S410-MIB

MIB Reference — IPNetwork Monitor

All MIBsS410-MIB

Category: Generic Switch Management

Description:

Defines management objects for a generic S410 series network switch.

Imported Objects

From RFC-1212

OBJECT-TYPE

From RFC-1215

TRAP-TYPE

From RFC1155-SMI

Counter
Gauge
IpAddress
NetworkAddress
TimeTicks
enterprises
internet
mgmt
private

From SNMPv2-TC

DisplayString

What Is S410-MIB?

S410-MIB is a vendor-specific MIB for the S410 remote telemetry/alarm monitoring unit, the kind of small RTU deployed at unmanned or lightly-staffed remote sites such as cell sites, huts, or cabinets. It exposes device identity and configuration data (serial number, firmware version, site ID, configured SNMP manager addresses) alongside discrete alarm input status and trap configuration. Its primary monitoring value is fault/alarm status and software version: alarmStatus and the forceTraps/thisTrapText pair let an operator see current alarm conditions and the human-readable trap description raised by the unit, while firmwareVersion confirms which software build a given unit is running. As a minimal, self-contained enterprise MIB it has no explicit dependency on other MIBs beyond standard SNMP trap mechanisms. It is typically deployed in remote telemetry/alarm monitoring applications where discrete environmental or equipment alarms need centralized SNMP reporting back to an NOC, and technicians reference the S410-MIB MIB definition when integrating a new remote unit.

IPNetwork Monitor allows you to monitor SNMP objects defined in S410-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.

What Can Be Monitored

  • alarm status
  • discrete input mode
  • trap text/description
  • firmware version
  • serial number
  • configured SNMP manager addresses

Supported Devices

  • S410 remote telemetry/alarm monitoring unit
  • remote site monitoring RTU

Monitoring Examples

An operator monitors alarmStatus to detect an active alarm condition at a remote site and reads thisTrapText for a human-readable description of the last trap sent, while input78Mode shows how a pair of discrete input channels is currently configured; siteID and serialNumber identify exactly which remote unit raised the condition so it can be dispatched correctly.

