All MIBs › IPOMANII-MIB
Category: Device Management
Description: IpomaNet II network management device MIB providing SNMP objects for device status and performance monitoring.
Start monitoring vendor-neutral, standards-based MIB, any SNMPv3-capable network device (SNMP engine identity/boot/clock status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.
What Is IPOMANII-MIB?
This is Ingrasys's "IpomaNet II" MIB for network-managed power distribution units (PDUs), part of the vendor's ingrasys/product/pduAgent OID tree. It exposes device identification (manufacturer, model, agent software version) and agent-level time/NTP synchronization configuration. It is used to monitor hardware and software status—tracking the agent's software version and NTP time-synchronization state (whether time comes from NTP, the configured server, and time zone/DST settings), which matters for accurate event timestamping on the PDU. No explicit external MIB dependency is stated, though it likely coexists with standard PDU/UPS MIBs in rack power-management deployments. It is deployed on Ingrasys-manufactured networked PDUs in data center rack power-monitoring setups. Engineers can download the IPOMANII-MIB file directly to load it into their MIB browser.
IPNetwork Monitor allows you to monitor SNMP objects defined in IPOMANII-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.
Supported Devices
- Ingrasys networked power distribution units (PDUs)
Monitoring Examples
ipmIdentManufacturer, ipmIdentModel, and ipmIdentAgentSoftwareVersion let an admin confirm the exact PDU hardware/firmware in use, while ipmAgentTimeDate/ipmAgentTimeTime combined with ipmAgentTimerFromNtp and ipmAgentNtpIpAddress reveal whether the device's clock is properly synced to an NTP server. An admin would also check ipmAgentNetworkIpAdress to confirm the management IP is correct; a stale ipmAgentTimeDate despite ipmAgentTimerFromNtp being enabled would indicate an NTP sync failure.
What Can Be Monitored
- PDU manufacturer/model/agent software version
- NTP sync status and server address
- time zone/daylight saving configuration
- device network IP address
- system date/time
This MIB depends on
Related MIBs
Imported Objects
From RFC-1212
| OBJECT-TYPE |
From RFC-1215
| TRAP-TYPE |
From RFC1155-SMI
| enterprises |
From RFC1213-MIB
| DisplayString |
OIDs
| OID symbolic | OID numeric | Type | Access | Description |
|---|---|---|---|---|
| ingrasys | 1.3.6.1.4.1.2468 | |||
| product | 1.3.6.1.4.1.2468.1 | |||
| pduAgent | 1.3.6.1.4.1.2468.1.4 | |||
| iPoManII | 1.3.6.1.4.1.2468.1.4.2 | |||
| ipmObjects | 1.3.6.1.4.1.2468.1.4.2.1 | |||
| ipmIdent | 1.3.6.1.4.1.2468.1.4.2.1.1 | |||
| STR ipmIdentManufacturer | 1.3.6.1.4.1.2468.1.4.2.1.1.1 | DisplayString | read-write | The name of manufacturer. |
| STR ipmIdentModel | 1.3.6.1.4.1.2468.1.4.2.1.1.2 | DisplayString | read-write | The Model designation of device. |
| STR ipmIdentAgentSoftwareVersion | 1.3.6.1.4.1.2468.1.4.2.1.1.3 | DisplayString | read-only | The firmware version of the device. |
| STR ipmIdentName | 1.3.6.1.4.1.2468.1.4.2.1.1.4 | DisplayString | read-write | A description of this device. |
| ipmAgent | 1.3.6.1.4.1.2468.1.4.2.1.2 | |||
| ipmAgentConfig | 1.3.6.1.4.1.2468.1.4.2.1.2.1 | |||
| INT ipmAgentMibVersion | 1.3.6.1.4.1.2468.1.4.2.1.2.1.1 | INTEGER | read-only | The Mib Version implemented on this device. |
| ipmAgentLog | 1.3.6.1.4.1.2468.1.4.2.1.2.1.4 | |||
| INT pduAgentDataLogInterval | 1.3.6.1.4.1.2468.1.4.2.1.2.1.4.1 | INTEGER | read-write | The interval of the updation of the data log. The value is in seconds |
| ipmAgentControl | 1.3.6.1.4.1.2468.1.4.2.1.2.1.5 | |||
| INT ipmAgentControlDefault | 1.3.6.1.4.1.2468.1.4.2.1.2.1.5.1 | INTEGER | read-write | Reset all parameters of the agent to default value. |
| INT ipmAgentControlRestart | 1.3.6.1.4.1.2468.1.4.2.1.2.1.5.2 | INTEGER | read-write | Restart the agent. |
| ipmAgentTrap | 1.3.6.1.4.1.2468.1.4.2.1.2.1.6 | |||
| INT ipmAgentTrapRetryCount | 1.3.6.1.4.1.2468.1.4.2.1.2.1.6.1 | INTEGER | read-write | The count of repeat traps send to NMS before trap acknowledgement received. |
| INT ipmAgentTrapRetryTime | 1.3.6.1.4.1.2468.1.4.2.1.2.1.6.2 | INTEGER | read-write | The time interval in seconds between retry traps sned to NMS. |
| INT ipmAgentTrapAckSignature | 1.3.6.1.4.1.2468.1.4.2.1.2.1.6.3 | INTEGER | read-write | The signature of trap acknowledgement. |
| ipmAgentTrapsReceiversTable | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7 | not-accessible | A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers | |
| ipmAgentTrapsReceiversEntry | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1 | not-accessible | The managers to send traps to. | |
| INT trapsIndex | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1.1 | INTEGER | read-only | The index to a trap receiver entry. |
| IP trapsReceiverAddr | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1.2 | IpAddress | read-write | The IP address of the manager to send a trap to. |
| STR receiverCommunityString | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1.3 | DisplayString | read-write | The community name to use in the trap when sent to the manager. |
| INT receiverNmsType | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1.4 | INTEGER | read-write | The trap group that NMS desired. |
| INT receiverSeverityLevel | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1.5 | INTEGER | read-write | The severity level of traps to be received by this manager. |
| STR receiverDescription | 1.3.6.1.4.1.2468.1.4.2.1.2.1.7.1.6 | DisplayString | read-write | Description of trap receivers |
| ipmAgentAccessControlTable | 1.3.6.1.4.1.2468.1.4.2.1.2.1.8 | not-accessible | A list of managers which can access the device with private community string. | |
| ipmAgentAccessControlEntry | 1.3.6.1.4.1.2468.1.4.2.1.2.1.8.1 | not-accessible | The managers. | |
| INT accessIndex | 1.3.6.1.4.1.2468.1.4.2.1.2.1.8.1.1 | INTEGER | read-only | The index to a access control entry. |
| IP accessControlAddr | 1.3.6.1.4.1.2468.1.4.2.1.2.1.8.1.2 | IpAddress | read-write | The IP address of the manager to access the device. |
| INT accessControlMode | 1.3.6.1.4.1.2468.1.4.2.1.2.1.8.1.3 | INTEGER | read-write | Access type, only read/Write access type can change parameter of the device. |
| ipmAgentTime | 1.3.6.1.4.1.2468.1.4.2.1.2.2 | |||
| STR ipmAgentTimeDate | 1.3.6.1.4.1.2468.1.4.2.1.2.2.1 | DisplayString | read-write | The date in agent, format is (dd/mm/yyyy) |
| STR ipmAgentTimeTime | 1.3.6.1.4.1.2468.1.4.2.1.2.2.2 | DisplayString | read-write | The time in agent, format is (hh:mm:ss) |
| INT ipmAgentTimerFromNtp | 1.3.6.1.4.1.2468.1.4.2.1.2.2.3 | INTEGER | read-write | Enable or disable the agent to synchronize date/time with NTP server. |
| IP ipmAgentNtpIpAddress | 1.3.6.1.4.1.2468.1.4.2.1.2.2.4 | IpAddress | read-write | The ip address of NTP server. |
| INT ipmAgentNtpTimeZone | 1.3.6.1.4.1.2468.1.4.2.1.2.2.5 | INTEGER | read-write | Time Zone to use when synchronize with NTP server. |
| INT ipmAgentDayLightSaving | 1.3.6.1.4.1.2468.1.4.2.1.2.2.6 | INTEGER | read-write | Enable/disable the Day Light Saving when synchronize with NTP server. |
| ipmAgentNetwork | 1.3.6.1.4.1.2468.1.4.2.1.2.3 | |||
| ipmAgentNetworkIp | 1.3.6.1.4.1.2468.1.4.2.1.2.3.1 | |||
| IP ipmAgentNetworkIpAdress | 1.3.6.1.4.1.2468.1.4.2.1.2.3.1.1 | IpAddress | read-write | The ip address that NMS can identify the managed device. |
