIB for managing a DC power system with PSC 3. | ||
| orionBaseMib | 1.3.6.1.4.1.20246.2.3.1.1.1 | |||
| controllerConfs | 1.3.6.1.4.1.20246.2.3.1.1.1.1 | |||
| controllerGroups | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1 | |||
| systemInfoGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1 | The collection of system info scalar objects. | ||
| systemAlarmGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2 | The collection of system alarm scalar objects. | ||
| systemMonitorGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3 | The collection of system monitor scalar objects. | ||
| rectifierGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4 | The collection of rectifier scalar objects. | ||
| eventHistoryTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5 | The collection of event history table objects. | ||
| alarmTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6 | The collection of alarm table objects. | ||
| rectifierTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7 | The collection of rectifier table objects. | ||
| notificationsGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8 | The group of all controller notifications. | ||
| genericAlarmTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9 | Assignment of events to alarm table entries. | ||
| batteryGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10 | The collection of battery scalar objects. | ||
| controlEventTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11 | Assignment of control events to table entries. | ||
| trapDestinationTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12 | Trap destionation table. | ||
| miscGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13 | The collection of miscellaneous objects. | ||
| rectifierGroupTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14 | The collection of rectifier group table objects. | ||
| batteryStringTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15 | The collection of battery string table objects. | ||
| defaultLogEventTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16 | The collection of default log event table objects. | ||
| eventProcessingEventTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17 | The collection of event processing event table objects. | ||
| lvdTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18 | The collection of LVD table objects. | ||
| powerLimitationTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19 | The collection of power limitation table objects. | ||
| measurementTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20 | The collection of measurement table objects. | ||
| meterPanelEventTableGroup | 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21 | The collection of meter panel event table objects. | ||
| controllerCompl | 1.3.6.1.4.1.20246.2.3.1.1.1.1.2 | |||
| controllerBasicCompl | 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1 | The basic implementation requirements for the controller MIB. | ||
| controllerObjects | 1.3.6.1.4.1.20246.2.3.1.1.1.2 | |||
| dcSystemInfo | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1 | |||
| STR dcSiteName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 | DisplayString | read-write | An administratively-assigned site name for this DC-power system. |
| STR dcSystemName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 | DisplayString | read-write | An administratively-assigned system name for this DC-power system. |
| STR dcSystemDateTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 | DisplayString | read-write | ISO 8601 representation of controller�s local date/time. The value is in the format YYYY-MM-DDThh:mm:ss. An example of a valid string is: '2004-10-04T13:45:00'. |
| STR dcSoftwareVersion | 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 | DisplayString | read-only | The controller�s software version e.g V2.50Build1. |
| dcSystemAlarms | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2 | |||
| dcEventHistoryTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 | not-accessible | Controller�s event history table that shows the content of the default log file. | |
| dcEventHistoryEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 | not-accessible | A particular Event History entry. | |
| I32 dcEventHistoryIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 | Integer32 | not-accessible | Table index. |
| STR dcEventHistoryTimestamp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 | DisplayString | read-only | ISO8601 timestamp representation of a particular entry in the form YYYY-MM-DDThh:mm:ss. |
| STR dcEventHistoryMessage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 | DisplayString | read-only | Event message of a particular entry. |
| dcAlarmTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 | not-accessible | Table that shows all currently active alarm sources causing urgent or non-urgent alarm(s). | |
| dcAlarmEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 | not-accessible | A particular active alarm source entry. | |
| I32 dcAlarmIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 | Integer32 | not-accessible | Table index. |
| INT dcAlarmEventCategory | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 | INTEGER | read-only | Specifies the type of alarm source. |
| STR dcAlarmEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 | DisplayString | read-only | Name of a particular alarm source entry. |
| G32 dcAlarmEventIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 | Gauge32 | read-only | Unique alarm event identifier. |
| INT dcAlarmEventValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 | INTEGER | read-only | Event status that corresponds to alarm event identifier. |
| G32 dcNumberUrgentAlarmsEx | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 | Gauge32 | read-only | Number of currently active urgent alarm sources. A zero value indicates that urgent alarm is not active. |
