All MIBs › ORION-BASE-MIB › dcBatteryTestMinDuration
dcBatteryTestMinDuration
Module: ORION-BASE-MIB
OID (symbolic): ORION-BASE-MIB::dcBatteryTestMinDuration
OID (numeric): 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5
Node type: OBJECT-TYPE
Type: Gauge32
Access: read-write
Description: Minimum battery test duration during which time a battery test is not stopped in case of a voltage below the support voltage or a current difference higher than the specified value defined in Idiff measurement is detected.
What is dcBatteryTestMinDuration?
The minimum time a battery test must run, in minutes, during which the test won't be aborted even if voltage drops below the support voltage or the current difference (Idiff) exceeds its threshold, settable read-write. This prevents a test from stopping prematurely on a transient dip.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 snmpwalk -v2c -c public <target> ORION-BASE-MIB::dcBatteryTestMinDuration
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5.1 snmpget -v2c -c public <target> ORION-BASE-MIB::dcBatteryTestMinDuration.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5.1 i <value>
Start monitoring DC power system controller, PSC 3-based, telecom/data center power plant with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ORION-BASE-MIB::dcBatteryTestMinDuration OID value, configure state conditions and alerts, and monitor any DC power system controller, PSC 3-based, telecom/data center power plant from a single console.
OID Breakdown
Upper-level ancestors (16 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.20246 | delta | DESCH-GLOBAL-REG |
| 1.3.6.1.4.1.20246.2 | deschRoot | DESCH-GLOBAL-REG |
| 1.3.6.1.4.1.20246.2.3 | deschProducts | DESCH-GLOBAL-REG |
| 1.3.6.1.4.1.20246.2.3.1 | deschController | DESCH-GLOBAL-REG |
| 1.3.6.1.4.1.20246.2.3.1.1 | deschPsc3 | DESCH-GLOBAL-REG |
| 1.3.6.1.4.1.20246.2.3.1.1.1 | deschPsc3BaseMib | DESCH-PSC3-BASE-MIB |
| 1.3.6.1.4.1.20246.2.3.1.1.1.2 | deschControllerObjects | DESCH-PSC3-BASE-MIB |
| 1.3.6.1.4.1.20246.2.3.1.1.1.2.5 | dcBattery | DESCH-PSC3-BASE-MIB |
| 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2 | dcBatteryTest | DESCH-PSC3-BASE-MIB |
| 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1 | dcBatteryTestParameter | DESCH-PSC3-BASE-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 | dcBatteryTestMinDuration | ORION-BASE-MIB |