| IP ipmAgentNetworkIpGateway | 1.3.6.1.4.1.2468.1.4.2.1.2.3.1.2 | IpAddress | read-write | The default gateway that allow device managed through routers. |
| IP ipmAgentNetworkIpSubnet | 1.3.6.1.4.1.2468.1.4.2.1.2.3.1.3 | IpAddress | read-write | Internet address subnet mask |
| INT ipmAgentNetworkDhcpControl | 1.3.6.1.4.1.2468.1.4.2.1.2.3.2 | INTEGER | read-write | Enable/disable DHCP protocol |
| INT ipmAgentNetworkPingControl | 1.3.6.1.4.1.2468.1.4.2.1.2.3.3 | INTEGER | read-write | Enable/disable to response to PING request. |
| INT ipmAgentNetworkTftpControl | 1.3.6.1.4.1.2468.1.4.2.1.2.3.4 | INTEGER | read-write | Enable/disable TFTP protocol |
| ipmAgentNetworkTelnet | 1.3.6.1.4.1.2468.1.4.2.1.2.3.5 | |||
| INT ipmAgentTelnetControl | 1.3.6.1.4.1.2468.1.4.2.1.2.3.5.1 | INTEGER | read-write | Enable/disable Telnet protocol. |
| INT ipmAgentTelnetPort | 1.3.6.1.4.1.2468.1.4.2.1.2.3.5.2 | INTEGER | read-write | The TCP port for telnet |
| ipmAgentNetworkHttp | 1.3.6.1.4.1.2468.1.4.2.1.2.3.6 | |||
| INT ipmAgentHttpControl | 1.3.6.1.4.1.2468.1.4.2.1.2.3.6.1 | INTEGER | read-write | Enable/disable HTTP protocol. |
| INT ipmAgentHttpPort | 1.3.6.1.4.1.2468.1.4.2.1.2.3.6.2 | INTEGER | read-write | The TCP port for HTTP. |
| ipmAgentNetworkSnmp | 1.3.6.1.4.1.2468.1.4.2.1.2.3.7 | |||
| INT ipmAgentSnmpControl | 1.3.6.1.4.1.2468.1.4.2.1.2.3.7.1 | INTEGER | read-write | Enable/disable SNMP protocol. |
| INT ipmAgentSnmpPort | 1.3.6.1.4.1.2468.1.4.2.1.2.3.7.2 | INTEGER | read-write | The UDP port for SNMP. |
| ipmDevice | 1.3.6.1.4.1.2468.1.4.2.1.3 | |||
| ipmDeviceInlet | 1.3.6.1.4.1.2468.1.4.2.1.3.1 | |||
| INT ipmDeviceInletNumber | 1.3.6.1.4.1.2468.1.4.2.1.3.1.1 | INTEGER | read-only | The inlet number on this device. |
| ipmDeviceInletConfigTable | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2 | not-accessible | A list of inlet on this device. | |
| ipmDeviceInletConfigEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1 | not-accessible | The inlet number of device. | |
| INT inletConfigIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.1 | INTEGER | read-only | The index to a access inlet configuration table. |
| STR inletConfigDesc | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.2 | DisplayString | read-write | A Description of inlet of device. |
| INT inletConfigVoltageHigh | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.3 | INTEGER | read-write | The Inlet high voltage threshold, in volts. |
| INT inletConfigVoltageHighAction | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.4 | INTEGER | read-write | Reaction of the device when inlet voltage higher than set point. |
| INT inletConfigVoltageLow | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.5 | INTEGER | read-write | The Inlet low voltage threshold, in volts. |
| INT inletConfigVoltageLowAction | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.6 | INTEGER | read-write | Reaction of the device when inlet voltage lower than set point. |
| INT inletConfigCurrentHigh | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.7 | INTEGER | read-write | The Inlet low voltage threshold, in 0.1 amps. |
| INT inletConfigCurrentHighAction | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.8 | INTEGER | read-write | Reaction of the device when inlet current higher than set point. |
| INT inletConfigFrequencyHigh | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.9 | INTEGER | read-write | The Inlet high frequency threshold, in hz. |
| INT inletConfigfrequencyHighAction | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.10 | INTEGER | read-write | Reaction of the device when inlet frequency higher than set point. |
| INT inletConfigFrequencyLow | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.11 | INTEGER | read-write | The Inlet low frequency threshold, in hz. |
| INT inletConfigfrequencyLowAction | 1.3.6.1.4.1.2468.1.4.2.1.3.1.2.1.12 | INTEGER | read-write | Reaction of the device when inlet frequency lower than set point. |
| ipmDeviceInletStatusTable | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3 | not-accessible | A list of inlet on this device. | |
| ipmDeviceInletStatusEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1 | not-accessible | The inlet number of device. | |
| INT inletStatusIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1.1 | INTEGER | read-only | The index to a access inlet configuration table. |
| INT inletStatusVoltage | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1.2 | INTEGER | read-only | The Inlet Voltage in 0.1 volts |
| INT inletStatusCurrent | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1.3 | INTEGER | read-only | The Inlet Current in 0.001 Amp. |
| INT inletStatusFrequency | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1.4 | INTEGER | read-only | The Inlet Frequency in 0.1 Hz |
| INT inletStatusKwatt | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1.5 | INTEGER | read-only | The Inlet Kwatt in 0.1 KW/H |
| INT inletStatusWH | 1.3.6.1.4.1.2468.1.4.2.1.3.1.3.1.6 | INTEGER | read-only | The Inlet Kwatt in 0.1 W/H |
| INT inletWattReset | 1.3.6.1.4.1.2468.1.4.2.1.3.1.4 | INTEGER | read-write | Reset inlet kw. |
| ipmDeviceOutlet | 1.3.6.1.4.1.2468.1.4.2.1.3.2 | |||
| INT ipmDeviceOutletNumber | 1.3.6.1.4.1.2468.1.4.2.1.3.2.1 | INTEGER | read-only | The outlet number on this device. |
| ipmDeviceOutletConfigTable | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2 | not-accessible | A list of outlet on this device. | |
| ipmDeviceOutletConfigEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1 | not-accessible | The inlet number of device. | |
| INT outletConfigIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.1 | INTEGER | read-only | The index to a access inlet configuration table. |
| STR outletConfigDesc | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.2 | DisplayString | read-write | A Description of outlet of device. |
| STR outletConfigLocation | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.3 | DisplayString | read-write | Location of device connectted to this outlet. |
| INT outletConfigOnDelay | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.4 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT outletConfigOffDelay | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.5 | INTEGER | read-write | The delay time before turn off tis outlet, in seconds. |
| INT outletConfigCurrentHigh | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.6 | INTEGER | read-write | The outlet high current threshold, in amp. |
| INT outletConfigCurrentHighAction | 1.3.6.1.4.1.2468.1.4.2.1.3.2.2.1.7 | INTEGER | read-write | Reaction of the device when outlet current higher than set point. |
| ipmDeviceOutletStatusTable | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3 | not-accessible | A list of outlet on this device. | |
| ipmDeviceOutletStatusEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1 | not-accessible | The outlet number of device. | |
| INT outletStatusIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT outletStatusStatus | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.2 | INTEGER | read-only | Outlet state |
| INT outletStatusCurrent | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.3 | INTEGER | read-only | The outlet Current in 0.001 Amp. |
| INT outletStatusKwatt | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.4 | INTEGER | read-only | The outlet Kwatt in 0.001 KW/H. |
| INT outletStatusWH | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.5 | INTEGER | read-only | The outlet Watt in 0.1 W/H. |
