| OID symbolic | OID numeric | Type | Access | Description |
| aii | 1.3.6.1.4.1.539 | | | |
| INT aislcainAnalogAlarmState | 1.3.6.1.4.1.539.28.1.1.46 | INTEGER | read-only | The point's current alarm state, or normal(5). |
| INT aislcainAnalogStatus | 1.3.6.1.4.1.539.28.1.1.44 | INTEGER | read-only | The current alarm status of the analog input. |
| STR aislcainCurrentStateText | 1.3.6.1.4.1.539.28.1.1.45 | DisplayString | read-only | Textual description of the point's current state.
This is either aislcainNormalStateText or aislcainAlarmStateText. |
| STR aislcainCurrentValuemA | 1.3.6.1.4.1.539.28.1.1.27 | DisplayString | read-only | The current input value in mA. |
| STR aislcainCurrentValueuu | 1.3.6.1.4.1.539.28.1.1.26 | DisplayString | read-only | The current input value in user-defined units. |
| STR aislcainDescription | 1.3.6.1.4.1.539.28.1.1.3 | DisplayString | read-write | Textual description of the point.
Maximum length is 80 characters. |
| STR aislcainHighAlarmHysteresisuu | 1.3.6.1.4.1.539.28.1.1.20 | DisplayString | read-write | The amount by which the input must drop below the High Alarm Threshold
before the High Alarm will be cleared. |
| INT aislcainHighAlarmMinPeriod | 1.3.6.1.4.1.539.28.1.1.19 | INTEGER | read-write | The minimum number of seconds the input(s) should be energized when
the input exceeds the high alarm threshold. |
| INT aislcainHighAlarmSeverity | 1.3.6.1.4.1.539.28.1.1.6 | INTEGER | read-write | Severity of the point's alarm state, or notReported(5)
if the point does not generate an alarm. |
| STR aislcainHighAlarmStateText | 1.3.6.1.4.1.539.28.1.1.7 | DisplayString | read-write | Textual description of the point's alarm state.
Maximum length is 80 characters. |
| STR aislcainHighAlarmThresholdIntervaluu | 1.3.6.1.4.1.539.28.1.1.18 | DisplayString | read-write | The high alarm level threshold interval in user-defined units.
When the high alarm is active, each time the input rises another
interval higher, a new alarm is sent. |
| STR aislcainHighAlarmThresholduu | 1.3.6.1.4.1.539.28.1.1.17 | DisplayString | read-write | The high alarm level in user-defined units. |
| INT aislcainHighLimitScan | 1.3.6.1.4.1.539.28.1.1.16 | INTEGER | read-write | If enabled, the high limit threshold will be checked when the input is scanned. |
| STR aislcainLastChangeTime | 1.3.6.1.4.1.539.28.1.1.28 | DisplayString | read-only | Textural representation of the time of the most recent
output change. 24-hour format YYYY-MM-DD HH:MM:SS. |
| STR aislcainLowAlarmHysteresisuu | 1.3.6.1.4.1.539.28.1.1.25 | DisplayString | read-write | The amount by which the input must rise above the Low Alarm Threshold
before the Low Alarm will be cleared. |
| INT aislcainLowAlarmMinPeriod | 1.3.6.1.4.1.539.28.1.1.24 | INTEGER | read-write | The minimum number of seconds the input(s) should be energized when
the input falls below the low alarm threshold. |
| INT aislcainLowAlarmSeverity | 1.3.6.1.4.1.539.28.1.1.8 | INTEGER | read-write | Severity of the point's alarm state, or notReported(5)
if the point does not generate an alarm. |
| STR aislcainLowAlarmStateText | 1.3.6.1.4.1.539.28.1.1.9 | DisplayString | read-write | Textual description of the point's alarm state.
Maximum length is 80 characters. |
| STR aislcainLowAlarmThresholdIntervaluu | 1.3.6.1.4.1.539.28.1.1.23 | DisplayString | read-write | The low alarm level threshold interval in user-defined units.
When the low alarm is active, each time the input drops another
interval lower, a new alarm is sent. |
| STR aislcainLowAlarmThresholduu | 1.3.6.1.4.1.539.28.1.1.22 | DisplayString | read-write | The low alarm level in user-defined units. |
| INT aislcainLowLimitScan | 1.3.6.1.4.1.539.28.1.1.21 | INTEGER | read-write | If enabled, the low limit threshold will be checked when the input is scanned. |
| STR aislcainMaxInputmA | 1.3.6.1.4.1.539.28.1.1.14 | DisplayString | read-write | The current in mA corresponding to the maximum input in user-defined units. |
| STR aislcainMaxInputuu | 1.3.6.1.4.1.539.28.1.1.15 | DisplayString | read-write | The maximum value in user-defined units corresponding to the maximum input in mA. |
| STR aislcainMinInputmA | 1.3.6.1.4.1.539.28.1.1.12 | DisplayString | read-write | The current in mA corresponding to the minimum input in user-defined units. |
| STR aislcainMinInputuu | 1.3.6.1.4.1.539.28.1.1.13 | DisplayString | read-write | The minimum value in user-defined units corresponding to the minimum input in mA. |
| STR aislcainNormalStateText | 1.3.6.1.4.1.539.28.1.1.10 | DisplayString | read-write | Textual description of the point's normal state.
