esPointValueInt

Module: SL10-MIB

OID (symbolic): SL10-MIB::esPointValueInt

OID (numeric): 1.3.6.1.4.1.3052.40.10.1.1.6

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: A number referring to the value of a point on an EventSensor.

If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit).

If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed).

If the point class is humidity, then this object is the percent relative humidity.

If the point class is analog input, then this object is the signed input value in tenths of the configured units.

For any point class except relay, this object is read-only. For relays, setting this object to 1 closes the relay, while setting it to 0 opens it. This works regardless of the control mode of the relay.

What is esPointValueInt?

The point's current value as a signed integer (-32768..32767): the raw temperature in its configured scale, 0/1 for an open/closed contact or relay, the percent relative humidity, or an analog reading in tenths of its configured unit, depending on the point's class. For relay points only, writing 1 closes the relay and 0 opens it, regardless of the relay's separate control mode.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3052.40.10.1.1.6
snmpwalk -v2c -c public <target> SL10-MIB::esPointValueInt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3052.40.10.1.1.6.1
snmpget -v2c -c public <target> SL10-MIB::esPointValueInt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.3052.40.10.1.1.6.1 i <value>

Start monitoring SL10-series remote site monitoring devices with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SL10-MIB::esPointValueInt OID value, configure state conditions and alerts, and monitor any SL10-series remote site monitoring devices from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.3052asentriaASENTRIA-ROOT-MIB
1.3.6.1.4.1.3052.40s410S410-MIB
1.3.6.1.4.1.3052.40.10eventSensorStatusS410-MIB
1.3.6.1.4.1.3052.40.10.1esPointTableS410-MIB
1.3.6.1.4.1.3052.40.10.1.1esPointEntryS410-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3052.40.10.1.1.6esPointValueIntSL10-MIB