| G32 dcNumberNonUrgentAlarms | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 | Gauge32 | read-only | Number of currently active non urgent alarm sources. A zero value indicates that non urgent alarm is not active. |
| INT dcMainsFailureAlarm | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 | INTEGER | read-only | Mains failure alarm. |
| G32 dcUrgentAlarmIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 | Gauge32 | read-only | Current unique urgent alarm event identifier. A zero value indicates that urgent alarm is not active. |
| INT dcUrgentAlarmValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 | INTEGER | read-only | Current urgent alarm event status that corresponds to the urgent alarm identifier. If the urgent alarm identifier is zero then the alarm value is false. |
| G32 dcNonUrgentAlarmIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 | Gauge32 | read-only | Current unique non urgent alarm event identifier. A zero value indicates that non urgent alarm is not active. |
| INT dcNonUrgentAlarmValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 | INTEGER | read-only | Current non urgent alarm event status that corresponds to non urgent alarm identifier. If the non urgent alarm identifier is zero then the alarm value is false. |
| STR dcUrgentAlarmName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 | DisplayString | read-only | Current alarm name for urgent alarm that corresponds to urgent alarm identifier. |
| STR dcNonUrgentAlarmName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 | DisplayString | read-only | Current alarm name for active non urgent alarm that corresponds to non urgent alarm identifier. |
| dcGenericAlarmTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 | not-accessible | Table that shows ten alarm event assignments that can be configured via WEB interface. | |
| dcGenericAlarmEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 | not-accessible | A particular generic alarm entry. | |
| I32 dcGenericAlarmIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 | Integer32 | not-accessible | Table index. |
| STR dcGenericAlarmEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 | DisplayString | read-only | Plain text name of the assigned alarm event. Empty if not configured. |
| G32 dcGenericAlarmEventIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 | Gauge32 | read-only | Unique numeric identifier of the assigned alarm event. Zero if not configured. |
| INT dcGenericAlarmEventValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 | INTEGER | read-only | Current value of the assigned alarm event. Value is false if not configured. |
| G32 dcNumberCriticalAlarms | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13 | Gauge32 | read-only | Number of currently active critical alarm sources. A zero value indicates that critical alarm is not active. |
| G32 dcCriticalAlarmIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14 | Gauge32 | read-only | Current unique critical alarm event identifier. A zero value indicates that critical alarm is not active. |
| INT dcCriticalAlarmValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15 | INTEGER | read-only | Current critical alarm event status that corresponds to the critical alarm identifier. If the critical alarm identifier is zero then the alarm value is false. |
| STR dcCriticalAlarmName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16 | DisplayString | read-only | Current alarm name for active critical alarm that corresponds to critical alarm identifier. |
| dcSystemMonitor | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3 | |||
| I32 dcSystemVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 | Integer32 | read-only | The measured system voltage. The max. value 2147483647 is used to indicate an invalid value. |
| I32 dcLoadCurrent | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 | Integer32 | read-only | The measured load current. The max. value 2147483647 is used to indicate an invalid value. |
| I32 dcBatteryCurrent | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 | Integer32 | read-only | The measured battery current. The max. value 2147483647 is used to indicate an invalid value. |
| I32 dcBatteryTemperature | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 | Integer32 | read-only | The measured battery temperature. The max. value 2147483647 is used to indicate an invalid value. |
| INT dcChargeState | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 | INTEGER | read-only | Battery charge state. |
| INT dcCurrentLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 | INTEGER | read-only | Battery current limit. |
| I32 dcRectifierCurrent | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 | Integer32 | read-only | Total current of all working rectifier modules. The maximum value 2147483647 is used to indicate an invalid value. |
| I32 dcSystemPower | 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 | Integer32 | read-only | Calculated system power. The maximum value 2147483647 is used to indicate an invalid value. |
| dcRectifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4 | |||
| G32 dcNumberRectifiers | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 | Gauge32 | read-only | The configured number of rectifiers plugged into the system. The maximum number of rectifiersi is 128. |
| G32 dcNumberRectifiersFailure | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 | Gauge32 | read-only | Number of rectifiers that are not properly working. |
| G32 dcNumberRectifiersOkay | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 | Gauge32 | read-only | Number of rectifiers that are properly working. |
| dcRectifierTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 | not-accessible | Table that shows all currently active rectifier modules. | |
| dcRectifierEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 | not-accessible | A particular rectifier entry. | |