| INT outletStatusStateTime | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.6 | INTEGER | read-only | Time in seconds since the outlet changed to current state. |
| INT outletStatusTimeToGo | 1.3.6.1.4.1.2468.1.4.2.1.3.2.3.1.7 | INTEGER | read-only | Remain time the outlet state will be changed by agent, in seconds |
| ipmDeviceOutletControlTable | 1.3.6.1.4.1.2468.1.4.2.1.3.2.4 | not-accessible | A list of outlet on this device. | |
| ipmDeviceOutletControlEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.2.4.1 | not-accessible | The outlet number of device. | |
| INT outletControlIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.2.4.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT outletControlControl | 1.3.6.1.4.1.2468.1.4.2.1.3.2.4.1.2 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT ipmDeviceOutletControlAll | 1.3.6.1.4.1.2468.1.4.2.1.3.2.5 | INTEGER | read-write | Set to control all outlets perform action as requested. |
| INT ipmDeviceOutletWattReset | 1.3.6.1.4.1.2468.1.4.2.1.3.2.6 | INTEGER | read-write | Reset outlet kw. |
| ipmDeviceCcOut | 1.3.6.1.4.1.2468.1.4.2.1.3.3 | |||
| INT ipmDeviceCcOutNumber | 1.3.6.1.4.1.2468.1.4.2.1.3.3.1 | INTEGER | read-only | The contact closure output number on this device. |
| ipmDeviceCcOutConfigTable | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2 | not-accessible | A list of contact closure output on this device. | |
| ipmDeviceCcOutConfigEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2.1 | not-accessible | The CC number of device. | |
| INT ccOutConfigIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2.1.1 | INTEGER | read-only | The index to access contact closure output configuration table. |
| STR ccOutConfigDesc | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2.1.2 | DisplayString | read-write | A Description of a contact closure output of device. |
| INT ccOutConfigEventAction | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2.1.3 | INTEGER | read-write | Enable/disble the contact closure output to react to events. |
| INT ccOutConfigCloseDelay | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2.1.4 | INTEGER | read-write | The delay time in seconds when the contact closure output set to close. |
| INT ccOutConfigOpenDelay | 1.3.6.1.4.1.2468.1.4.2.1.3.3.2.1.5 | INTEGER | read-write | The delay time in seconds when the contact closure output set to open. |
| ipmDeviceCcOutStatusTable | 1.3.6.1.4.1.2468.1.4.2.1.3.3.3 | not-accessible | A list of contact closure output on this device. | |
| ipmDeviceCcOutStatusEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.3.3.1 | not-accessible | The CC number of device. | |
| INT ccOutStatusIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.3.3.1.1 | INTEGER | read-only | The index to access contact closure output configuration table. |
| INT ccOutStatusStatus | 1.3.6.1.4.1.2468.1.4.2.1.3.3.3.1.2 | INTEGER | read-only | State of a contact closure output of device. |
| INT ccOutStatusTimeOnState | 1.3.6.1.4.1.2468.1.4.2.1.3.3.3.1.3 | INTEGER | read-only | Time in seconds since the contact closure output changed to current state. |
| ipmDeviceCcOutControlTable | 1.3.6.1.4.1.2468.1.4.2.1.3.3.4 | not-accessible | A list of contact closure output on this device. | |
| ipmDeviceCcOutControlEntry | 1.3.6.1.4.1.2468.1.4.2.1.3.3.4.1 | not-accessible | The outlet number of device. | |
| INT ccOutControlIndex | 1.3.6.1.4.1.2468.1.4.2.1.3.3.4.1.1 | INTEGER | read-only | The index to a access contact closure output configuration table. |
| INT ccOutControlControl | 1.3.6.1.4.1.2468.1.4.2.1.3.3.4.1.2 | INTEGER | read-write | Set to control the contact closure output perform action as requested. |
| ipmSlave | 1.3.6.1.4.1.2468.1.4.2.1.4 | |||
| ipmSlaveState | 1.3.6.1.4.1.2468.1.4.2.1.4.1 | |||
| ipmSlaveStateTable | 1.3.6.1.4.1.2468.1.4.2.1.4.1.1 | not-accessible | A list of outlet on this device. | |
| ipmSlaveStateEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.1.1.1 | not-accessible | The outlet number of device. | |
| INT slaveStateIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.1.1.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveStateControl01 | 1.3.6.1.4.1.2468.1.4.2.1.4.1.1.1.2 | INTEGER | read-only | Set to control the outlet perform action as requested to slave outlet A |
| ipmSlaveInlet | 1.3.6.1.4.1.2468.1.4.2.1.4.2 | |||
| ipmSlaveInletStatus | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1 | |||
| ipmDeviceSlaveInletStatusTable | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1 | not-accessible | A list of inlet on this device. | |
| ipmDeviceSlaveInletStatusEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1 | not-accessible | The inlet number of device. | |
| INT inletSlaveStatusIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.1 | INTEGER | read-only | The index to a access inlet configuration table. |
| INT inletSlaveStatusVoltage | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.2 | INTEGER | read-only | The Inlet Voltage in 0.1 volts |
| INT inletSlaveStatusCurrent | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.3 | INTEGER | read-only | The Inlet Current in 0.001 Amp. |
| INT inletSlaveStatusFrequency | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.4 | INTEGER | read-only | The Inlet Frequency in 0.1 Hz |
| INT inletSlaveStatusKwatt | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.5 | INTEGER | read-only | The Inlet Kwatt in 0.001 KW/H |
| INT inletSlaveStatusWH | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.6 | INTEGER | read-only | The Inlet Kwatt in 0.001 KW/H |
| INT inletSlaveStatusVoltage2 | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.7 | INTEGER | read-only | The Inlet Voltage in 0.1 volts |
| INT inletSlaveStatusCurrent2 | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.8 | INTEGER | read-only | The Inlet Current in 0.001 Amp. |
| INT inletSlaveStatusFrequency2 | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.9 | INTEGER | read-only | The Inlet Frequency in 0.1 Hz |
| INT inletSlaveStatusKwatt2 | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.10 | INTEGER | read-only | The Inlet Kwatt in 0.001 KW/H |
| INT inletSlaveStatusWH2 | 1.3.6.1.4.1.2468.1.4.2.1.4.2.1.1.1.11 | INTEGER | read-only | The Inlet Kwatt in 0.001 KW/H |
| ipmSlaveInletConfig | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2 | |||
| ipmDeviceslaveInletConfigTable | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1 | not-accessible | A list of inlet on this device. | |
| ipmDeviceslaveInletConfigEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1.1 | not-accessible | The inlet number of device. | |
| INT slaveInletConfigIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1.1.1 | INTEGER | read-only | The index to a access inlet configuration table. |
| INT slaveInletConfigVoltageHigh | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1.1.2 | INTEGER | read-write | The Inlet high voltage threshold, in volts. |
| INT slaveInletConfigVoltageLow | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1.1.3 | INTEGER | read-write | The Inlet low voltage threshold, in volts. |
| INT slaveInlet2ConfigVoltageHigh | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1.1.4 | INTEGER | read-write | The Inlet 2 high voltage threshold, in volts. |
| INT slaveInlet2ConfigVoltageLow | 1.3.6.1.4.1.2468.1.4.2.1.4.2.2.1.1.5 | INTEGER | read-write | The Inlet low voltage threshold, in volts. |
| ipmSlaveOutlet | 1.3.6.1.4.1.2468.1.4.2.1.4.3 | |||
| ipmSlaveOutletConfig | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1 | |||
| ipmSlaveDeviceOutletNameTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletNameEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletNameIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| STR slaveOutletName01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.2 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.3 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.4 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.5 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.6 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.7 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.8 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.9 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.10 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.11 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.12 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletName12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.1.1.13 | DisplayString | read-write | A Description of a outlet name of device. |
| ipmSlaveDeviceOutletLocationTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletLocationEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletLocationIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| STR slaveOutletLocation01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.2 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.3 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.4 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.5 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.6 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.7 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.8 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.9 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.10 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.11 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.12 | DisplayString | read-write | A Description of a outlet name of device. |
| STR slaveOutletLocation12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.2.1.13 | DisplayString | read-write | A Description of a outlet name of device. |
| ipmSlaveDeviceOutletOnTimeTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletOnTimeEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletOnTimeIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletOnTime01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.2 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.3 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.4 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.5 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.6 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.7 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.8 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.9 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.10 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.11 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.12 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOnTime12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.3.1.13 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| ipmSlaveDeviceOutletOffTimeTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletOffTimeEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletOffTimeIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletOffTime01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.2 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.3 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.4 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.5 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.6 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.7 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.8 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.9 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.10 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.11 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.12 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| INT slaveOutletOffTime12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.4.1.13 | INTEGER | read-write | The delay time before turn on tis outlet, in seconds. |
| ipmSlaveDeviceOutletCurrThTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletCurrThEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletCurrThIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletCurrTh01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.2 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.3 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.4 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.5 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.6 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.7 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.8 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.9 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.10 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.11 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.12 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| INT slaveOutletCurrTh12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.1.5.1.13 | INTEGER | read-write | The Outlet Current Threshold ,in 0.1 Amp. |
| ipmSlaveOutletStatus | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2 | |||
| ipmSlaveDeviceOutletCurrentTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletCurrentEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletCurrentIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletCurrent01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.2 | INTEGER | read-only | The outlet A Current in 0.001 Amp. |
| INT slaveOutletCurrent02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.3 | INTEGER | read-only | The outlet B Current in 0.001 Amp. |
| INT slaveOutletCurrent03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.4 | INTEGER | read-only | The outlet C Current in 0.001 Amp. |
| INT slaveOutletCurrent04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.5 | INTEGER | read-only | The outlet D Current in 0.001 Amp. |
| INT slaveOutletCurrent05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.6 | INTEGER | read-only | The outlet E Current in 0.001 Amp. |
| INT slaveOutletCurrent06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.7 | INTEGER | read-only | The outlet F Current in 0.001 Amp. |
| INT slaveOutletCurrent07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.8 | INTEGER | read-only | The outlet G Current in 0.001 Amp. |
| INT slaveOutletCurrent08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.9 | INTEGER | read-only | The outlet H Current in 0.001 Amp. |
| INT slaveOutletCurrent09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.10 | INTEGER | read-only | The outlet I Current in 0.001 Amp. |
| INT slaveOutletCurrent10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.11 | INTEGER | read-only | The outlet J Current in 0.001 Amp. |
| INT slaveOutletCurrent11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.12 | INTEGER | read-only | The outlet K Current in 0.001 Amp. |
| INT slaveOutletCurrent12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.1.1.13 | INTEGER | read-only | The outlet L Current in 0.001 Amp. |
| ipmSlaveDeviceOutletWattTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletWattEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletWattIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletWatt01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.2 | INTEGER | read-only | The outlet A Watt in 0.1 W/H. |
