| OID symbolic | OID numeric | Type | Access | Description |
| apNederland | 1.3.6.1.4.1.29640 | | | This MIB module defines the modular PDU version of AP Nederland. |
| apnlDirectory | 1.3.6.1.4.1.29640.1 | | | |
| apnlMib | 1.3.6.1.4.1.29640.2 | | | |
| apnlTmp | 1.3.6.1.4.1.29640.3 | | | |
| apnlModules | 1.3.6.1.4.1.29640.4 | | | |
| cm | 1.3.6.1.4.1.29640.4.1 | | | |
| cmTraps | 1.3.6.1.4.1.29640.4.2 | | | |
| pdu | 1.3.6.1.4.1.29640.4.3 | | | |
| INT pduType | 1.3.6.1.4.1.29640.4.3.1 | INTEGER | read-only | Type of the Pdu.
PduModular (0) Modulaire OEC2 PDU communication through SNMPV3, MOD-BUS or AP-BUS in emulation mode.
PduGateway1 (1) Gateway to connect OEC1 products with external AP-BUS protocol to OEC2 Manager (SNMPV3).
PduGateway2 (2) Gateway to connect OEC2 products with external MOD-BUS to OEC Manager (SNMPV3). |
| I32 pduProductIdentifier | 1.3.6.1.4.1.29640.4.3.2 | Integer32 | read-only | Unique serial number to identify a pdu, the number is between 1 and 65535. |
| STR pduSerialNumber | 1.3.6.1.4.1.29640.4.3.3 | DisplayString | read-only | PDU onboard Serial Number. |
| INT pduStatus | 1.3.6.1.4.1.29640.4.3.4 | INTEGER | read-only | Status of the Pdu.
pduBusy (0) Indicates that an admin command is in progress.
pduReady (1) The execution of an admin command was successfull.
pduAlarm (2) This state is not in use.
pduError (3) The execution of an admin command failed. |
| U32 pduPower | 1.3.6.1.4.1.29640.4.3.5 | Unsigned32 | read-only | The total measured pdu power in Kilo Watt's*Hour. |
| U32 pduPowerL1 | 1.3.6.1.4.1.29640.4.3.6 | Unsigned32 | read-only | The total measured pdu power in Kilo Watt's*Hour for phase 1. |
| U32 pduPowerL2 | 1.3.6.1.4.1.29640.4.3.7 | Unsigned32 | read-only | The total measured pdu power in Kilo Watt's*Hour for phase 2. |
| U32 pduPowerL3 | 1.3.6.1.4.1.29640.4.3.8 | Unsigned32 | read-only | The total measured pdu power in Kilo Watt's*Hour for phase 3. |
| U32 pduKvar | 1.3.6.1.4.1.29640.4.3.9 | Unsigned32 | read-only | The total Reactive Power of the pdu. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. |
| U32 pduKvarL1 | 1.3.6.1.4.1.29640.4.3.10 | Unsigned32 | read-only | The total Reactive Power of the pdu for phase 1. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. |
| U32 pduKvarL2 | 1.3.6.1.4.1.29640.4.3.11 | Unsigned32 | read-only | The total Reactive Power of the pdu for phase 2. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. |
| U32 pduKvarL3 | 1.3.6.1.4.1.29640.4.3.12 | Unsigned32 | read-only | The total Reactive Power of the pdu for phase 3. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. |
| U32 pdulAcurrent | 1.3.6.1.4.1.29640.4.3.13 | Unsigned32 | read-only | The total measured ac current for the pdu (in 1/10th Amperes) . |
| U32 pduAcurrentL1 | 1.3.6.1.4.1.29640.4.3.14 | Unsigned32 | read-only | The total measured ac current for phase 1 (in 1/10th Amperes). |
| U32 pduAcurrentL2 | 1.3.6.1.4.1.29640.4.3.15 | Unsigned32 | read-only | The total measured ac current for phase 2 (in 1/10th Amperes). |
| U32 pduAcurrentL3 | 1.3.6.1.4.1.29640.4.3.16 | Unsigned32 | read-only | The total measured ac current for phase 3 (in 1/10th Amperes). |
| IP pduCurIpAddress | 1.3.6.1.4.1.29640.4.3.17 | IpAddress | read-only | The current PDU IPv4 Address by which TCP/IP access is available. |
| IP pduCurSubNetMask | 1.3.6.1.4.1.29640.4.3.18 | IpAddress | read-only | The current PDU IPv4 Subnet Mask used by the Ipstack (e.g: 255.255.255.0). |
| IP pduCurDefGwAddress | 1.3.6.1.4.1.29640.4.3.19 | IpAddress | read-only | The current PDU IPv4 default gateway address used by the Ipstack (e.g: 192.168.1.1). |
| I32 pduNumberOfNodes | 1.3.6.1.4.1.29640.4.3.20 | Integer32 | read-only | Number of items in the node table. |
| I32 pduNumberOfSensors | 1.3.6.1.4.1.29640.4.3.21 | Integer32 | read-only | Number of items in the sensor table. |
| STR pduSoftwareVersion | 1.3.6.1.4.1.29640.4.3.22 | DisplayString | read-only | PDU software version number. |
| STR pduFirmwareVersion | 1.3.6.1.4.1.29640.4.3.23 | DisplayString | read-only | PDU firmware version number. |
| INT pduBusProtocol | 1.3.6.1.4.1.29640.4.3.24 | INTEGER | read-only | Selected protocol used on the external bus of the pdu.
