| OID symbolic | OID numeric | Type | Access | Description |
| cyACS5KPM | 1.3.6.1.4.1.2925.8.5 | | | This module defines objects of the Proxy for PM |
| I32 cyNumberOfPMEx | 1.3.6.1.4.1.2925.8.5.1 | Integer32 | read-only | The total number of PM's connected on the unit |
| cyPMTable | 1.3.6.1.4.1.2925.8.5.2 | | not-accessible | Allows to read information about each connected PM |
| cyPMEntry | 1.3.6.1.4.1.2925.8.5.2.1 | | not-accessible | Information about the connected PM |
| NUM cyPMSerialPortNumber | 1.3.6.1.4.1.2925.8.5.2.1.1 | InterfaceIndex | read-only | The number of the serial port when the PM is connected. |
| I32 cyPMNumberOutlets | 1.3.6.1.4.1.2925.8.5.2.1.2 | Integer32 | read-only | Number of outlets. |
| I32 cyPMNumberUnits | 1.3.6.1.4.1.2925.8.5.2.1.3 | Integer32 | read-only | Total number of PM unists that are accessed by this
serial port. |
| STR cyPMCurrent | 1.3.6.1.4.1.2925.8.5.2.1.4 | DisplayString | read-only | Current reading for the PM. |
| STR cyPMVersion | 1.3.6.1.4.1.2925.8.5.2.1.5 | DisplayString | read-only | The software version of the PM. |
| STR cyPMCommand | 1.3.6.1.4.1.2925.8.5.2.1.7 | DisplayString | read-write | A character string for the user to send commands to
PM. He can use it to does the save command.
Or to list the outlets that need to be turned off,
or turned on , or cycled or locked or unlocked as a
group. The command is the first word and is followed
by a space and the outlet list (otulets commands).
Valid commands are 'on', 'off', 'cycle', 'lock',
'unlock', 'save'. |
| cyPMUnitTable | 1.3.6.1.4.1.2925.8.5.3 | | not-accessible | Allow operations on specific PM unit connected |
| cyPMUnitEntry | 1.3.6.1.4.1.2925.8.5.3.1 | | not-accessible | Allow operations on outlet |
| NUM cyPMUnitNumber | 1.3.6.1.4.1.2925.8.5.3.1.1 | InterfaceIndex | not-accessible | The number of the PM unit in the daisy-chained mode. |
| STR cyPMUnitVersion | 1.3.6.1.4.1.2925.8.5.3.1.2 | DisplayString | read-only | The software version of this PM unit. |
| I32 cyPMUnitOutlets | 1.3.6.1.4.1.2925.8.5.3.1.3 | Integer32 | read-only | Number of outlets of this PM unit. |
| I32 cyPMUnitFirstOutlet | 1.3.6.1.4.1.2925.8.5.3.1.4 | Integer32 | read-only | Number of the first outlet of this PM unit. |
| I32 cyPMUnitCurrent | 1.3.6.1.4.1.2925.8.5.3.1.5 | Integer32 | read-only | Current of this PM unit in AMP.
The value of this object is the actual current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the current is 0.5 AMP.) |
| I32 cyPMUnitMaxCurrent | 1.3.6.1.4.1.2925.8.5.3.1.6 | Integer32 | read-only | Maximum current of this PM unit in AMP.
The value of this object is the maximum current in
AMP * 10. You need to translate the readed value
(Ex. : value is 5, the maximum current is 0.5 AMP.) |
| I32 cyPMUnitSequenceInterval | 1.3.6.1.4.1.2925.8.5.3.1.9 | Integer32 | read-only | Sequence interval delay.
