| OID symbolic | OID numeric | Type | Access | Description |
| DMI a1Installation | 1.3.6.1.4.1.318.1.2.2.1.1.1.5 | DmiDateX | read-only | The time and date when this component was installed. |
| STR a1Manufacturer | 1.3.6.1.4.1.318.1.2.2.1.1.1.1 | DmiDisplaystring | read-only | Manufacturer of this system. |
| STR a1Product | 1.3.6.1.4.1.318.1.2.2.1.1.1.2 | DmiDisplaystring | read-only | Product name for this system. |
| STR a1SerialNumber | 1.3.6.1.4.1.318.1.2.2.1.1.1.4 | DmiDisplaystring | read-only | Serial number for this system. |
| INT a1Verify | 1.3.6.1.4.1.318.1.2.2.1.1.1.6 | INTEGER | read-only | A code that provides a level of verification that the component
is stillinstalled and working. |
| STR a1Version | 1.3.6.1.4.1.318.1.2.2.1.1.1.3 | DmiDisplaystring | read-only | Version number of this system. |
| NUM a2BatteryCurrent | 1.3.6.1.4.1.318.1.2.2.1.2.1.6 | DmiGauge | read-only | The present battery current in 0.1 Amps DC. |
| INT a2BatteryStatus | 1.3.6.1.4.1.318.1.2.2.1.2.1.1 | INTEGER | read-only | The indication of the capacity remaining in the UPS system's
batteries. Avalue of 'battery normal' indicates that the remaining estimated
minutes of run-time isgreater than the UPS's configured 'low battery time'
(typically two minutes). A valueof 'battery low' indicates that the remaining
estimated minutes of battery run-time isless than or equal to the UPS's configur
d 'low battery time'. A value of 'batterydepleted' indicates that the UPS
will be unable to sustain the present load when and ifthe uti |
| NUM a2BatteryVoltage | 1.3.6.1.4.1.318.1.2.2.1.2.1.5 | DmiGauge | read-only | The magnitude of the present battery voltage in 0.1 volts
DC. |
| NUM a2EstimatedChargeRemaining | 1.3.6.1.4.1.318.1.2.2.1.2.1.4 | DmiGauge | read-only | An estimate of the time to battery charge depletion under
the present load conditions if theutility power is off and remains off, or
if it were to be lost and remain off. The valuerepresents a percent of full
charge. |
| NUM a2EstimatedMinutesRemaining | 1.3.6.1.4.1.318.1.2.2.1.2.1.3 | DmiInteger | read-only | An estimate in minutes of the time to battery charge depletion
under thepresent load conditions if the utility power is off and remains
off, or if it were to be lostand remain off. |
| NUM a2FruGroupIndex | 1.3.6.1.4.1.318.1.2.2.1.2.1.8 | DmiInteger | read-only | If this is a Field Replaceable Unit or it is part of another
FRU, this providesan index into the FRU table; 'value = -1' indicates that
the group is not a FRU. |
| NUM a2OperationalGroupIndex | 1.3.6.1.4.1.318.1.2.2.1.2.1.9 | DmiInteger | read-only | The index into the Operational State table for this device. |
| NUM a2SecondsOnBattery | 1.3.6.1.4.1.318.1.2.2.1.2.1.2 | DmiCounter | read-only | If the UPS is on battery power, the elapsed time in seconds
since theUPS last switched to battery power, or the time since the UPS component
software waslast restarted, whichever is less. Zero shall be returned if
the UPS is not on batterypower. |
| NUM a2TemperatureProbeIndex | 1.3.6.1.4.1.318.1.2.2.1.2.1.7 | DmiInteger | read-only | Index into the Temperature Probe table. This probe indicates
the ambienttemperature at or near the UPS battery casing. |
| NUM a3FruGroupIndex | 1.3.6.1.4.1.318.1.2.2.1.3.1.20 | DmiInteger | read-only | Index into the FRU table. A value of -1 indicates that this
device is not an FRU. |
| NUM a3MonitoredTemperatureNominalReading | 1.3.6.1.4.1.318.1.2.2.1.3.1.6 | DmiInteger | read-only | The nominal temperature reading of the temperature monitored
by this probe in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported' |