| INT slaveOutletWatt02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.3 | INTEGER | read-only | The outlet B Watt in 0.1 W/H. |
| INT slaveOutletWatt03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.4 | INTEGER | read-only | The outlet C Watt in 0.1 W/H. |
| INT slaveOutletWatt04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.5 | INTEGER | read-only | The outlet D Watt in 0.1 W/H. |
| INT slaveOutletWatt05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.6 | INTEGER | read-only | The outlet E Watt in 0.1 W/H. |
| INT slaveOutletWatt06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.7 | INTEGER | read-only | The outlet F Watt in 0.1 W/H. |
| INT slaveOutletWatt07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.8 | INTEGER | read-only | The outlet G Watt in 0.1 W/H. |
| INT slaveOutletWatt08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.9 | INTEGER | read-only | The outlet H Watt in 0.1 W/H. |
| INT slaveOutletWatt09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.10 | INTEGER | read-only | The outlet I Watt in 0.1 W/H. |
| INT slaveOutletWatt10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.11 | INTEGER | read-only | The outlet J Watt in 0.1 W/H. |
| INT slaveOutletWatt11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.12 | INTEGER | read-only | The outlet K Watt in 0.1 W/H. |
| INT slaveOutletWatt12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.2.1.13 | INTEGER | read-only | The outlet L Watt in 0.1 W/H. |
| ipmSlaveDeviceOutletKwattTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletKwattEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletKwattIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletKwatt01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.2 | INTEGER | read-only | The outlet A Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.3 | INTEGER | read-only | The outlet B Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.4 | INTEGER | read-only | The outlet C Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.5 | INTEGER | read-only | The outlet D Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.6 | INTEGER | read-only | The outlet E Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.7 | INTEGER | read-only | The outlet F Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.8 | INTEGER | read-only | The outlet G Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.9 | INTEGER | read-only | The outlet H Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.10 | INTEGER | read-only | The outlet I Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.11 | INTEGER | read-only | The outlet J Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.12 | INTEGER | read-only | The outlet K Kwatt in 0.001 KW/H. |
| INT slaveOutletKwatt12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.2.3.1.13 | INTEGER | read-only | The outlet L Kwatt in 0.001 KW/H. |
| ipmSlaveOutletAction | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3 | |||
| ipmSlaveDeviceOutletActionTable | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1 | not-accessible | A list of outlet on this device. | |
| ipmSlaveDeviceOutletActionEntry | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1 | not-accessible | The outlet number of device. | |
| INT slaveOutletActionIndex | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.1 | INTEGER | read-only | The index to a access outlet configuration table. |
| INT slaveOutletAction01 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.2 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction02 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.3 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction03 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.4 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction04 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.5 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction05 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.6 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction06 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.7 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction07 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.8 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction08 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.9 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction09 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.10 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction10 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.11 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction11 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.12 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| INT slaveOutletAction12 | 1.3.6.1.4.1.2468.1.4.2.1.4.3.3.1.1.13 | INTEGER | read-write | Set to control the outlet perform action as requested. |
| ipmEnv | 1.3.6.1.4.1.2468.1.4.2.1.5 | |||
| ipmEnvEmd | 1.3.6.1.4.1.2468.1.4.2.1.5.1 | |||
| ipmEnvEmdStatus | 1.3.6.1.4.1.2468.1.4.2.1.5.1.1 | |||
| INT ipmEnvEmdStatusEmdType | 1.3.6.1.4.1.2468.1.4.2.1.5.1.1.1 | INTEGER | read-only | EMD Type. |
| INT ipmEnvEmdStatusTemperature | 1.3.6.1.4.1.2468.1.4.2.1.5.1.1.2 | INTEGER | read-only | EMD Temperature in 0.1 degree C. |
| INT ipmEnvEmdStatusHumidity | 1.3.6.1.4.1.2468.1.4.2.1.5.1.1.3 | INTEGER | read-only | EMD Humidity in 0.1%. |
| INT ipmEnvEmdStatusAlarm1 | 1.3.6.1.4.1.2468.1.4.2.1.5.1.1.4 | INTEGER | read-only | EMD Alarm-1 state. |
| INT ipmEnvEmdStatusAlarm2 | 1.3.6.1.4.1.2468.1.4.2.1.5.1.1.5 | INTEGER | read-only | EMD Alarm-2 state. |
| ipmEnvEmdConfig | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2 | |||
| INT ipmEnvEmdConfigEmdPresence | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.1 | INTEGER | read-write | Configure the EMD presence by auto-detect or not exist (disabled). |
| STR ipmEnvEmdConfigEmdName | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.2 | DisplayString | read-write | The name of Emd. |
| ipmEnvEmdConfigTemp | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3 | |||
| STR ipmEnvEmdConfigTempName | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3.1 | DisplayString | read-write | The name of EMD Temperature sensor. |
| INT ipmEnvEmdConfigTempHighSetPoint | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3.2 | INTEGER | read-write | EMD Temperature set point high, alarm will active when temperature over this value, in degree C. |
| INT ipmEnvEmdConfigTempHighStatus | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3.3 | INTEGER | read-write | Enabled/disabled the high setpoint be applied or not |
| INT ipmEnvEmdConfigTempLowSetPoint | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3.4 | INTEGER | read-write | EMD Temperature set point high, alarm will active when temperature under this value, in degree C. |
| INT ipmEnvEmdConfigTempLowStatus | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3.5 | INTEGER | read-write | Enabled/disabled the low setpoint be applied or not |
| INT ipmEnvEmdConfigTempOffset | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.3.6 | INTEGER | read-write | Offset of temperature in degree C to adjust EMD temperature measurement. |
| ipmEnvEmdConfigHumi | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4 | |||
| STR ipmEnvEmdConfigHumiName | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4.1 | DisplayString | read-write | The name of EMD Humidity. |