Valid values are 2 to 15 (seconds). |
| I32 cyPMUnitCycleInterval | 1.3.6.1.4.1.2925.8.5.3.1.10 | Integer32 | read-only | Number of seconds that a socket stays off
before turning it back on. |
| STR cyPMUnitID | 1.3.6.1.4.1.2925.8.5.3.1.11 | DisplayString | read-only | PDU identification. |
| INT cyPMUnitPhases | 1.3.6.1.4.1.2925.8.5.3.1.12 | INTEGER | read-only | Number of phases of this PDU unit. |
| I32 cyPMUnitBanks | 1.3.6.1.4.1.2925.8.5.3.1.13 | Integer32 | read-only | Number of banks of this PDU unit. |
| I32 cyPMUnitNominalVoltage | 1.3.6.1.4.1.2925.8.5.3.1.14 | Integer32 | read-only | Nominal Voltage configured for this PDU unit, when it does not have voltage sensor |
| I32 cyPMUnitPower | 1.3.6.1.4.1.2925.8.5.3.1.15 | Integer32 | read-only | Power Consumption of this PDU unit (it is estimated when PDU does not have voltage sensor). |
| cyOutletTable | 1.3.6.1.4.1.2925.8.5.4 | | not-accessible | Allow operations on outlet |
| cyOutletEntry | 1.3.6.1.4.1.2925.8.5.4.1 | | not-accessible | Allow operations on outlet |
| NUM cyOutletNumber | 1.3.6.1.4.1.2925.8.5.4.1.1 | InterfaceIndexOrZero | not-accessible | The outlet number on the PM. Zero is ALL outlets. |
| STR cyOutletName | 1.3.6.1.4.1.2925.8.5.4.1.2 | DisplayString | read-write | The name given to a particular outlet Maximum size is 8 characters. |
| STR cyOutletServer | 1.3.6.1.4.1.2925.8.5.4.1.3 | DisplayString | read-only | Alias of the Server connected to this outlet . |
| INT cyOutletPower | 1.3.6.1.4.1.2925.8.5.4.1.4 | INTEGER | read-write | Getting this object will return the power state of
the outlet. Valid return states are UNKNOW, OFF and
ON. Setting this object will change the power state
of the outlet. |
| INT cyOutletLock | 1.3.6.1.4.1.2925.8.5.4.1.5 | INTEGER | read-write | Getting this object will return the lock state of
the outlet. Setting this object will change the
lock state of the outlet. |
| I32 cyOutletPUInterval | 1.3.6.1.4.1.2925.8.5.4.1.6 | Integer32 | read-write | The power unit interval of this outlet in seconds.
The value of this object is the actual interval in
seconds * 10. You need to translate the readed value
(Ex. : value is 5, the interval is 0.5 seconds.) |
| I32 cyOutletMinimumOnInterval | 1.3.6.1.4.1.2925.8.5.4.1.7 | Integer32 | read-only | Minimum time in seconds an outlet will stay on before
turning it off. |
| I32 cyOutletMinimumOffInterval | 1.3.6.1.4.1.2925.8.5.4.1.8 | Integer32 | read-only | Minimum time in seconds an outlet will stay off before
turning it on. |
| I32 cyOutletWakeupState | 1.3.6.1.4.1.2925.8.5.4.1.9 | Integer32 | read-only | Outlet state after a cold boot. It can be set to on
or off. |
| STR cyOutletPduID | 1.3.6.1.4.1.2925.8.5.4.1.10 | DisplayString | read-only | PDU identification. |
| I32 cyOutletPduNumber | 1.3.6.1.4.1.2925.8.5.4.1.11 | Integer32 | not-accessible | The number of the PDU unit in the daisy-chained mode. |
| cyPMElecPduTable | 1.3.6.1.4.1.2925.8.5.5 | | not-accessible | Allow operations on elecmon element of the PDUs |
| cyPMElecPduTableEntry | 1.3.6.1.4.1.2925.8.5.5.1 | | not-accessible | each entry has the information about the elecmon element of the PDUs. |
| NUM cyPMElecPduTablePortNumber | 1.3.6.1.4.1.2925.8.5.5.1.1 | InterfaceIndex | read-only | Serial Port number where the PDU is connected. |
| NUM cyPMElecPduTablePduNumber | 1.3.6.1.4.1.2925.8.5.5.1.2 | InterfaceIndex | read-only | The number of the PDU unit in the daisy-chained mode |
| I32 cyPMElecPduTableCurrentValue | 1.3.6.1.4.1.2925.8.5.5.1.3 | Integer32 | read-only | Actual value of current in the element (A x 10). |
| I32 cyPMElecPduTableCurrentMax | 1.3.6.1.4.1.2925.8.5.5.1.4 | Integer32 | read-write | Maximum detected value of current in the element (A x 10).
Write operation accepts only 0 for reset action. |
| I32 cyPMElecPduTablePowerValue | 1.3.6.1.4.1.2925.8.5.5.1.5 | Integer32 | read-only | Actual value of power in the element (W x 10). |
| I32 cyPMElecPduTablePowerMax | 1.3.6.1.4.1.2925.8.5.5.1.6 | Integer32 | read-write | Maximum value of power in the element (W x 10).