OIDs
OID symbolicOID numericTypeAccessDescription
asentria1.3.6.1.4.1.3052
s4101.3.6.1.4.1.3052.40
NTF contact1ActiveTrap1.3.6.1.4.1.3052.40.0.20001Sent to show Contact 1 is in the alarm state
NTF contact2ActiveTrap1.3.6.1.4.1.3052.40.0.20002Sent to show Contact 2 is in the alarm state
NTF contact3ActiveTrap1.3.6.1.4.1.3052.40.0.20003Sent to show Contact 3 is in the alarm state
NTF contact4ActiveTrap1.3.6.1.4.1.3052.40.0.20004Sent to show Contact 4 is in the alarm state
NTF contact5ActiveTrap1.3.6.1.4.1.3052.40.0.20005Sent to show Contact 5 is in the alarm state
NTF contact6ActiveTrap1.3.6.1.4.1.3052.40.0.20006Sent to show Contact 6 is in the alarm state
NTF contact7ActiveTrap1.3.6.1.4.1.3052.40.0.20007Sent to show Contact 7 is in the alarm state
NTF contact8ActiveTrap1.3.6.1.4.1.3052.40.0.20008Sent to show Contact 8 is in the alarm state
NTF contact9ActiveTrap1.3.6.1.4.1.3052.40.0.20009Send to show Contact 9 is in the alarm state
NTF tempHighTrap1.3.6.1.4.1.3052.40.0.20010Sent to show Temp exceeded High Temp Threshold
NTF tempVeryHighTrap1.3.6.1.4.1.3052.40.0.20011Sent to show Temp exceeded Very High Temp Threshold
NTF tempLowTrap1.3.6.1.4.1.3052.40.0.20012Sent to show Temp went below Low Temp Threshold
NTF tempVeryLowTrap1.3.6.1.4.1.3052.40.0.20013Sent to show Temp went below Very Low Temp Threshold
NTF humidityHighTrap1.3.6.1.4.1.3052.40.0.20020Sent to show humidity exceeded High humidity Threshold
NTF humidityVeryHighTrap1.3.6.1.4.1.3052.40.0.20021Sent to show humidity exceeded Very High humidity Threshold
NTF humidityLowTrap1.3.6.1.4.1.3052.40.0.20022Sent to show humidity went below Low humidity Threshold
NTF humidityVeryLowTrap1.3.6.1.4.1.3052.40.0.20023Sent to show humidity went below Very Low humidity Threshold
NTF analog1HighTrap1.3.6.1.4.1.3052.40.0.20030Sent to show analog1 exceeded High analog1 Threshold
NTF analog1VeryHighTrap1.3.6.1.4.1.3052.40.0.20031Sent to show analog1 exceeded Very High analog1 Threshold
NTF analog1LowTrap1.3.6.1.4.1.3052.40.0.20032Sent to show analog1 went below Low analog1 Threshold
NTF analog1VeryLowTrap1.3.6.1.4.1.3052.40.0.20033Sent to show analog1 went below Very Low analog1 Threshold
NTF analog2HighTrap1.3.6.1.4.1.3052.40.0.20040Sent to show analog2 exceeded High analog2 Threshold
NTF analog2VeryHighTrap1.3.6.1.4.1.3052.40.0.20041Sent to show analog2 exceeded Very High analog2 Threshold
NTF analog2LowTrap1.3.6.1.4.1.3052.40.0.20042Sent to show analog2 went below Low analog2 Threshold
NTF analog2VeryLowTrap1.3.6.1.4.1.3052.40.0.20043Sent to show analog2 went below Very Low analog2 Threshold
NTF contactESActiveTrap1.3.6.1.4.1.3052.40.0.20101Sent to show EventSensor contact is in the alarm state
NTF tempESHighTrap1.3.6.1.4.1.3052.40.0.20110Sent to show Temp exceeded High Threshold on an EventSensor
NTF tempESVeryHighTrap1.3.6.1.4.1.3052.40.0.20111Sent to show Temp exceeded Very High Threshold on an EventSensor
NTF tempESLowTrap1.3.6.1.4.1.3052.40.0.20112Sent to show Temp went below Low Threshold on an EventSensor
NTF tempESVeryLowTrap1.3.6.1.4.1.3052.40.0.20113Sent to show Temp went below Very Low Threshold on an EventSensor
NTF humidityESHighTrap1.3.6.1.4.1.3052.40.0.20120Sent to show humidity exceeded High Threshold on an EventSensor
NTF humidityESVeryHighTrap1.3.6.1.4.1.3052.40.0.20121Sent to show humidity exceeded Very High Threshold on an EventSensor
NTF humidityESLowTrap1.3.6.1.4.1.3052.40.0.20122Sent to show humidity went below Low Threshold on an EventSensor
NTF humidityESVeryLowTrap1.3.6.1.4.1.3052.40.0.20123Sent to show humidity went below Very Low Threshold on an EventSensor