| INT ipmEnvEmdConfigHumiHighSetPoint | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4.2 | INTEGER | read-write | EMD humidity set point high, alarm will active when humidity over this value, in %. |
| INT ipmEnvEmdConfigHumiHighStatus | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4.3 | INTEGER | read-write | Enabled/disabled the high setpoint be applied or not |
| INT ipmEnvEmdConfigHumiLowSetPoint | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4.4 | INTEGER | read-write | EMD humidity set point low, alarm will active when humidity under this value, in %. |
| INT ipmEnvEmdConfigHumiLowStatus | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4.5 | INTEGER | read-write | Enabled/disabled the high setpoint be applied or not |
| INT ipmEnvEmdConfigHumiOffset | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.4.6 | INTEGER | read-write | Emd Hum Offset; |
| ipmEnvEmdConfigAlarm1 | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.5 | |||
| STR ipmEnvEmdConfigAlarm1Name | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.5.1 | DisplayString | read-write | The name of EMD Alarm-1. |
| INT ipmEnvEmdConfigAlarm1Type | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.5.2 | INTEGER | read-write | EMD Alarm-1 type |
| ipmEnvEmdConfigAlarm2 | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.6 | |||
| STR ipmEnvEmdConfigAlarm2Name | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.6.1 | DisplayString | read-write | The name of EMD Alarm-2. |
| INT ipmEnvEmdConfigAlarm2Type | 1.3.6.1.4.1.2468.1.4.2.1.5.1.2.6.2 | INTEGER | read-write | EMD Alarm-2 type |
| ipmTraps | 1.3.6.1.4.1.2468.1.4.2.2 | |||
| NTF ipmInletVoltageTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.1 | CRITICAL: The input voltage over high threshold. | ||
| NTF ipmInletVoltageNotTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.2 | WARNING: The input voltage return from over high threshold. | ||
| NTF ipmInletVoltageTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.3 | CRITICAL: The input voltage under low threshold. | ||
| NTF ipmInletVoltageNotTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.4 | WARNING: The input voltage return from under low threshold. | ||
| NTF ipmInletCurrentTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.5 | CRITICAL: The input current over high threshold. | ||
| NTF ipmInletCurrentNotTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.6 | WARNING: The input current return from over high threshold. | ||
| NTF ipmInletFrequencyTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.7 | CRITICAL: The input frequency over high threshold. | ||
| NTF ipmInletFrequencyNotTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.8 | WARNING: The input frequency return from over high threshold. | ||
| NTF ipmInletFrequencyTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.9 | CRITICAL: The input frequency under low threshold. | ||
| NTF ipmInletFrequencyNotTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.10 | WARNING: The input frequency return from under low threshold. | ||
| NTF ipmOutletCurrentTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.11 | CRITICAL: The output current of outlet over high threshold. | ||
| NTF ipmOutletCurrentNotTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.12 | WARNING: The output current of outlet return from over high threshold. | ||
| NTF ipmOutletStateChanged | 1.3.6.1.4.1.2468.1.4.2.2.0.13 | INFORMATION: The outlet state had changed from on to off, or from off to on. | ||
| NTF ipmEmdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.14 | INFORMATION: emd Temperature Not High. | ||
| NTF ipmEmdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.15 | WARNING: emd Temperature Too High. | ||
| NTF ipmEmdTemperatureNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.16 | INFORMATION: emd Temperature Not Low. | ||
| NTF ipmEmdTemperatureTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.17 | WARNING: emd Temperature Too Low. | ||
| NTF ipmEmdHumidityNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.18 | INFORMATION: emd Humidity Not High. | ||
| NTF ipmEmdHumidityTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.19 | WARNING: emd Humidity Too High. | ||
| NTF ipmEmdHumidityNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.20 | INFORMATION: emd Humidity Not Low. | ||
| NTF ipmEmdHumidityTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.21 | WARNING: emd Humidity Too Low. | ||
| NTF ipmEmdAlarm1Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.22 | INFORMATION: emd Alarm1 Normal. | ||
| NTF ipmEmdAlarm1Active | 1.3.6.1.4.1.2468.1.4.2.2.0.23 | WARNING: emd Alarm1 Active. | ||
| NTF ipmEmdAlarm2Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.24 | INFORMATION: emd Alarm2 Normal. | ||
| NTF ipmEmdAlarm2Active | 1.3.6.1.4.1.2468.1.4.2.2.0.25 | WARNING: emd Alarm2 Active. | ||
| NTF ipmSlave01Inlet01OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.26 | CRITICAL: The Slave01 input01 voltage over high threshold. | ||
| NTF ipmSlave01Inlet01NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.27 | CRITICAL: The Slave01 input01 voltage Not over high threshold. | ||
| NTF ipmSlave01Inlet02OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.28 | CRITICAL: The Slave01 input02 voltage over high threshold. | ||
| NTF ipmSlave01Inlet02NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.29 | CRITICAL: The Slave01 input02 voltage Not over high threshold. | ||
| NTF ipmSlave01Inlet01UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.30 | CRITICAL: The Slave01 input01 voltage under low threshold. | ||
| NTF ipmSlave01Inlet01NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.31 | CRITICAL: The Slave01 input01 voltage Not under low threshold. | ||
| NTF ipmSlave01Inlet02UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.32 | CRITICAL: The Slave01 input02 voltage under low threshold. | ||
| NTF ipmSlave01Inlet02NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.33 | CRITICAL: The Slave01 input02 voltage Not under low threshold. | ||
| NTF ipmSlave01Inlet01CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.34 | CRITICAL: The Slave01 input01 current over high threshold. | ||
| NTF ipmSlave01Inlet01NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.35 | CRITICAL: The Slave01 input01 current not over high threshold. | ||
| NTF ipmSlave01Inlet02CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.36 | CRITICAL: The Slave01 input02 current over high threshold. | ||
| NTF ipmSlave01Inlet02NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.37 | CRITICAL: The Slave01 input02 current not over high threshold. | ||
| NTF ipmSlave01EmdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.38 | INFORMATION: The Slave01 emd Temperature Not High. | ||
| NTF ipmSlave01EmdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.39 | WARNING: The Slave01 emd Temperature Too High. | ||
| NTF ipmSlave01EmdTemperatureNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.40 | INFORMATION: The Slave01 emd Temperature Not Low. | ||
| NTF ipmSlave01EmdTemperatureTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.41 | WARNING: The Slave01 emd Temperature Too Low. | ||
| NTF ipmSlave01EmdHumidityNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.42 | INFORMATION: The Slave01 emd Humidity Not High. | ||
| NTF ipmSlave01EmdHumidityTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.43 | WARNING: The Slave01 emd Humidity Too High. | ||
| NTF ipmSlave01EmdHumidityNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.44 | INFORMATION: The Slave01 emd Humidity Not Low. | ||