| I32 dcRectifierIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 | Integer32 | not-accessible | Table index. |
| STR dcRectifierIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 | DisplayString | read-only | Unique rectifier identifier. If positioning active the position number scheme is used otherwise the rectifier instance is used to identify a rectifier. |
| INT dcRectifierStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 | INTEGER | read-only | Specifies status of rectifiers. |
| dcRectifierGroupTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 | not-accessible | Table that shows all available rectifier groups. | |
| dcRectifierGroupEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1 | not-accessible | A particular rectifier group entry. | |
| I32 dcRectifierGroupIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1 | Integer32 | not-accessible | Table index. |
| STR dcRectifierGroupName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2 | DisplayString | read-only | Rectifier group name to identify an individual device parameter set. |
| INT dcRectifierGroupRectifierType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3 | INTEGER | read-only | Rectifier type defined for this group. |
| I32 dcRectifierGroupDefaultVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4 | Integer32 | read-write | This default voltage is used by rectifiers when there is no connection to PSC 3. |
| I32 dcRectifierGroupDefaultCurrentLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5 | Integer32 | read-write | This default current limit is used by rectifiers when there is no connection to PSC 3. |
| I32 dcRectifierGroupDefaultPowerLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6 | Integer32 | read-write | This default power limit is used by rectifiers when there is no connection to PSC 3. |
| I32 dcRectifierGroupInputLowOff | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7 | Integer32 | read-write | Threshold for low AC input voltage. It can is used to adjust the behaviour of the power system to the available AC network limitation. |
| I32 dcRectifierGroupInputLowOn | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8 | Integer32 | read-write | For details see dcRectifierGroupInputLowOff. |
| I32 dcRectifierGroupStartupVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9 | Integer32 | read-write | Startup parameters are the values that rectifiers use during the start-up phase. These parameters allow starting the system smoothly after a mains failure even on a discharged battery and even without PSC 3. |
| I32 dcRectifierGroupStartupCurrentLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10 | Integer32 | read-write | For details see dcRectifierGroupStartupVoltage. |
| I32 dcRectifierGroupStartupPowerLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11 | Integer32 | read-write | For details see dcRectifierGroupStartupVoltage. |
| G32 dcRectifierGroupStartupTimeLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12 | Gauge32 | read-write | For details see dcRectifierGroupStartupVoltage. |
| G32 dcRectifierGroupPowerupDelay | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13 | Gauge32 | read-write | This parameter is used after a mains failure to delay the start-up of all rectifiers. |
| G32 dcRectifierGroupPowerupTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14 | Gauge32 | read-write | This parameter used after a mains failure and allows defining a time within all rectifiers needs to start-up one after another. |
| I32 dcRectifierGroupUmaxOff | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15 | Integer32 | read-write | Overvoltage protection value. |
| dcRectifierFunctions | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6 | |||
| dcEfficiencyCycling | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1 | |||
| INT dcEfficiencyCyclingEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1 | INTEGER | read-write | Enable/disable efficiency cycling. |
| INT dcLimitSwitchingTimes | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2 | INTEGER | read-write | Enable/disable limit switching times. |
| INT dcForceSwitchingOncePerMonth | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3 | INTEGER | read-write | Enable/disable force switching once per month. |
| I32 dcMaximumLoadStep | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4 | Integer32 | read-write | Maximum load setup. |
| I32 dcMinimumLoadStep | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5 | Integer32 | read-write | Minimum load setup. |
| dcPowerLimitation | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 | |||
| dcPowerLimitationTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 | not-accessible | Table that shows parameters of the available power limitation functions. | |
| dcPowerLimitationEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1 | not-accessible | A particular power limitation entry. | |
| I32 dcPowerLimitationIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.1 | Integer32 | not-accessible | Table index. |
| STR dcPowerLimitationEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.2 | DisplayString | read-only | Name of the power limitation event. |
| INT dcPowerLimitationStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.3 | INTEGER | read-only | Status of power limitation. |
| INT dcPowerLimitationType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.4 | INTEGER | read-only | Power limitation type. |
| I32 dcPowerLimitationLimit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.5 | Integer32 | read-write | Limit used for power limitation. |
| INT dcPowerLimitationNoBatteryDischarge | 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1.6 | INTEGER | read-write | Enable/disable no battery discharge during power limitation. |
| dcBattery | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5 | |||
| dcFloatCharge | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1 | |||