| NUM a3MonitoredTemperatureNormalMaximum | 1.3.6.1.4.1.318.1.2.2.1.3.1.7 | DmiInteger | read-only | The normal maximum temperature reading of the temperature
monitored by this probe in 1/10th degrees C. 0x80000000 denotes 'unknown'
or 'unsupported'. |
| NUM a3MonitoredTemperatureNormalMinimum | 1.3.6.1.4.1.318.1.2.2.1.3.1.8 | DmiInteger | read-only | The normal minimum temperature reading of the temperature
monitored by this probe in 1/10th degrees C. 0x80000000 denotes 'unknown'
or 'unsupported'. |
| NUM a3OperationalGroupIndex | 1.3.6.1.4.1.318.1.2.2.1.3.1.21 | DmiInteger | read-only | Index into the Operational State table |
| NUM a3TemperatureProbeAccuracy | 1.3.6.1.4.1.318.1.2.2.1.3.1.19 | DmiInteger | read-write | The accuracy for the reading from this temperature probe,
in plus/minus hundredths of a percent. 0x80000000 denotes 'unknown' or 'unsuppor
ed'. |
| STR a3TemperatureProbeDescription | 1.3.6.1.4.1.318.1.2.2.1.3.1.3 | DmiDisplaystring | read-only | Additional descriptive information about the temperature
probe orprobe's location. |
| INT a3TemperatureProbeLocation | 1.3.6.1.4.1.318.1.2.2.1.3.1.2 | INTEGER | read-only | Identifies the physical location of the temperature probe. |
| NUM a3TemperatureProbeMaximum | 1.3.6.1.4.1.318.1.2.2.1.3.1.9 | DmiInteger | read-only | The maximum temperature reading specified to be readable
by this probe in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported' |
| NUM a3TemperatureProbeMinimum | 1.3.6.1.4.1.318.1.2.2.1.3.1.10 | DmiInteger | read-only | The minimum temperature reading specified to be readable
by this probe in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported' |
| NUM a3TemperatureProbeResolution | 1.3.6.1.4.1.318.1.2.2.1.3.1.17 | DmiInteger | read-write | The resolution for the reading from this temperature probe,
in tenths of 1/10th degrees C. '0x80000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureProbeTableIndex | 1.3.6.1.4.1.318.1.2.2.1.3.1.1 | DmiInteger | read-only | Index into this temperature probe table. |
| NUM a3TemperatureProbeTemperatureReading | 1.3.6.1.4.1.318.1.2.2.1.3.1.5 | DmiInteger | read-only | The present temperature reading of this temperature probe
in 1/10th degrees C. 0x8000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureProbeTolerance | 1.3.6.1.4.1.318.1.2.2.1.3.1.18 | DmiInteger | read-write | The tolerance for the reading from this temperature probe,
in plus/minus 1/10 degrees C. 0x80000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureReadingLowerThreshold_Criti | 1.3.6.1.4.1.318.1.2.2.1.3.1.13 | DmiInteger | read-write | The lower critical threshold for the temperature probe, in 1/10 degrees C. 0x80000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureReadingLowerThreshold_Non_c | 1.3.6.1.4.1.318.1.2.2.1.3.1.11 | DmiInteger | read-write | The lower non-critical threshold for the temperature reading set by the user, in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupport d'. |
| NUM a3TemperatureReadingLowerThreshold_Non_r | 1.3.6.1.4.1.318.1.2.2.1.3.1.15 | DmiInteger | read-write | The lower non-recoverable threshold for the temperature probe, in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureReadingUpperThreshold_Criti | 1.3.6.1.4.1.318.1.2.2.1.3.1.14 | DmiInteger | read-write | The upper critical threshold for the temperature probe, in /10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureReadingUpperThreshold_Non_c | 1.3.6.1.4.1.318.1.2.2.1.3.1.12 | DmiInteger | read-write | The upper non-critical threshold for the temperature probe, in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported'. |