Maximum length is 80 characters. |
| INT aislcainNormalStateTrap | 1.3.6.1.4.1.539.28.1.1.5 | INTEGER | read-write | If enabled, transitions from an alarm state to the normal
state will generate an SNMP trap or TL1 message. |
| NUM aislcainPointNumber | 1.3.6.1.4.1.539.28.1.1.1 | PositiveInteger | read-only | Input point number to which this table row applies. |
| INT aislcainScanningEnabled | 1.3.6.1.4.1.539.28.1.1.2 | INTEGER | read-write | Enable or disable scanning of the input. |
| STR aislcaintl1AccessID | 1.3.6.1.4.1.539.28.1.1.29 | DisplayString | read-write | Unique TL1 access identifier for this point.
Maximum length is 22 characters. |
| INT aislcaintl1AccessIDType | 1.3.6.1.4.1.539.28.1.1.31 | INTEGER | read-write | Identifies the point as either an equipment(1) alarm condition
or an environmental(2) alarm. |
| STR aislcaintl1HighAlarmConditionDesc | 1.3.6.1.4.1.539.28.1.1.39 | DisplayString | read-write | Textual description of the alarm condition, used only
when aislcaintl1AccessIDType is equipment(1).
Maximum length is 64 characters. |
| STR aislcaintl1HighAlarmConditionType | 1.3.6.1.4.1.539.28.1.1.38 | DisplayString | read-write | String indicating the type of alarm condition, used
only when aislcaintl1AccessIDType is equipment(1).
Maximum length is 20 characters. |
| STR aislcaintl1HighAlarmMessage | 1.3.6.1.4.1.539.28.1.1.33 | DisplayString | read-write | Textual description of the alarm, used only when
aislcaintl1AccessIDType is environmental(2).
Maximum length is 40 characters. |
| INT aislcaintl1HighAlarmNotificationCode | 1.3.6.1.4.1.539.28.1.1.36 | INTEGER | read-write | Severity of the point's alarm state. |
| INT aislcaintl1HighAlarmServiceAffecting | 1.3.6.1.4.1.539.28.1.1.37 | INTEGER | read-write | Indicates whether or not the alarm affects the functioning
of the equipment. This is only meaningful when
aislcaintl1AccessIDType is equipment(1). |
| STR aislcaintl1HighAlarmType | 1.3.6.1.4.1.539.28.1.1.32 | DisplayString | read-write | String indicating the type of alarm, used only
when aislcaintl1AccessIDType is environmental(2).
Maximum length is 10 characters. |
| STR aislcaintl1LowAlarmConditionDesc | 1.3.6.1.4.1.539.28.1.1.43 | DisplayString | read-write | Textual description of the alarm condition, used only
when aislcaintl1AccessIDType is equipment(1).
Maximum length is 64 characters. |
| STR aislcaintl1LowAlarmConditionType | 1.3.6.1.4.1.539.28.1.1.42 | DisplayString | read-write | String indicating the type of alarm condition, used
only when aislcaintl1AccessIDType is equipment(1).
Maximum length is 20 characters. |
| STR aislcaintl1LowAlarmMessage | 1.3.6.1.4.1.539.28.1.1.35 | DisplayString | read-write | Textual description of the alarm, used only when
aislcaintl1AccessIDType is environmental(2).
Maximum length is 40 characters. |
| INT aislcaintl1LowAlarmNotificationCode | 1.3.6.1.4.1.539.28.1.1.40 | INTEGER | read-write | Severity of the point's alarm state. |
| INT aislcaintl1LowAlarmServiceAffecting | 1.3.6.1.4.1.539.28.1.1.41 | INTEGER | read-write | Indicates whether or not the alarm affects the functioning
of the equipment. This is only meaningful when
aislcaintl1AccessIDType is equipment(1). |
| STR aislcaintl1LowAlarmType | 1.3.6.1.4.1.539.28.1.1.34 | DisplayString | read-write | String indicating the type of alarm, used only
when aislcaintl1AccessIDType is environmental(2).
Maximum length is 10 characters. |
| T/F aislcaintl1Provisioned | 1.3.6.1.4.1.539.28.1.1.30 | TruthValue | read-write | Enable TL1 management of this point. |
| INT aislcainTrapEnable | 1.3.6.1.4.1.539.28.1.1.4 | INTEGER | read-write | Enable or disable alarm traps. |
| STR aislcainUserUnits | 1.3.6.1.4.1.539.28.1.1.11 | DisplayString | read-write | The user-defined units for this input (e.g. degC, degF, etc.). |
| aiSLCAnalog | 1.3.6.1.4.1.539.28 | | | MIB module for SLCs with analog input points. |
| aiSLCAnalogInputEntry | 1.3.6.1.4.1.539.28.1.1 | | not-accessible | Entry of aiSLCAnalogInputTable. |
| aiSLCAnalogInputTable | 1.3.6.1.4.1.539.28.1 | | not-accessible | Table of analog inputs points indexed by point number.
Includes description, configuration and status information. |