| I32 dcUsys20 | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 | Integer32 | read-write | Voltage to regulate to at 20�C. If temperature compensation is used, this voltage will vary. |
| dcBatteryTest | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2 | |||
| dcBatteryTestParameter | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1 | |||
| I32 dcBatteryTestUsupport | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 | Integer32 | read-write | Support charge voltage for the battery. |
| G32 dcBatteryTestDuration | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 | Gauge32 | read-write | Battery test duration. |
| G32 dcBatteryTestInterval | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 | Gauge32 | read-write | Minimal time between programmed battery tests as start condition. |
| I32 dcBatteryTestDischargeCurrent | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 | Integer32 | read-write | Battery discharge current. The maximum value 2147483647 is used to indicate an invalid value. |
| G32 dcBatteryTestMinDuration | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 | Gauge32 | read-write | Minimum battery test duration during which time a battery test is not stopped in case of a voltage below the support voltage or a current difference higher than the specified value defined in Idiff measurement is detected. |
| I32 dcBatteryTestVoltageWithinUfloat | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6 | Integer32 | read-write | Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestVoltageWithinUfloatPeriod) in order to start a battery test. |
| G32 dcBatteryTestVoltageWithinUfloatPeriod | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7 | Gauge32 | read-write | For details see dcBatteryTestVoltageWithinUfloat parameter. |
| I32 dcBatteryTestTempFrom | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8 | Integer32 | read-write | Battery temperature must be within temperature range given by dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery test can be started. |
| I32 dcBatteryTestTempTo | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9 | Integer32 | read-write | For details see dcBatteryTestTempFrom parameter. |
| INT dcBatteryTestIntervalEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.10 | INTEGER | read-write | Enable/disable interval. For more details see dcBatteryTestInterval. |
| STR dcBatteryTestStartTimeFrom | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11 | DisplayString | read-write | Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestStartTimeFrom and dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'. |
| STR dcBatteryTestStartTimeTo | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12 | DisplayString | read-write | For details see dcBatteryTestStartTimeFrom. |
| dcBatteryTestResults | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2 | |||
| STR dcBatteryTestDateTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 | DisplayString | read-only | ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available. |
| INT dcBatteryTestResult | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 | INTEGER | read-only | Result of last performed battery test. |
| I32 dcBatteryTestEndVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 | Integer32 | read-only | System voltage at the end of the last performed battery test. The maximum value 2147483647 is used to indicate an invalid value. |
| INT dcBatteryTestControl | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 | INTEGER | read-write | Start/stop of battery test. This special charge mode is used to check the capacity of a battery. Please note that a battery test can be started even if the battery is not fully charged. In this case the test result is ambiguous and the set failure event will become active. |
| INT dcBatteryTestStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 | INTEGER | read-only | Status of battery test. |
| INT dcBatteryTestFailureEvent | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 | INTEGER | read-write | Reset battery test failure event. |
| INT dcBatteryTestType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6 | INTEGER | read-write | Battery test type used. |
| dcBatteryParameter | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3 | |||
| G32 dcTotalBatteryCapacity | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 | Gauge32 | read-only | Total battery capacity for all available batteries. |
| dcBatteryStringTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 | not-accessible | Table that shows parameters of the available battery strings. | |
| dcBatteryStringEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1 | not-accessible | A particular battery string entry. | |
| I32 dcBatteryStringIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1 | Integer32 | not-accessible | Table index. |
| STR dcBatteryStringName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2 | DisplayString | read-only | Name of the battery string. |
| I32 dcBatteryStringMaxIBatt | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3 | Integer32 | read-write | Maximum battery charging current for this string. This parameter can be set individually for each battery. PSC 3 then regulates the system voltage such that the maximum battery charging current of each battery is respected. |
| G32 dcBatteryStringCapacity | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4 | Gauge32 | read-write | Capacity of battery can be defined individually. It is used to calculate the expected backup time of the system. |
| dcLossOfBackupTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3 | |||
| INT dcLossOfBackupTimeEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1 | INTEGER | read-write | Enable/disable loss of backup time functionality. |
| INT dcLossOfBackupTimeStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2 | INTEGER | read-only | Status of loss of backup time functionality. |