Write operation accepts only 0 for reset action. |
| I32 cyPMElecPduTableVoltageValue | 1.3.6.1.4.1.2925.8.5.5.1.7 | Integer32 | read-only | Actual value of voltage in the element (V).When element
does not have voltage sensor, it returns 0. |
| I32 cyPMElecPduTableVoltageMax | 1.3.6.1.4.1.2925.8.5.5.1.8 | Integer32 | read-write | Maximum value of voltage in the element (V). When element
does not have voltage sensor, it returns 0. Write operation
accepts only 0 for reset action. |
| I32 cyPMElecPduTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.5.1.9 | Integer32 | read-only | Actual value of power factor in the element (Pf x 10).
When element does not have power factor sensor, returns 0. |
| I32 cyPMElecPduTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.5.1.10 | Integer32 | read-write | Maximum value of power factor in the element (Pf x 10).
When element does not have power factor sensor, returns 0.
Write operation accepts only 0 for reset action. |
| INT cyPMElecPduTablePowerType | 1.3.6.1.4.1.2925.8.5.5.1.11 | INTEGER | read-only | This PDU unit's Power sensor type. |
| INT cyPMElecPduTableVoltageType | 1.3.6.1.4.1.2925.8.5.5.1.12 | INTEGER | read-only | This PDU unit's has voltage sensor type. |
| INT cyPMElecPduTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.5.1.13 | INTEGER | read-only | This PDU unit's Power Factor sensor type. |
| cyPMElecPhaseTable | 1.3.6.1.4.1.2925.8.5.6 | | not-accessible | Allow operations on elecmon element for phases |
| cyPMElecPhaseTableEntry | 1.3.6.1.4.1.2925.8.5.6.1 | | not-accessible | each entry has the information about the elecmon for phase. |
| NUM cyPMElecPhaseTablePortNumber | 1.3.6.1.4.1.2925.8.5.6.1.1 | InterfaceIndex | read-only | Serial Port number where the PDU is connected. |
| NUM cyPMElecPhaseTablePduNumber | 1.3.6.1.4.1.2925.8.5.6.1.2 | InterfaceIndex | read-only | The number of the PDU unit in the daisy-chained mode |
| NUM cyPMElecPhaseTableIndex | 1.3.6.1.4.1.2925.8.5.6.1.3 | InterfaceIndex | read-only | index of the phase in the PDU. Index can be 1,2 or 3. |
| STR cyPMElecPhaseTableName | 1.3.6.1.4.1.2925.8.5.6.1.4 | DisplayString | read-only | Sys-name of the phase. |
| I32 cyPMElecPhaseTableCurrentValue | 1.3.6.1.4.1.2925.8.5.6.1.5 | Integer32 | read-only | Actual value of current in the phase (A x 10). |
| I32 cyPMElecPhaseTableCurrentMax | 1.3.6.1.4.1.2925.8.5.6.1.6 | Integer32 | read-write | Maximum detected value of current in the phase (A x 10).
Write operation accepts only 0 for reset action. |
| I32 cyPMElecPhaseTablePowerValue | 1.3.6.1.4.1.2925.8.5.6.1.7 | Integer32 | read-only | Actual value of power in the phase (W x 10). |
| I32 cyPMElecPhaseTablePowerMax | 1.3.6.1.4.1.2925.8.5.6.1.8 | Integer32 | read-write | Maximum value of power in the phase (W x 10).Write operation
accepts only 0 for reset action. |
| I32 cyPMElecPhaseTableVoltageValue | 1.3.6.1.4.1.2925.8.5.6.1.9 | Integer32 | read-only | Actual value of voltage in the phase (V).When phase does
not have voltage sensor, it returns 0. |
| I32 cyPMElecPhaseTableVoltageMax | 1.3.6.1.4.1.2925.8.5.6.1.10 | Integer32 | read-write | Maximum value of voltage in the phase (V). When phase does
not have voltage sensor, it returns 0. Write operation accepts
only 0 for reset action. |
| I32 cyPMElecPhaseTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.6.1.11 | Integer32 | read-only | Actual value of power factor in the phase (Pf x 10). When
phase does not have power factor sensor, returns 0. |
| I32 cyPMElecPhaseTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.6.1.12 | Integer32 | read-write | Maximum value of power factor in the phase (Pf x 10). When
phase does not have power factor sensor, returns 0.Write
operation accepts only 0 for reset action. |
| INT cyPMElecPhaseTablePowerType | 1.3.6.1.4.1.2925.8.5.6.1.13 | INTEGER | read-only | The type of Power sensor for this elecmon |
| INT cyPMElecPhaseTableVoltageType | 1.3.6.1.4.1.2925.8.5.6.1.14 | INTEGER | read-only | The type of Voltage sensor for this elecmon |