| NUM a3TemperatureReadingUpperThreshold_Non_r | 1.3.6.1.4.1.318.1.2.2.1.3.1.16 | DmiInteger | read-write | The upper non-recoverable threshold for the temperature probe, in 1/10th degrees C. 0x80000000 denotes 'unknown' or 'unsupported'. |
| INT a3TemperatureStatus | 1.3.6.1.4.1.318.1.2.2.1.3.1.4 | INTEGER | read-only | Defines the status of the temperature monitored by this temperat
reprobe. |
| INT a4AdministrativeState | 1.3.6.1.4.1.318.1.2.2.1.4.1.6 | INTEGER | read-only | The administrative state of the Device Group instance. |
| INT a4AvailabilityStatus | 1.3.6.1.4.1.318.1.2.2.1.4.1.5 | INTEGER | read-only | The availability status of the Device Group instance. |
| INT a4CurrentErrorStatus | 1.3.6.1.4.1.318.1.2.2.1.4.1.10 | INTEGER | read-only | This attribute presents the current error status for this
Device Groupinstance. The most critical error status in effect should be
presented. I.e. if a part of theDevice Group instance is 'Critical', while
other status is 'Non-critical' then the status'Critical' should be reported. |
| NUM a4DeviceGroupIndex | 1.3.6.1.4.1.318.1.2.2.1.4.1.2 | DmiInteger | read-only | The group ID of the group referencing this instance. |
| NUM a4FatalErrorCount | 1.3.6.1.4.1.318.1.2.2.1.4.1.7 | DmiCounter | read-only | The accumulated Fatal or Non-recoverable error count for
this DeviceGroup instance. |
| NUM a4MajorErrorCount | 1.3.6.1.4.1.318.1.2.2.1.4.1.8 | DmiCounter | read-only | The accumulated Major or Critical error count for this Device
Groupinstance. |
| NUM a4OperationalStateInstanceIndex | 1.3.6.1.4.1.318.1.2.2.1.4.1.1 | DmiInteger | read-only | The Index into the Operational State table. |
| INT a4OperationalStatus | 1.3.6.1.4.1.318.1.2.2.1.4.1.3 | INTEGER | read-only | The operational status of the Device Group instance. |
| INT a4UsageState | 1.3.6.1.4.1.318.1.2.2.1.4.1.4 | INTEGER | read-only | The usage state of the Device Group instance. |
| NUM a4WarningErrorCount | 1.3.6.1.4.1.318.1.2.2.1.4.1.9 | DmiCounter | read-only | The accumulated Warning or Non-Critical error count for this
DeviceGroup instance. |
| STR a5DiagnosticFunctionDescription | 1.3.6.1.4.1.318.1.2.2.1.5.1.3 | DmiDisplaystring | read-only | A description of what this diagnostic function does. |
| STR a5DiagnosticFunctionName | 1.3.6.1.4.1.318.1.2.2.1.5.1.2 | DmiDisplaystring | read-only | A specific descriptive name of the diagnostic function, includin
versioninformation, if relevant. |
| NUM a5DiagnosticFunctionTableIndex | 1.3.6.1.4.1.318.1.2.2.1.5.1.1 | DmiInteger | read-only | A unique identifier for this specific diagnostic function. |
| INT a5ExclusiveAccessRequired | 1.3.6.1.4.1.318.1.2.2.1.5.1.4 | INTEGER | read-only | Indicates whether this diagnostic function requires exclusive
access tothe device or component, implying that the user or management applicati
n must takesome action within the operating system to ensure that the device
or component cannotbe used by any other function. |
| INT a5PrerequisiteConditions | 1.3.6.1.4.1.318.1.2.2.1.5.1.5 | INTEGER | read-only | Indicates what conditions must be met before this diagnostic
functioncan be run. |
| NUM a5PrerequisiteDiagnosticFunction | 1.3.6.1.4.1.318.1.2.2.1.5.1.6 | DmiInteger | read-only | If non-0, this specifies the ID of another diagnostic function
that must berun immediately prior to this one. |
| NUM a6DiagnosticFunctionRequest | 1.3.6.1.4.1.318.1.2.2.1.6.1.2 | DmiInteger | read-write | The ID of the specific diagnostic function which is being
requested. Ifthe interface is reserved, a set request to this attribute should
also set the DiagnosticFunction Reserve Key with the reserve key value. |