| G32 dcExpectedBackupTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3 | Gauge32 | read-write | Expected backup time value. Based on the given value for the parameter expected backup time, the corresponding maximum discharge current is calculated. |
| dcEqualize | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4 | |||
| INT dcEqualizeControl | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 | INTEGER | read-write | Start/stop of battery equalize which is a special charge mode that applies a higher voltage to the batteries than the float charge. This ensures that the cells are all equally charged. |
| INT dcEqualizeStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 | INTEGER | read-only | Current status of battery equalize. |
| INT dcEqualizeEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3 | INTEGER | read-write | Enable/disable equalize. |
| dcEqualizeParameter | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4 | |||
| I32 dcEqualizeVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1 | Integer32 | read-write | Voltage used for equalize. |
| G32 dcEqualizeDuration | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2 | Gauge32 | read-write | Duration of equalize. |
| INT dcEqualizeUseBattRoomFanEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3 | INTEGER | read-write | Enable/disable battery room fan during equalize. |
| G32 dcEqualizeLeadTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4 | Gauge32 | read-write | Lead time for equalize. |
| G32 dcEqualizeTimeLag | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5 | Gauge32 | read-write | Time lag for equalize. |
| G32 dcEqualizeInterval | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6 | Gauge32 | read-write | Interval for equalize as start condition. |
| STR dcEqualizeStartTimeIntervalFrom | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7 | DisplayString | read-write | Defines start time window for equqlize. The possible time window is defined as the range between dcEqualizeStartTimeIntervalFrom and dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'. |
| STR dcEqualizeStartTimeIntervalTo | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8 | DisplayString | read-write | For detail see dcEqualizeStartTimeIntervalFrom. |
| G32 dcEqualizeInhibitAfterBoost | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9 | Gauge32 | read-write | Inhibit after boost as start condition. |
| dcBoostCharge | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5 | |||
| INT dcBoostChargeControl | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 | INTEGER | read-write | Start/stop of boost charge which is a special charge mode that applies a higher voltage to the batteries than the float charge. This mode is started after a discharge phase to recharge the batteries faster. |
| INT dcBoostChargeStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 | INTEGER | read-only | Current status of boost charge. |
| INT dcBoostChargeType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3 | INTEGER | read-write | Boost charge type. |
| dcBoostChargeParameter | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4 | |||
| I32 dcBoostChargeVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.1 | Integer32 | read-write | Voltage used for boost charge. |
| G32 dcBoostChargeMaxDuration | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.2 | Gauge32 | read-write | Defines the maximum allowed time for boost charge to prevent that the battery is charged forever. |
| INT dcBoostChargeUseBattRoomFanEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.3 | INTEGER | read-write | Enable/disable battery room fan during boost charge. |
| G32 dcBoostChargeTimeLag | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.4 | Gauge32 | read-write | Time lag used for boost charge. |
| I32 dcBoostChargeIstart | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.5 | Integer32 | read-write | For current based boost charge, the parameters Istart and Istop are the battery current values at which boost charge starts or stops. |
| I32 dcBoostChargeIstop | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.6 | Integer32 | read-write | For details see dcBoostChargeIstart. |
| G32 dcBoostChargeInhibitTime | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4.7 | Gauge32 | read-write | A start condition for all types of boost charge. It defines the time from last boost charge stop to the next acceptable boost charge start. |
| dcSystemVoltageSupervision | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6 | |||
| I32 dcUaMax | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 | Integer32 | read-write | If the system voltage is outside the range specified by the values UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the system event 'S Ua low'/'S Ua high' is activated. The values for the parameters UaMin and UaMax are not temperature compensated. |
| I32 dcUaMin | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 | Integer32 | read-write | For details see dcUaMax. |
| I32 dcUsMax | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 | Integer32 | read-write | If the voltage is outside the range defined by the parameters UsMin (lower safety voltage)/UsMax (upper safety voltage), the system event 'S Us low'/'S Us high' is activated. If temperature compensation is enabled, the levels for Us min and / Us max are automatically temperature compensated to correspond to the required system voltage. The parameters are defined at 20�C. |
| I32 dcUsMin | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 | Integer32 | read-write | For details see dcUsMax. |
| I32 dcBoD | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 | Integer32 | read-write | Voltage threshold for Battery on Discharge alarm. |
| I32 dcHysteresis | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 | Integer32 | read-write | Hysteresis used for Ua and Us. |