NTF voltageESHighTrap1.3.6.1.4.1.3052.40.0.20130Sent to show voltage exceeded High Threshold on an EventSensor
NTF voltageESVeryHighTrap1.3.6.1.4.1.3052.40.0.20131Sent to show voltage exceeded Very High Threshold on an EventSensor
NTF voltageESLowTrap1.3.6.1.4.1.3052.40.0.20132Sent to show voltage went below Low Threshold on an EventSensor
NTF voltageESVeryLowTrap1.3.6.1.4.1.3052.40.0.20133Sent to show voltage went below Very Low Threshold on an EventSensor
NTF contact1NormalTrap1.3.6.1.4.1.3052.40.0.21001Sent to show Contact 1 is in the normal state
NTF contact2NormalTrap1.3.6.1.4.1.3052.40.0.21002Sent to show Contact 2 is in the normal state
NTF contact3NormalTrap1.3.6.1.4.1.3052.40.0.21003Sent to show Contact 3 is in the normal state
NTF contact4NormalTrap1.3.6.1.4.1.3052.40.0.21004Sent to show Contact 4 is in the normal state
NTF contact5NormalTrap1.3.6.1.4.1.3052.40.0.21005Sent to show Contact 5 is in the normal state
NTF contact6NormalTrap1.3.6.1.4.1.3052.40.0.21006Sent to show Contact 6 is in the normal state
NTF contact7NormalTrap1.3.6.1.4.1.3052.40.0.21007Sent to show Contact 7 is in the normal state
NTF contact8NormalTrap1.3.6.1.4.1.3052.40.0.21008Sent to show Contact 8 is in the normal state
NTF contact9NormalTrap1.3.6.1.4.1.3052.40.0.21009Send to show Contact 9 is in the normal state
NTF tempNormalTrap1.3.6.1.4.1.3052.40.0.21010Sent to show Temp went back to Normal range
NTF humidityNormalTrap1.3.6.1.4.1.3052.40.0.21020Sent to show Humidity went back to Normal range
NTF analog1NormalTrap1.3.6.1.4.1.3052.40.0.21030Sent to show analog1 went back to Normal range
NTF analog2NormalTrap1.3.6.1.4.1.3052.40.0.21040Sent to show analog2 went back to Normal range
NTF contactESNormalTrap1.3.6.1.4.1.3052.40.0.21101Send to show EventSensor contact has returned to normal state
NTF tempESNormalTrap1.3.6.1.4.1.3052.40.0.21110Sent to show EventSensor Temp went back to Normal range
NTF humidityESNormalTrap1.3.6.1.4.1.3052.40.0.21120Sent to show EventSensor Humidity went back to Normal range
NTF voltageESNormalTrap1.3.6.1.4.1.3052.40.0.21130Sent to show EventSensor voltage went back to Normal range
NTF testTrap1.3.6.1.4.1.3052.40.0.22000Sent for testing the SNMP interface
device1.3.6.1.4.1.3052.40.1
STR serialNumber1.3.6.1.4.1.3052.40.1.1DisplayStringread-only8-character serial number
STR firmwareVersion1.3.6.1.4.1.3052.40.1.2DisplayStringread-onlyFirmware version text string
STR siteID1.3.6.1.4.1.3052.40.1.3DisplayStringread-writeSite Identifier, up to 12 characters.
IP snmpManager1.3.6.1.4.1.3052.40.1.4IpAddressread-writeThis is snmp manager #1
INT input78Mode1.3.6.1.4.1.3052.40.1.5INTEGERread-onlyMode of operation of inputs 7/8. 0-analog 1&2 =default, 1-contacts 7&8
INT forceTraps1.3.6.1.4.1.3052.40.1.6INTEGERread-writeAny write non-zero forces set of traps to be send to the SNMP Manager
STR thisTrapText1.3.6.1.4.1.3052.40.1.7DisplayStringread-writeA text string included in all traps
STR alarmStatus1.3.6.1.4.1.3052.40.1.8DisplayStringread-onlyA text status of all alarms
IP snmpManager11.3.6.1.4.1.3052.40.1.9IpAddressread-writeSNMP manager #1
IP snmpManager21.3.6.1.4.1.3052.40.1.10IpAddressread-writeSNMP manager #2
IP snmpManager31.3.6.1.4.1.3052.40.1.11IpAddressread-writeSNMP manager #3
IP snmpManager41.3.6.1.4.1.3052.40.1.12IpAddressread-writeSNMP manager #4
INT statusRepeatHours1.3.6.1.4.1.3052.40.1.13INTEGERread-write0=none, 1-24 Number of Hours between Status Traps being Sent
INT serialTimeout1.3.6.1.4.1.3052.40.1.14INTEGERread-write5-30, Minutes of non-activity timeout on serial setup
INT powerupTrapsend1.3.6.1.4.1.3052.40.1.15INTEGERread-write0-no, 1-yes, send traps for all sensors on powerup