AP-BUS (0) Protocol used by OEC1 products or by OEC2 products in emulation mode.
MOD-BUS (1) Protocol used by OEC2 products. |
| INT pduAdminCommand | 1.3.6.1.4.1.29640.4.3.25 | INTEGER | read-write | PDU admin management Commands:
noOp (0) No operation.
rebootPdu (1) Reboot the PDU (to execute new settings).
rediscover (2) Not supported.
updateSofware (3) Not supported.
resetConfig (4) Node and group tables will be cleared .
resetSNMPv3Config (5) Not supported.
resetNetworkSetting (6) Reset network params: ip address, defualt gatewy, subnet mask.
readDataFromBusPdu (7) Read data from a PDU connected to the external bus (address is set in pduBusAddress).
writeDataToBusPdu (8) With this command modified data is writen back to the bus PDU (address is set in pduBusAddress). |
| IP pduStartupIpAddress | 1.3.6.1.4.1.29640.4.3.26 | IpAddress | read-write | Not supported. |
| IP pduStartupSubNetMask | 1.3.6.1.4.1.29640.4.3.27 | IpAddress | read-write | Not supported. |
| IP pduStartupDefGwAddress | 1.3.6.1.4.1.29640.4.3.28 | IpAddress | read-write | Not supported. |
| DAT pduRealTimeClock | 1.3.6.1.4.1.29640.4.3.29 | DateAndTime | read-write | PDU Real-Time Clock. Maybe set by the manager. |
| BIT pduEnableFeatures | 1.3.6.1.4.1.29640.4.3.30 | Bits | read-write | Array of bits each one an specific feature within the pdu:
globalWebEnabled (0) This bit enables the PDU webpages.
globalUsbEnabled (1) This bit enables the USB menu.
globalSwitchEnabled (2) This bit enables switching in general.
displaySwitchEnabled (3) This bit enables switching through the presentation module.
webSwitchEnabled (4) This bit enables switching throuhg the web inteface. |
| I32 pduBusAddress | 1.3.6.1.4.1.29640.4.3.31 | Integer32 | read-write | Address used to access this PDU via the external bus.
When MOD-BUS protocol is used the address is valid between 1-247.
When AP-BUS protocol is used the address is valid between 1-65535. |
| STR pduName | 1.3.6.1.4.1.29640.4.3.32 | DisplayString | read-write | Name of the PDU. |
| nodeTable | 1.3.6.1.4.1.29640.4.3.33 | | not-accessible | A table of the modules on the PDU.
Each entry represents an module unit. |
| nodeEntry | 1.3.6.1.4.1.29640.4.3.33.1 | | not-accessible | An port entry in the port table. |
| U32 nodeIndex | 1.3.6.1.4.1.29640.4.3.33.1.1 | Unsigned32 | not-accessible | The node table Index. |
| INT nodeType | 1.3.6.1.4.1.29640.4.3.33.1.2 | INTEGER | read-only | Type of the node.
TypeUnknown (0) Unknown node.
TypePresModChar (1) PM LCD Character Module.
TypePresModMono (2) PM Mono Graphics Module.
TypePresModGraph (3) PM Color Graphics Module.
TypePowerMeter (4) Power meter.