| INT dcSuppressUaLowEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 | INTEGER | read-write | Suppress Ua Low alarm during mains failure. |
| INT dcSuppressUsLowEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 | INTEGER | read-write | Suppress Us Low alarm during mains failure. |
| INT dcEnableUsTempComp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9 | INTEGER | read-write | Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max). |
| dcEvtCtrlCharge | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7 | |||
| INT dcEvtCtrlChargeStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1 | INTEGER | read-only | Event control charge status. |
| INT dcEvtCtrlChargeType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2 | INTEGER | read-write | Selected event control charge type. |
| dcEvtCtrlChargeParameter | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3 | |||
| I32 dcEvtCtrlChargeVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.1 | Integer32 | read-write | Voltage used for event control charge. |
| INT dcEvtCtrlChargeTempCompEnabled | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.2 | INTEGER | read-write | Enable/disable temperature compensation during event control charge. |
| I32 dcEvtCtrlChargeMaxIBatt | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3.3 | Integer32 | read-write | Max. IBatt used for event control charge. |
| dcTempComp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8 | |||
| INT dcTempCompType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1 | INTEGER | read-write | Enable/disable battery temperature compensation. |
| I32 dcSlope | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2 | Integer32 | read-write | Temperature compensation coefficient for system voltage. |
| I32 dcStartTemp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3 | Integer32 | read-write | Lower limit for the area in which the temperature compensation is active. |
| I32 dcStopTemp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4 | Integer32 | read-write | Upper limit for the area in which the temperature compensation is active. |
| I32 dcMaxVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5 | Integer32 | read-write | Upper limit for the area in which the temperature compensation is not controlling the system voltage. |
| I32 dcLowStopVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6 | Integer32 | read-write | The temperature compensation will not control the charging voltage above this parameter at low temperatures. |
| I32 dcLowStartTemp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7 | Integer32 | read-write | High temperature limit of the lower range. |
| I32 dcLowTempSlope | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8 | Integer32 | read-write | Compensation factor applied inside the low range. |
| I32 dcHighStartTemp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9 | Integer32 | read-write | The low temperature limit of the higher range. |
| I32 dcHighTempSlope | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10 | Integer32 | read-write | Compensation factor applied inside the high range. |
| I32 dcHighStopVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11 | Integer32 | read-write | The temperature compensation will not control the charging voltage below this parameter at high temperatures. |
| I32 dcRunawayTemp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12 | Integer32 | read-write | A threshold for detecting thermal runaway of the battery. |
| I32 dcRunawayVoltage | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13 | Integer32 | read-write | Charging voltage while Runaway Temp has been exceeded. |
| dcTempSupervision | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9 | |||
| I32 dcHighTemp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1 | Integer32 | read-write | Temperature threshold for high battery temperature alarm 10�C ... 70�C |
| I32 dcHighTempHyst | 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2 | Integer32 | read-write | Hysteresis for the High Temp 1�C ... 70�C |
| dcInputOutput | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6 | |||
| dcControlEventTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 | not-accessible | Table that shows ten output event assignments that can be configured via WEB interface. | |
| dcControlEventEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 | not-accessible | A particular generic output entry. | |
| I32 dcControlEventIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 | Integer32 | not-accessible | Table index. |
| STR dcControlEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 | DisplayString | read-only | Plain text name of the assigned control event. Empty if not configure. |
| G32 dcControlEventIdentifier | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 | Gauge32 | read-only | Unique numeric identifier of the assigned control event. Zero if not configured. |
| INT dcControlEventValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 | INTEGER | read-write | Current value of the assigned control event. Value is false if not configured. |
| dcMisc | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7 | |||
| dcTrapDestinationTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 | not-accessible | Trap table that shows all configured trap destinations. | |
| dcTrapDestinationEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 | not-accessible | A particular trap destination entry. | |
| I32 dcTrapDestinationIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 | Integer32 | not-accessible | Table index. |
| IP dcTrapDestinationIp | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 | IpAddress | read-write | IP address of the trap destination. Value is 0.0.0.0 if IP address is not configured. |
| G32 dcTrapDestinationPort | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 | Gauge32 | read-write | Port number of the trap destination. By default port 162 is used. |