INT netlossTrapsend1.3.6.1.4.1.3052.40.1.16INTEGERread-write0-no, 1-yes, send traps for detected netloss and back up
STR buildID1.3.6.1.4.1.3052.40.1.17DisplayStringread-only5-chars max text for build identifier
contacts1.3.6.1.4.1.3052.40.2
contact11.3.6.1.4.1.3052.40.2.1
STR contact1Name1.3.6.1.4.1.3052.40.2.1.1DisplayStringread-writeName for contact, up to 30 characters
INT contact1State1.3.6.1.4.1.3052.40.2.1.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact1AlarmEnable1.3.6.1.4.1.3052.40.2.1.3INTEGERread-write0-alarms disabled 1-alarms enabled
INT contact1ActiveDirection1.3.6.1.4.1.3052.40.2.1.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact1Threshold1.3.6.1.4.1.3052.40.2.1.5INTEGERread-writeNumber of seconds that the contact must remain in a state before generating a trap, range 0-255
INT contact1ReturnNormalTrap1.3.6.1.4.1.3052.40.2.1.6INTEGERread-write0-return to normal traps not sent, 1-sent
INT contact1TrapRepeat1.3.6.1.4.1.3052.40.2.1.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps.
INT contact1Severity1.3.6.1.4.1.3052.40.2.1.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact21.3.6.1.4.1.3052.40.2.2
STR contact2Name1.3.6.1.4.1.3052.40.2.2.1DisplayStringread-writeName for contact, up to 30 characters
INT contact2State1.3.6.1.4.1.3052.40.2.2.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact2AlarmEnable1.3.6.1.4.1.3052.40.2.2.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact2ActiveDirection1.3.6.1.4.1.3052.40.2.2.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact2Threshold1.3.6.1.4.1.3052.40.2.2.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact2ReturnNormalTrap1.3.6.1.4.1.3052.40.2.2.6INTEGERread-write0-not sent, 1-sent
INT contact2TrapRepeat1.3.6.1.4.1.3052.40.2.2.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact2Severity1.3.6.1.4.1.3052.40.2.2.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact31.3.6.1.4.1.3052.40.2.3
STR contact3Name1.3.6.1.4.1.3052.40.2.3.1DisplayStringread-writeName for contact, up to 30 characters
INT contact3State1.3.6.1.4.1.3052.40.2.3.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact3AlarmEnable1.3.6.1.4.1.3052.40.2.3.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact3ActiveDirection1.3.6.1.4.1.3052.40.2.3.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact3Threshold1.3.6.1.4.1.3052.40.2.3.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact3ReturnNormalTrap1.3.6.1.4.1.3052.40.2.3.6INTEGERread-write0-not sent, 1-sent
INT contact3TrapRepeat1.3.6.1.4.1.3052.40.2.3.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact3Severity1.3.6.1.4.1.3052.40.2.3.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact41.3.6.1.4.1.3052.40.2.4
STR contact4Name1.3.6.1.4.1.3052.40.2.4.1DisplayStringread-writeName for contact, up to 30 characters
INT contact4State1.3.6.1.4.1.3052.40.2.4.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact4AlarmEnable1.3.6.1.4.1.3052.40.2.4.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact4ActiveDirection1.3.6.1.4.1.3052.40.2.4.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact4Threshold1.3.6.1.4.1.3052.40.2.4.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact4ReturnNormalTrap1.3.6.1.4.1.3052.40.2.4.6INTEGERread-write0-not sent, 1-sent
INT contact4TrapRepeat1.3.6.1.4.1.3052.40.2.4.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact4Severity1.3.6.1.4.1.3052.40.2.4.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact51.3.6.1.4.1.3052.40.2.5
STR contact5Name1.3.6.1.4.1.3052.40.2.5.1DisplayStringread-writeName for contact, up to 30 characters