TypePowerMeterSwitch (5) Switchable power meter.
TypeSwitch (6) Switch only. |
| U32 nodeOutlet | 1.3.6.1.4.1.29640.4.3.33.1.3 | Unsigned32 | read-only | The number associated with the physical outlet of the node.
The special value of 0 indicates that this entry is not associated with a physical port. |
| BIT nodeAlarmStatus | 1.3.6.1.4.1.29640.4.3.33.1.4 | Bits | read-only | Array of bits each one indicates an alarm activated in the alarm selector value.
TrapCurrHi (0) The current is to high against the high current threshold.
TrapCurrLo (1) The current is to low against the low current threshold.
TrapVoltHi (2) The voltage is to high against the high voltage threshold.
TrapVoltLo (3) The volage is to low against the low voltage threshold.
SwitchOn (4) The switch is on against the switch on bitfield.
SwitchOff (5) The switch is off against the switch off bitfield. |
| U32 nodePower | 1.3.6.1.4.1.29640.4.3.33.1.5 | Unsigned32 | read-only | The measured node power in Kilo Watt's*Hour. |
| U32 nodeAcurrent | 1.3.6.1.4.1.29640.4.3.33.1.6 | Unsigned32 | read-only | The measured ac current at the node (in 1/10th Amperes). |
| U32 nodePeakCurrent | 1.3.6.1.4.1.29640.4.3.33.1.7 | Unsigned32 | read-only | The measured max current since last reset of the node (in 1/10th Amperes). |
| U32 nodeVoltage | 1.3.6.1.4.1.29640.4.3.33.1.8 | Unsigned32 | read-only | The measured voltage on the node. |
| U32 nodeMinVoltage | 1.3.6.1.4.1.29640.4.3.33.1.9 | Unsigned32 | read-only | The measured minimum voltage at the node since last reset. |
| U32 nodeKvar | 1.3.6.1.4.1.29640.4.3.33.1.10 | Unsigned32 | read-only | The Reactive Power. It is the power that magnetic equipment
(transformer, motor and relay) needs to produce the magnetizing flux. |
| U32 nodeFrequency | 1.3.6.1.4.1.29640.4.3.33.1.11 | Unsigned32 | read-only | The frequency of alternating current in Hertz. e.g 50 in Europe or 60 in USA. |
| U32 nodePowerFactor | 1.3.6.1.4.1.29640.4.3.33.1.12 | Unsigned32 | read-only | The effective power facton (Cosinus Phi) in percents of the node. |
| INT nodeSwitchOperStatus | 1.3.6.1.4.1.29640.4.3.33.1.13 | INTEGER | read-only | The actual operational Status of the node.
Unknown (0) not known status.
Off (1) switch is off.
On (2) switch is on. |
| INT nodeSwitchAdminStatus | 1.3.6.1.4.1.29640.4.3.33.1.14 | INTEGER | read-write | The desired admin Status of the switch.
Unknown (0) not known.
Off (1) switch is off.
On (2) switch is on. |
| U32 nodeCurrHiThresh | 1.3.6.1.4.1.29640.4.3.33.1.15 | Unsigned32 | read-write | The current high threshold (in 1/10th Amperes). |
| U32 nodeCurrLoThresh | 1.3.6.1.4.1.29640.4.3.33.1.16 | Unsigned32 | read-write | The current low threshold (in 1/10th Amperes). |
| U32 nodeVoltHiThresh | 1.3.6.1.4.1.29640.4.3.33.1.17 | Unsigned32 | read-write | The voltage high threshold. |
| U32 nodeVoltLoThresh | 1.3.6.1.4.1.29640.4.3.33.1.18 | Unsigned32 | read-write | The voltage low threshold. |
| BIT nodeAlarmSelector | 1.3.6.1.4.1.29640.4.3.33.1.19 | Bits | read-write | Array of bits each one controls one alarm.
TrapCurrHi (0) Enable/disable the high current alarm.
TrapCurrLo (1) Enable/disable the low current alarm.
TrapVoltHi (2) Enable/disable the high voltage alarm.
TrapVoltLo (3) Enable/disable the low voltage alarm.
SwitchOn (4) Enable/disable the specific switch on alarm.