| NTF ipmSlave01EmdHumidityTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.45 | WARNING: The Slave01 emd Humidity Too Low. | ||
| NTF ipmSlave01EmdAlarm1Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.46 | INFORMATION: The Slave01 emd Alarm1 Normal. | ||
| NTF ipmSlave01EmdAlarm1Active | 1.3.6.1.4.1.2468.1.4.2.2.0.47 | WARNING: The Slave01 emd Alarm1 Active. | ||
| NTF ipmSlave01EmdAlarm2Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.48 | INFORMATION: The Slave01 emd Alarm2 Normal. | ||
| NTF ipmSlave01EmdAlarm2Active | 1.3.6.1.4.1.2468.1.4.2.2.0.49 | WARNING: The Slave01 emd Alarm2 Active. | ||
| NTF ipmSlave01OutletCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.50 | WARNING: The Slave01 Outlet Current over threshold. | ||
| NTF ipmSlave02Inlet01OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.51 | CRITICAL: The Slave02 input01 voltage over high threshold. | ||
| NTF ipmSlave02Inlet01NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.52 | CRITICAL: The Slave02 input01 voltage Not over high threshold. | ||
| NTF ipmSlave02Inlet02OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.53 | CRITICAL: The Slave02 input02 voltage over high threshold. | ||
| NTF ipmSlave02Inlet02NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.54 | CRITICAL: The Slave02 input02 voltage Not over high threshold. | ||
| NTF ipmSlave02Inlet01UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.55 | CRITICAL: The Slave02 input01 voltage under low threshold. | ||
| NTF ipmSlave02Inlet01NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.56 | CRITICAL: The Slave02 input01 voltage Not under low threshold. | ||
| NTF ipmSlave02Inlet02UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.57 | CRITICAL: The Slave02 input02 voltage under low threshold. | ||
| NTF ipmSlave02Inlet02NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.58 | CRITICAL: The Slave02 input02 voltage Not under low threshold. | ||
| NTF ipmSlave02Inlet01CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.59 | CRITICAL: The Slave02 input01 current over high threshold. | ||
| NTF ipmSlave02Inlet01NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.60 | CRITICAL: The Slave02 input01 current not over high threshold. | ||
| NTF ipmSlave02Inlet02CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.61 | CRITICAL: The Slave02 input02 current over high threshold. | ||
| NTF ipmSlave02Inlet02NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.62 | CRITICAL: The Slave02 input02 current not over high threshold. | ||
| NTF ipmSlave02EmdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.63 | INFORMATION: The Slave02 emd Temperature Not High. | ||
| NTF ipmSlave02EmdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.64 | WARNING: The Slave02 emd Temperature Too High. | ||
| NTF ipmSlave02EmdTemperatureNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.65 | INFORMATION: The Slave02 emd Temperature Not Low. | ||
| NTF ipmSlave02EmdTemperatureTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.66 | WARNING: The Slave02 emd Temperature Too Low. | ||
| NTF ipmSlave02EmdHumidityNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.67 | INFORMATION: The Slave02 emd Humidity Not High. | ||
| NTF ipmSlave02EmdHumidityTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.68 | WARNING: The Slave02 emd Humidity Too High. | ||
| NTF ipmSlave02EmdHumidityNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.69 | INFORMATION: The Slave02 emd Humidity Not Low. | ||
| NTF ipmSlave02EmdHumidityTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.70 | WARNING: The Slave02 emd Humidity Too Low. | ||
| NTF ipmSlave02EmdAlarm1Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.71 | INFORMATION: The Slave02 emd Alarm1 Normal. | ||
| NTF ipmSlave02EmdAlarm1Active | 1.3.6.1.4.1.2468.1.4.2.2.0.72 | WARNING: The Slave02 emd Alarm1 Active. | ||
| NTF ipmSlave02EmdAlarm2Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.73 | INFORMATION: The Slave02 emd Alarm2 Normal. | ||
| NTF ipmSlave02EmdAlarm2Active | 1.3.6.1.4.1.2468.1.4.2.2.0.74 | WARNING: The Slave02 emd Alarm2 Active. | ||
| NTF ipmSlave02OutletCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.75 | WARNING: The Slave02 Outlet Current over threshold. | ||
| NTF ipmSlave03Inlet01OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.76 | CRITICAL: The Slave03 input01 voltage over high threshold. | ||
| NTF ipmSlave03Inlet01NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.77 | CRITICAL: The Slave03 input01 voltage Not over high threshold. | ||
| NTF ipmSlave03Inlet02OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.78 | CRITICAL: The Slave03 input02 voltage over high threshold. | ||
| NTF ipmSlave03Inlet02NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.79 | CRITICAL: The Slave03 input02 voltage Not over high threshold. | ||
| NTF ipmSlave03Inlet01UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.80 | CRITICAL: The Slave03 input01 voltage under low threshold. | ||
| NTF ipmSlave03Inlet01NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.81 | CRITICAL: The Slave03 input01 voltage Not under low threshold. | ||
| NTF ipmSlave03Inlet02UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.82 | CRITICAL: The Slave03 input02 voltage under low threshold. | ||
| NTF ipmSlave03Inlet02NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.83 | CRITICAL: The Slave03 input02 voltage Not under low threshold. | ||
| NTF ipmSlave03Inlet01CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.84 | CRITICAL: The Slave03 input01 current over high threshold. | ||
| NTF ipmSlave03Inlet01NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.85 | CRITICAL: The Slave03 input01 current not over high threshold. | ||
| NTF ipmSlave03Inlet02CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.86 | CRITICAL: The Slave03 input02 current over high threshold. | ||
| NTF ipmSlave03Inlet02NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.87 | CRITICAL: The Slave03 input02 current not over high threshold. | ||
| NTF ipmSlave03EmdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.88 | INFORMATION: The Slave03 emd Temperature Not High. | ||
| NTF ipmSlave03EmdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.89 | WARNING: The Slave03 emd Temperature Too High. | ||
| NTF ipmSlave03EmdTemperatureNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.90 | INFORMATION: The Slave03 emd Temperature Not Low. | ||
| NTF ipmSlave03EmdTemperatureTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.91 | WARNING: The Slave03 emd Temperature Too Low. | ||
| NTF ipmSlave03EmdHumidityNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.92 | INFORMATION: The Slave03 emd Humidity Not High. | ||
| NTF ipmSlave03EmdHumidityTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.93 | WARNING: The Slave03 emd Humidity Too High. | ||
| NTF ipmSlave03EmdHumidityNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.94 | INFORMATION: The Slave03 emd Humidity Not Low. | ||
| NTF ipmSlave03EmdHumidityTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.95 | WARNING: The Slave03 emd Humidity Too Low. | ||
| NTF ipmSlave03EmdAlarm1Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.96 | INFORMATION: The Slave03 emd Alarm1 Normal. | ||
| NTF ipmSlave03EmdAlarm1Active | 1.3.6.1.4.1.2468.1.4.2.2.0.97 | WARNING: The Slave03 emd Alarm1 Active. | ||
| NTF ipmSlave03EmdAlarm2Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.98 | INFORMATION: The Slave03 emd Alarm2 Normal. | ||