| NUM a6DiagnosticFunctionReserveKey | 1.3.6.1.4.1.318.1.2.2.1.6.1.1 | DmiInteger | read-write | Indicates whether the interface to this component's diagnostic
functionsis reserved. A zero value returned on a get indicates that a reserve
is already in effect. A non-zero value indicates that no reserve was in effect,
and the returned value may beused as a reserve key. |
| NUM a6DiagnosticFunctionResult | 1.3.6.1.4.1.318.1.2.2.1.6.1.3 | DmiInteger | read-only | The integer-based result code of the last diagnostic function
run. |
| NUM a7DiagnosticFunctionId | 1.3.6.1.4.1.318.1.2.2.1.7.1.1 | DmiInteger | read-only | The unique ID for a specific diagnostic function. |
| NUM a7DiagnosticFunctionResult | 1.3.6.1.4.1.318.1.2.2.1.7.1.2 | DmiInteger | read-only | An integer-based result code of the diagnostic function. |
| STR a7DiagnosticFunctionResultDescription | 1.3.6.1.4.1.318.1.2.2.1.7.1.3 | DmiDisplaystring | read-only | A description of what this result code for this diagnostic
functionmeans, including suggested corrective actions, where possible. |
| INT a7FaultIsolatedToThisComponent | 1.3.6.1.4.1.318.1.2.2.1.7.1.4 | INTEGER | read-only | An indicator of whether the fault is strictly isolated within
the bounds ofthis component. A False value indicates that the fault might
be caused by a failingparent component; for example, a disk test may fail
because of a faulty disk controller. |
| INT a8AlarmGeneration | 1.3.6.1.4.1.318.1.2.2.1.8.1.7 | INTEGER | read-write | Controls indication generation for errors. |
| INT a8ErrorStatus | 1.3.6.1.4.1.318.1.2.2.1.8.1.5 | INTEGER | read-only | current error status |
| INT a8ErrorStatusType | 1.3.6.1.4.1.318.1.2.2.1.8.1.6 | INTEGER | read-only | Indicates the type of detection that set the current error
status. |
| NUM a8NumberOfFatalErrors | 1.3.6.1.4.1.318.1.2.2.1.8.1.2 | DmiCounter | read-only | Count of all fatal errors since system startup. |
| NUM a8NumberOfMajorErrors | 1.3.6.1.4.1.318.1.2.2.1.8.1.3 | DmiCounter | read-only | Count of all major errors since system startup. |
| NUM a8NumberOfWarnings | 1.3.6.1.4.1.318.1.2.2.1.8.1.4 | DmiCounter | read-only | Count of all warning errors since system startup. |
| NUM a8Selfid | 1.3.6.1.4.1.318.1.2.2.1.8.1.1 | DmiInteger | read-only | Instance id. A unique number that identifies this row. |
| NUM a9999ComponentId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.5 | DmiInteger | read-only | Component ID of the component that caused this error |
| NUM a9999ErrorGroupId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.3 | DmiInteger | read-only | Group ID of the errorControl Group |
| NUM a9999ErrorInstanceId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.4 | DmiInteger | read-only | Instance ID of the errorControl Group |
| NUM a9999ErrorStatus | 1.3.6.1.4.1.318.1.2.2.1.9999.1.2 | DmiInteger | read-only | Error Status Code |
| STR a9999ErrorTime | 1.3.6.1.4.1.318.1.2.2.1.9999.1.1 | DisplayString | read-only | The Date & Time when the error occured |
| NUM a9999GroupId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.6 | DmiInteger | read-only | Group ID of the Group that caused this error |
| NUM a9999InstanceId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.7 | DmiInteger | read-only | Instance ID of the Group that caused this error |
| NUM a9999ParentGroupId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.11 | DmiInteger | read-only | Group ID of parent of Group that caused this error |
| NUM a9999ParentInstanceId | 1.3.6.1.4.1.318.1.2.2.1.9999.1.12 | DmiInteger | read-only | Instance ID of parent of Group that caused this error |