SwitchOff (5) Enable/disable the specific switch off alarm. |
| STR nodeName | 1.3.6.1.4.1.29640.4.3.33.1.20 | DisplayString | read-write | The node name. My be set by manager. |
| INT nodePhase | 1.3.6.1.4.1.29640.4.3.33.1.21 | INTEGER | read-write | The measured phase of the node.
Maybe assigned when not configured in production.
PhaseUnknown (0).
PhaseL1 (1).
PhaseL2 (2).
PhaseL3 (3). |
| sensorTable | 1.3.6.1.4.1.29640.4.3.34 | | not-accessible | A table of the Sensors on the PDU.
Each entry represents an an Sensor unit. |
| sensorEntry | 1.3.6.1.4.1.29640.4.3.34.1 | | not-accessible | An Sensor Entry in the Sensor table |
| U32 sensorIndex | 1.3.6.1.4.1.29640.4.3.34.1.1 | Unsigned32 | not-accessible | The Sensor table Index. |
| INT sensorType | 1.3.6.1.4.1.29640.4.3.34.1.2 | INTEGER | read-only | Sensor Typ:
Measured values are used according to sensor type.
Other (0) unknown sensor type.
Temperature (1) .
Humidity (2).
Smoke (3).
CO1 (4).
Vibration (5).
Doorstatus (6). |
| BIT sensorAlarmStatus | 1.3.6.1.4.1.29640.4.3.34.1.3 | Bits | read-only | Array of bits each one indicates an alarm activated in the alarm selector value. |
| I32 sensorValue | 1.3.6.1.4.1.29640.4.3.34.1.4 | Integer32 | read-only | The measured value of the sensor, units are depending on sensor type. |
| INT sensorSwitchOperStatus | 1.3.6.1.4.1.29640.4.3.34.1.5 | INTEGER | read-only | The actual operational Status of the switch. |
| INT sensorSwitchAdminStatus | 1.3.6.1.4.1.29640.4.3.34.1.6 | INTEGER | read-write | The desired admin Status of the switch. |
| I32 sensorHiThresh | 1.3.6.1.4.1.29640.4.3.34.1.7 | Integer32 | read-write | High threshold. |
| I32 sensorLoThresh | 1.3.6.1.4.1.29640.4.3.34.1.8 | Integer32 | read-write | Low threshold. |
| BIT sensorAlarmSelector | 1.3.6.1.4.1.29640.4.3.34.1.9 | Bits | read-write | Array of bits each one controls one alarm.
E.g trap, beeper etc. |
| STR sensorName | 1.3.6.1.4.1.29640.4.3.34.1.10 | DisplayString | read-write | The sensor name. May be set by the manager. |
| pduTraps | 1.3.6.1.4.1.29640.4.4 | | | |
| INT trapType | 1.3.6.1.4.1.29640.4.4.1 | INTEGER | accessible-for-notify | An enumation value to indicate an Alarm trap: pduPduAlarm. |
| INT pduTableType | 1.3.6.1.4.1.29640.4.4.2 | INTEGER | accessible-for-notify | The table type. |
| I32 trapTableIndex | 1.3.6.1.4.1.29640.4.4.3 | Integer32 | accessible-for-notify | The index of the table entry for which the trap is issued. |
| INT trapThreshHoldType | 1.3.6.1.4.1.29640.4.4.4 | INTEGER | accessible-for-notify | The threshold type for which the trap is made. |
| I32 trapThreshHold | 1.3.6.1.4.1.29640.4.4.5 | Integer32 | accessible-for-notify | The threshold reference value. |
| NTF pduVoltageAlarm | 1.3.6.1.4.1.29640.4.4.6 | | | Voltage alarm. |
| NTF pduCurrentAlarm | 1.3.6.1.4.1.29640.4.4.7 | | | Current alaram. |
| NTF pduPowerAlarm | 1.3.6.1.4.1.29640.4.4.8 | | | Power alarm. |
| NTF sensorAlarm | 1.3.6.1.4.1.29640.4.4.9 | | | Sensor Alarm:
Temperature, Humidity or another type.
The sensorType indicates the type of alarm.
The sensorValue indicate the measured value. |
| NTF pduSwitchAlarm | 1.3.6.1.4.1.29640.4.4.10 | | | Not supported. |
| apnlTest | 1.3.6.1.4.1.29640.5 | | | |
| apnlDemo | 1.3.6.1.4.1.29640.6 | | | |
| apnlMIBConformance | 1.3.6.1.4.1.29640.7 | | | |