| NTF ipmSlave03EmdAlarm2Active | 1.3.6.1.4.1.2468.1.4.2.2.0.99 | WARNING: The Slave03 emd Alarm2 Active. | ||
| NTF ipmSlave03OutletCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.100 | WARNING: The Slave03 Outlet Current over threshold. | ||
| NTF ipmSlave04Inlet01OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.101 | CRITICAL: The Slave04 input01 voltage over high threshold. | ||
| NTF ipmSlave04Inlet01NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.102 | CRITICAL: The Slave04 input01 voltage Not over high threshold. | ||
| NTF ipmSlave04Inlet02OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.103 | CRITICAL: The Slave04 input02 voltage over high threshold. | ||
| NTF ipmSlave04Inlet02NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.104 | CRITICAL: The Slave04 input02 voltage Not over high threshold. | ||
| NTF ipmSlave04Inlet01UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.105 | CRITICAL: The Slave04 input01 voltage under low threshold. | ||
| NTF ipmSlave04Inlet01NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.106 | CRITICAL: The Slave04 input01 voltage Not under low threshold. | ||
| NTF ipmSlave04Inlet02UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.107 | CRITICAL: The Slave04 input02 voltage under low threshold. | ||
| NTF ipmSlave04Inlet02NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.108 | CRITICAL: The Slave04 input02 voltage Not under low threshold. | ||
| NTF ipmSlave04Inlet01CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.109 | CRITICAL: The Slave04 input01 current over high threshold. | ||
| NTF ipmSlave04Inlet01NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.110 | CRITICAL: The Slave04 input01 current not over high threshold. | ||
| NTF ipmSlave04Inlet02CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.111 | CRITICAL: The Slave04 input02 current over high threshold. | ||
| NTF ipmSlave04Inlet02NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.112 | CRITICAL: The Slave04 input02 current not over high threshold. | ||
| NTF ipmSlave04EmdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.113 | INFORMATION: The Slave04 emd Temperature Not High. | ||
| NTF ipmSlave04EmdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.114 | WARNING: The Slave04 emd Temperature Too High. | ||
| NTF ipmSlave04EmdTemperatureNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.115 | INFORMATION: The Slave04 emd Temperature Not Low. | ||
| NTF ipmSlave04EmdTemperatureTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.116 | WARNING: The Slave04 emd Temperature Too Low. | ||
| NTF ipmSlave04EmdHumidityNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.117 | INFORMATION: The Slave04 emd Humidity Not High. | ||
| NTF ipmSlave04EmdHumidityTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.118 | WARNING: The Slave04 emd Humidity Too High. | ||
| NTF ipmSlave04EmdHumidityNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.119 | INFORMATION: The Slave04 emd Humidity Not Low. | ||
| NTF ipmSlave04EmdHumidityTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.120 | WARNING: The Slave04 emd Humidity Too Low. | ||
| NTF ipmSlave04EmdAlarm1Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.121 | INFORMATION: The Slave04 emd Alarm1 Normal. | ||
| NTF ipmSlave04EmdAlarm1Active | 1.3.6.1.4.1.2468.1.4.2.2.0.122 | WARNING: The Slave04 emd Alarm1 Active. | ||
| NTF ipmSlave04EmdAlarm2Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.123 | INFORMATION: The Slave04 emd Alarm2 Normal. | ||
| NTF ipmSlave04EmdAlarm2Active | 1.3.6.1.4.1.2468.1.4.2.2.0.124 | WARNING: The Slave04 emd Alarm2 Active. | ||
| NTF ipmSlave04OutletCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.125 | WARNING: The Slave04 Outlet Current over threshold. | ||
| NTF ipmSlave05Inlet01OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.126 | CRITICAL: The Slave05 input01 voltage over high threshold. | ||
| NTF ipmSlave05Inlet01NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.127 | CRITICAL: The Slave05 input01 voltage Not over high threshold. | ||
| NTF ipmSlave05Inlet02OverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.128 | CRITICAL: The Slave05 input02 voltage over high threshold. | ||
| NTF ipmSlave05Inlet02NotOverHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.129 | CRITICAL: The Slave05 input02 voltage Not over high threshold. | ||
| NTF ipmSlave05Inlet01UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.130 | CRITICAL: The Slave05 input01 voltage under low threshold. | ||
| NTF ipmSlave05Inlet01NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.131 | CRITICAL: The Slave05 input01 voltage Not under low threshold. | ||
| NTF ipmSlave05Inlet02UnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.132 | CRITICAL: The Slave05 input02 voltage under low threshold. | ||
| NTF ipmSlave05Inlet02NotUnderLow | 1.3.6.1.4.1.2468.1.4.2.2.0.133 | CRITICAL: The Slave05 input02 voltage Not under low threshold. | ||
| NTF ipmSlave05Inlet01CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.134 | CRITICAL: The Slave05 input01 current over high threshold. | ||
| NTF ipmSlave05Inlet01NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.135 | CRITICAL: The Slave05 input01 current not over high threshold. | ||
| NTF ipmSlave05Inlet02CurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.136 | CRITICAL: The Slave05 input02 current over high threshold. | ||
| NTF ipmSlave05Inlet02NotCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.137 | CRITICAL: The Slave05 input02 current not over high threshold. | ||
| NTF ipmSlave05EmdTemperatureNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.138 | INFORMATION: The Slave05 emd Temperature Not High. | ||
| NTF ipmSlave05EmdTemperatureTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.139 | WARNING: The Slave05 emd Temperature Too High. | ||
| NTF ipmSlave05EmdTemperatureNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.140 | INFORMATION: The Slave05 emd Temperature Not Low. | ||
| NTF ipmSlave05EmdTemperatureTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.141 | WARNING: The Slave05 emd Temperature Too Low. | ||
| NTF ipmSlave05EmdHumidityNotHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.142 | INFORMATION: The Slave05 emd Humidity Not High. | ||
| NTF ipmSlave05EmdHumidityTooHigh | 1.3.6.1.4.1.2468.1.4.2.2.0.143 | WARNING: The Slave05 emd Humidity Too High. | ||
| NTF ipmSlave05EmdHumidityNotLow | 1.3.6.1.4.1.2468.1.4.2.2.0.144 | INFORMATION: The Slave05 emd Humidity Not Low. | ||
| NTF ipmSlave05EmdHumidityTooLow | 1.3.6.1.4.1.2468.1.4.2.2.0.145 | WARNING: The Slave05 emd Humidity Too Low. | ||
| NTF ipmSlave05EmdAlarm1Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.146 | INFORMATION: The Slave05 emd Alarm1 Normal. | ||
| NTF ipmSlave05EmdAlarm1Active | 1.3.6.1.4.1.2468.1.4.2.2.0.147 | WARNING: The Slave05 emd Alarm1 Active. | ||
| NTF ipmSlave05EmdAlarm2Normal | 1.3.6.1.4.1.2468.1.4.2.2.0.148 | INFORMATION: The Slave05 emd Alarm2 Normal. | ||
| NTF ipmSlave05EmdAlarm2Active | 1.3.6.1.4.1.2468.1.4.2.2.0.149 | WARNING: The Slave05 emd Alarm2 Active. | ||
| NTF ipmSlave05OutletCurrentOverTh | 1.3.6.1.4.1.2468.1.4.2.2.0.150 | WARNING: The Slave05 Outlet Current over threshold. |
RFC description
Manages intelligent power distribution unit (PDU) operations and environmental monitoring for Ingrasys iPo systems.
Start monitoring Ingrasys networked power distribution unit (PDU) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.