| NUM a9999VendorCode1 | 1.3.6.1.4.1.318.1.2.2.1.9999.1.8 | DmiInteger | read-only | Vendor specific code 1 |
| NUM a9999VendorCode2 | 1.3.6.1.4.1.318.1.2.2.1.9999.1.9 | DmiInteger | read-only | Vendor specific code 2 |
| OCT a9999VendorText | 1.3.6.1.4.1.318.1.2.2.1.9999.1.10 | OCTET STRING | read-only | Vendor specific octet string info |
| NUM a99DisableTrap | 1.3.6.1.4.1.318.1.2.2.1.99.1.3 | DmiInteger | read-write | This attribute can be changed to disable sending oftraps
from this component |
| STR a99MibName | 1.3.6.1.4.1.318.1.2.2.1.99.1.1 | DmiDisplaystring | read-only | The MIB name that defines this MIF |
| STR a99MibOid | 1.3.6.1.4.1.318.1.2.2.1.99.1.2 | DmiDisplaystring | read-only | The MIB Object Identifier that corresponds to this MIF |
| apc | 1.3.6.1.4.1.318 | | | |
| dmtfGroups | 1.3.6.1.4.1.318.1.2.2.1 | | | |
| eComponentid | 1.3.6.1.4.1.318.1.2.2.1.1.1 | | not-accessible | |
| eDiagnosticRequestGroup | 1.3.6.1.4.1.318.1.2.2.1.6.1 | | not-accessible | |
| eDiagnosticResults | 1.3.6.1.4.1.318.1.2.2.1.7.1 | | not-accessible | |
| eDiagnostics | 1.3.6.1.4.1.318.1.2.2.1.5.1 | | not-accessible | |
| eErrorControlGroup | 1.3.6.1.4.1.318.1.2.2.1.8.1 | | not-accessible | |
| eMiftomib | 1.3.6.1.4.1.318.1.2.2.1.99.1 | | not-accessible | |
| eOperationalStateTable | 1.3.6.1.4.1.318.1.2.2.1.4.1 | | not-accessible | |
| eTemperatureProbe | 1.3.6.1.4.1.318.1.2.2.1.3.1 | | not-accessible | |
| eTrapGroup | 1.3.6.1.4.1.318.1.2.2.1.9999.1 | | not-accessible | |
| eUpsBattery | 1.3.6.1.4.1.318.1.2.2.1.2.1 | | not-accessible | |
| powerChuteDMIAgent | 1.3.6.1.4.1.318.1.2.2 | | | |
| products | 1.3.6.1.4.1.318.1 | | | |
| NTF pwrchuteEventError | 1.3.6.1.4.1.318.1.2.2.1.9999.1.0.1 | | | DMI Service Layer generated event for APC UPS |
| software | 1.3.6.1.4.1.318.1.2 | | | |
| tComponentid | 1.3.6.1.4.1.318.1.2.2.1.1 | | not-accessible | This group defines the attributes common to all components.
This groupis required. |
| tDiagnosticRequestGroup | 1.3.6.1.4.1.318.1.2.2.1.6 | | not-accessible | This group defines the attributes which a management application
usesto request an actual diagnostic analysis. |
| tDiagnosticResults | 1.3.6.1.4.1.318.1.2.2.1.7 | | not-accessible | This group defines the attributes for interpreting diagnostic
functionresult codes. |
| tDiagnostics | 1.3.6.1.4.1.318.1.2.2.1.5 | | not-accessible | This group defines the diagnostic functions that are provided
by thiscomponent for analyzing potential failures within the component. A
diagnosticfunction could be an actual test run against the component, the
results of a self-test ofthe component, an analysis of failure information
captured during a failure of thecomponent, or an analysis of the current
state of the component. |
| tErrorControlGroup | 1.3.6.1.4.1.318.1.2.2.1.8 | | not-accessible | Indication control and status for the parent group. |
| tMiftomib | 1.3.6.1.4.1.318.1.2.2.1.99 | | not-accessible | This group defines attributes required for DMI to
SNMP translati
n. |
| tOperationalStateTable | 1.3.6.1.4.1.318.1.2.2.1.4 | | not-accessible | This group provides the operational state, usage, and availabili
y status,and administrative state indicators for specific Device Group instances |
| tTemperatureProbe | 1.3.6.1.4.1.318.1.2.2.1.3 | | not-accessible | This group defines the attributes for the temperature probes
in thissystem. |
| tTrapGroup | 1.3.6.1.4.1.318.1.2.2.1.9999 | | not-accessible | This group defines attributes needed for Trap
definition. This group does not exist in MIF file |
| tUpsBattery | 1.3.6.1.4.1.318.1.2.2.1.2 | | not-accessible | The UPS Battery group contains information regarding the
UPSsystem's battery status. |