| INT cyPMElecPhaseTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.6.1.15 | INTEGER | read-only | The type of Power Factor sensor for this elecmon |
| cyPMElecBankTable | 1.3.6.1.4.1.2925.8.5.7 | | not-accessible | Allow operations on elecmon element for banks |
| cyPMElecBankTableEntry | 1.3.6.1.4.1.2925.8.5.7.1 | | not-accessible | each entry has the information about the elecmon for Bank. |
| NUM cyPMElecBankTablePortNumber | 1.3.6.1.4.1.2925.8.5.7.1.1 | InterfaceIndex | read-only | Serial Port number where the PDU is connected. |
| NUM cyPMElecBankTablePduNumber | 1.3.6.1.4.1.2925.8.5.7.1.2 | InterfaceIndex | read-only | The number of the PDU unit in the daisy-chained mode |
| NUM cyPMElecBankTableIndex | 1.3.6.1.4.1.2925.8.5.7.1.3 | InterfaceIndex | read-only | index of the Bank in the PDU. Index can be 1,2, ... number of banks of the PDU. |
| STR cyPMElecBankTableName | 1.3.6.1.4.1.2925.8.5.7.1.4 | DisplayString | read-only | Sys-name of the Bank. |
| I32 cyPMElecBankTableCurrentValue | 1.3.6.1.4.1.2925.8.5.7.1.5 | Integer32 | read-only | Actual value of current in the Bank (A x 10). |
| I32 cyPMElecBankTableCurrentMax | 1.3.6.1.4.1.2925.8.5.7.1.6 | Integer32 | read-write | Maximum detected value of current in the Bank (A x 10).
Write operation accepts only 0 for reset action. |
| I32 cyPMElecBankTablePowerValue | 1.3.6.1.4.1.2925.8.5.7.1.7 | Integer32 | read-only | Actual value of power in the Bank (W x 10). |
| I32 cyPMElecBankTablePowerMax | 1.3.6.1.4.1.2925.8.5.7.1.8 | Integer32 | read-write | Maximum value of power in the Bank (W x 10).Write operation
accepts only 0 for reset action. |
| I32 cyPMElecBankTableVoltageValue | 1.3.6.1.4.1.2925.8.5.7.1.9 | Integer32 | read-only | Actual value of voltage in the Bank (V).When Bank does
not have voltage sensor, it returns 0. |
| I32 cyPMElecBankTableVoltageMax | 1.3.6.1.4.1.2925.8.5.7.1.10 | Integer32 | read-write | Maximum value of voltage in the Bank (V). When Bank does
not have voltage sensor, it returns 0. Write operation accepts
only 0 for reset action. |
| I32 cyPMElecBankTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.7.1.11 | Integer32 | read-only | Actual value of power factor in the Bank (Pf x 10). When
Bank does not have power factor sensor, returns 0. |
| I32 cyPMElecBankTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.7.1.12 | Integer32 | read-write | Maximum value of power factor in the Bank (Pf x 10). When
Bank does not have power factor sensor, returns 0.Write
operation accepts only 0 for reset action. |
| INT cyPMElecBankTablePowerType | 1.3.6.1.4.1.2925.8.5.7.1.13 | INTEGER | read-only | The type of Power sensor for this elecmon |
| INT cyPMElecBankTableVoltageType | 1.3.6.1.4.1.2925.8.5.7.1.14 | INTEGER | read-only | The type of Voltage sensor for this elecmon |
| INT cyPMElecBankTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.7.1.15 | INTEGER | read-only | The type of Power Factor sensor for this elecmon |
| cyPMElecOutletTable | 1.3.6.1.4.1.2925.8.5.8 | | not-accessible | Allow operations on elecmon element for outlets |
| cyPMElecOutletTableEntry | 1.3.6.1.4.1.2925.8.5.8.1 | | not-accessible | each entry has the information about the elecmon for Outlet. |
| NUM cyPMElecOutletTablePortNumber | 1.3.6.1.4.1.2925.8.5.8.1.1 | InterfaceIndex | read-only | Serial Port number where the PDU is connected. |
| NUM cyPMElecOutletTablePduNumber | 1.3.6.1.4.1.2925.8.5.8.1.2 | InterfaceIndex | read-only | The number of the PDU unit in the daisy-chained mode |
| NUM cyPMElecOutletTableNumber | 1.3.6.1.4.1.2925.8.5.8.1.3 | InterfaceIndex | read-only | outlet number in the PDU |
| STR cyPMElecOutletTableName | 1.3.6.1.4.1.2925.8.5.8.1.4 | DisplayString | read-only | name of the Outlet. |
| I32 cyPMElecOutletTableCurrentValue | 1.3.6.1.4.1.2925.8.5.8.1.5 | Integer32 | read-only | Actual value of current in the Outlet (A x 10). |
| I32 cyPMElecOutletTableCurrentMax | 1.3.6.1.4.1.2925.8.5.8.1.6 | Integer32 | read-write | Maximum detected value of current in the Outlet (A x 10).
