ORION-BASE-MIB :: dcRunawayVoltage

MIB Reference — IPNetwork Monitor · Updated September 21, 2026

All MIBs › ORION-BASE-MIB › dcRunawayVoltage

dcRunawayVoltage

Module: ORION-BASE-MIB

OID (symbolic): ORION-BASE-MIB::dcRunawayVoltage

OID (numeric): 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: Charging voltage while Runaway Temp has been exceeded.

What is dcRunawayVoltage?

The reduced charging voltage, in units of 10 mV, applied once the thermal runaway temperature threshold (dcRunawayTemp) has been exceeded, settable read-write, a protective measure to stop feeding a battery that's overheating.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13
snmpwalk -v2c -c public <target> ORION-BASE-MIB::dcRunawayVoltage

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13.1
snmpget -v2c -c public <target> ORION-BASE-MIB::dcRunawayVoltage.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13.1 i <value>

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> dcRunawayVoltage.1

Start monitoring DC power system controller, PSC 3-based, telecom/data center power plant with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ORION-BASE-MIB::dcRunawayVoltage OID value, configure state conditions and alerts, and monitor any DC power system controller, PSC 3-based, telecom/data center power plant from a single console.

OID Breakdown

Upper-level ancestors (14 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.20246deltaDESCH-GLOBAL-REG
1.3.6.1.4.1.20246.2deschRootDESCH-GLOBAL-REG
1.3.6.1.4.1.20246.2.3deschProductsDESCH-GLOBAL-REG
1.3.6.1.4.1.20246.2.3.1deschControllerDESCH-GLOBAL-REG
1.3.6.1.4.1.20246.2.3.1.1deschPsc3DESCH-GLOBAL-REG
1.3.6.1.4.1.20246.2.3.1.1.1deschPsc3BaseMibDESCH-PSC3-BASE-MIB
1.3.6.1.4.1.20246.2.3.1.1.1.2deschControllerObjectsDESCH-PSC3-BASE-MIB
1.3.6.1.4.1.20246.2.3.1.1.1.2.5dcBatteryDESCH-PSC3-BASE-MIB
Numeric OIDNameModule
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8dcTempCompORION-BASE-MIB
1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13dcRunawayVoltageORION-BASE-MIB