Description: Setting this variable to 'start' will initiate the diagnostics test. Setting this variable to 'abort' will stop the diagnostics test if the test is in-progress, otherwise it has no effect. Setting this variable to 'unknown' has no effect. Reading this variable will always result in a return value of 'unknown'.
What is lcUpsTestDiag?
Writing 'start' begins a UPS diagnostics test and 'abort' cancels one in progress; like lcUpsTestBattery, reading it always returns 'unknown' — check lcUpsTestDiagStatus for the actual result.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.7.3 snmpwalk -v2c -c public <target> LIEBERT-SERIES-300-UPS-MIB::lcUpsTestDiag
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.7.3.1 snmpget -v2c -c public <target> LIEBERT-SERIES-300-UPS-MIB::lcUpsTestDiag.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.7.3.1 i <value>
Start monitoring Liebert UPS systems with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-SERIES-300-UPS-MIB::lcUpsTestDiag OID value, configure state conditions and alerts, and monitor any Liebert UPS systems from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.1 | liebertUps | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1 | luExtensions | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1 | luCore | LIEBERT-MICRO-UPS-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.1.1.1.7 | lcUpsTest | LIEBERT-SERIES-300-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1.7.3 | lcUpsTestDiag | LIEBERT-SERIES-300-UPS-MIB |