| INT dcFileProcessingStatus | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 | INTEGER | read-only | File processing status for software and setup up/downloads. |
| INT dcResendActiveAlarmTraps | 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4 | INTEGER | read-write | Resend all active Urgent, Non Urgent, and Critical Alarm Traps. |
| dcConfig | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8 | |||
| dcDefaultLogEventTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 | not-accessible | Event config table for default log. | |
| dcDefaultLogEventEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1 | not-accessible | A particular event entry. | |
| I32 dcDefaultLogEventIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1 | Integer32 | not-accessible | Table index. |
| STR dcDefaultLogEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2 | DisplayString | read-only | Plain text name of the event that can be logged. |
| INT dcDefaultLogEventLogged | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3 | INTEGER | read-write | If yes then this event is logged otherwise not. |
| dcEventProcessingEventTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 | not-accessible | Event config table for event ORs. | |
| dcEventProcessingEventEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1 | not-accessible | A particular event entry. | |
| I32 dcEventProcessingEventIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1 | Integer32 | not-accessible | Table index. |
| STR dcEventProcessingEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2 | DisplayString | read-only | Plain text name of the input event. |
| INT dcEventProcessingEventAssigned | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3 | INTEGER | read-write | If yes then the input event is assigned to the selected event. Please note, that it is only possible to change assignment of event ORs. |
| INT dcEventProcessingEventType | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4 | INTEGER | read-only | Type of the input event. |
| G32 dcEventProcessingEventSelected | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3 | Gauge32 | read-write | Reference to dcEventProcessingEventIndex in order to select a specific event. |
| dcLvdTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 | not-accessible | Table lists all available LVDs. | |
| dcLvdEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1 | not-accessible | A particular LVD entry. | |
| I32 dcLvdIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1 | Integer32 | not-accessible | Table index. |
| STR dcLvdName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2 | DisplayString | read-only | Name of the LVD. |
| STR dcLvdDisconnectDelay | 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3 | DisplayString | read-write | Time delay from the activation of the source event, after which the LVD event is switched. The value is in the format 'hh:mm:ss'. |
| dcMeasurement | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9 | |||
| dcMeasurementTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 | not-accessible | Table lists all available measurements. | |
| dcMeasurementEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1 | not-accessible | A particular measurement entry. | |
| I32 dcMeasurementIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1 | Integer32 | not-accessible | Table index. |
| STR dcMeasurementName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2 | DisplayString | read-only | Name of the measurement. |
| I32 dcMeasurementValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3 | Integer32 | read-only | Unscaled calibrated value of the measurement. |
| I32 dcMeasurementScaleFactor | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4 | Integer32 | read-only | Scale factor as power of 10 to be multiplied with measurement value. |
| INT dcMeasurementUnit | 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5 | INTEGER | read-only | Unit of the measurement. |
| dcMeterPanel | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10 | |||
| dcMeterPanelEventTable | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 | not-accessible | Table lists all available meter panel events. | |
| dcMeterPanelEventEntry | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1 | not-accessible | A particular meter panel event entry. | |
| I32 dcMeterPanelEventIndex | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1 | Integer32 | not-accessible | Table index. |
| STR dcMeterPanelEventName | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2 | DisplayString | read-only | Name of the event. |
| INT dcMeterPanelEventValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3 | INTEGER | read-only | Value of the event. |
| G32 dcMeterPanelEventHourMeterValue | 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4 | Gauge32 | read-only | Value of the hour meter event. |
| controllerEvents | 1.3.6.1.4.1.20246.2.3.1.1.1.3 | |||
| controllerEventObjects | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1 | |||
| controllerEventsV2 | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0 | |||
| NTF systemNonUrgentAlarm | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1 | The controller reports that one or more elements have changed into none urgent alarm state. | ||
| NTF systemUrgentAlarm | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2 | The controller reports that one or more elements have changed into urgent alarm state. | ||
| NTF systemCriticalAlarm | 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3 | The controller reports that one or more elements have changed into critical alarm state. |
RFC description
Delta Energy ORION (formerly PSC 3) DC power system management; defines objects for battery, charger, and power supply monitoring.
Start monitoring DC power system controller, PSC 3-based, telecom/data center power plant with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.