Write operation accepts only 0 for reset action. |
| I32 cyPMElecOutletTablePowerValue | 1.3.6.1.4.1.2925.8.5.8.1.7 | Integer32 | read-only | Actual value of power in the Outlet (W x 10). |
| I32 cyPMElecOutletTablePowerMax | 1.3.6.1.4.1.2925.8.5.8.1.8 | Integer32 | read-write | Maximum value of power in the Outlet (W x 10).Write operation
accepts only 0 for reset action. |
| I32 cyPMElecOutletTableVoltageValue | 1.3.6.1.4.1.2925.8.5.8.1.9 | Integer32 | read-only | Actual value of voltage in the Outlet (V).When Outlet does
not have voltage sensor, it returns 0. |
| I32 cyPMElecOutletTableVoltageMax | 1.3.6.1.4.1.2925.8.5.8.1.10 | Integer32 | read-write | Maximum value of voltage in the Outlet (V). When Outlet does
not have voltage sensor, it returns 0. Write operation accepts
only 0 for reset action. |
| I32 cyPMElecOutletTablePowerFactorValue | 1.3.6.1.4.1.2925.8.5.8.1.11 | Integer32 | read-only | Actual value of power factor in the Outlet (Pf x 10). When
Outlet does not have power factor sensor, returns 0. |
| I32 cyPMElecOutletTablePowerFactorMax | 1.3.6.1.4.1.2925.8.5.8.1.12 | Integer32 | read-write | Maximum value of power factor in the Outlet (Pf x 10). When
Outlet does not have power factor sensor, returns 0.Write
operation accepts only 0 for reset action. |
| INT cyPMElecOutletTablePowerType | 1.3.6.1.4.1.2925.8.5.8.1.13 | INTEGER | read-only | The type of Power sensor for this elecmon |
| INT cyPMElecOutletTableVoltageType | 1.3.6.1.4.1.2925.8.5.8.1.14 | INTEGER | read-only | The type of Voltage sensor for this elecmon |
| INT cyPMElecOutletTablePowerFactorType | 1.3.6.1.4.1.2925.8.5.8.1.15 | INTEGER | read-only | The type of Power Factor sensor for this elecmon |
| cyPMEnvMonTable | 1.3.6.1.4.1.2925.8.5.9 | | not-accessible | Allow operations on environmental monitors |
| cyPMEnvMonTableEntry | 1.3.6.1.4.1.2925.8.5.9.1 | | not-accessible | each entry has the information about the environmental monitors. |
| NUM cyPMEnvMonTablePortNumber | 1.3.6.1.4.1.2925.8.5.9.1.1 | InterfaceIndex | read-only | Serial Port number where the PDU is connected. |
| NUM cyPMEnvMonTablePduNumber | 1.3.6.1.4.1.2925.8.5.9.1.2 | InterfaceIndex | read-only | The number of the PDU unit in the daisy-chained mode |
| NUM cyPMEnvMonTableIndex | 1.3.6.1.4.1.2925.8.5.9.1.3 | InterfaceIndex | read-only | index of the environmental monitor in the PDU. |
| STR cyPMEnvMonTableName | 1.3.6.1.4.1.2925.8.5.9.1.4 | DisplayString | read-only | Name of the environmental monitor. |
| INT cyPMEnvMonTableType | 1.3.6.1.4.1.2925.8.5.9.1.5 | INTEGER | read-only | The type of environmental monitor. |
| INT cyPMEnvMonTableStatus | 1.3.6.1.4.1.2925.8.5.9.1.6 | INTEGER | read-only | The status of Dry-Contact/Water-level/Smoke/Motion monitors.
Dry-Contact sensor: Opened(1), closed(2).
Water level: Normal (1), Triggered(2).
Smoke sensor: not-detected(1), detected(2).
Motion sensor: not-detected(1), detected(2). |
| I32 cyPMEnvMonTableValue | 1.3.6.1.4.1.2925.8.5.9.1.7 | Integer32 | read-only | Actual value of Temperature/Humidity/Air-flow monitors (x 10). |
| I32 cyPMEnvMonTableMaxValue | 1.3.6.1.4.1.2925.8.5.9.1.8 | Integer32 | read-write | Maximum detected value of Temperature/Humidity/Air-flow monitor (x 10).
Write operation accepts only 0 for reset action. |