INT contact5State1.3.6.1.4.1.3052.40.2.5.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact5AlarmEnable1.3.6.1.4.1.3052.40.2.5.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact5ActiveDirection1.3.6.1.4.1.3052.40.2.5.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact5Threshold1.3.6.1.4.1.3052.40.2.5.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact5ReturnNormalTrap1.3.6.1.4.1.3052.40.2.5.6INTEGERread-write0-not sent, 1-sent
INT contact5TrapRepeat1.3.6.1.4.1.3052.40.2.5.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact5Severity1.3.6.1.4.1.3052.40.2.5.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact61.3.6.1.4.1.3052.40.2.6
STR contact6Name1.3.6.1.4.1.3052.40.2.6.1DisplayStringread-writeName for contact, up to 30 characters
INT contact6State1.3.6.1.4.1.3052.40.2.6.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact6AlarmEnable1.3.6.1.4.1.3052.40.2.6.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact6ActiveDirection1.3.6.1.4.1.3052.40.2.6.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact6Threshold1.3.6.1.4.1.3052.40.2.6.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact6ReturnNormalTrap1.3.6.1.4.1.3052.40.2.6.6INTEGERread-write0-not sent, 1-sent
INT contact6TrapRepeat1.3.6.1.4.1.3052.40.2.6.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps.
INT contact6Severity1.3.6.1.4.1.3052.40.2.6.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact71.3.6.1.4.1.3052.40.2.7
STR contact7Name1.3.6.1.4.1.3052.40.2.7.1DisplayStringread-writeName for contact, up to 30 characters
INT contact7State1.3.6.1.4.1.3052.40.2.7.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact7AlarmEnable1.3.6.1.4.1.3052.40.2.7.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact7ActiveDirection1.3.6.1.4.1.3052.40.2.7.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact7Threshold1.3.6.1.4.1.3052.40.2.7.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact7ReturnNormalTrap1.3.6.1.4.1.3052.40.2.7.6INTEGERread-write0-not sent, 1-sent
INT contact7TrapRepeat1.3.6.1.4.1.3052.40.2.7.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact7Severity1.3.6.1.4.1.3052.40.2.7.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact81.3.6.1.4.1.3052.40.2.8
STR contact8Name1.3.6.1.4.1.3052.40.2.8.1DisplayStringread-writeName for contact, up to 30 characters
INT contact8State1.3.6.1.4.1.3052.40.2.8.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact8AlarmEnable1.3.6.1.4.1.3052.40.2.8.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact8ActiveDirection1.3.6.1.4.1.3052.40.2.8.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact8Threshold1.3.6.1.4.1.3052.40.2.8.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact8ReturnNormalTrap1.3.6.1.4.1.3052.40.2.8.6INTEGERread-write0-not sent, 1-sent
INT contact8TrapRepeat1.3.6.1.4.1.3052.40.2.8.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact8Severity1.3.6.1.4.1.3052.40.2.8.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
contact91.3.6.1.4.1.3052.40.2.9
STR contact9Name1.3.6.1.4.1.3052.40.2.9.1DisplayStringread-writeName for contact, up to 30 characters
INT contact9State1.3.6.1.4.1.3052.40.2.9.2INTEGERread-onlyCurrent State of Contact, 0-open 1-closed
INT contact9AlarmEnable1.3.6.1.4.1.3052.40.2.9.3INTEGERread-write0-no alarms 1-alarms enabled
INT contact9ActiveDirection1.3.6.1.4.1.3052.40.2.9.4INTEGERread-write0-alarm on open 1-alarm on closed
INT contact9Threshold1.3.6.1.4.1.3052.40.2.9.5INTEGERread-writeNumber of seconds must be in a state to be 'open' or 'closed'
INT contact9ReturnNormalTrap1.3.6.1.4.1.3052.40.2.9.6INTEGERread-write0-not sent, 1-sent
INT contact9TrapRepeat1.3.6.1.4.1.3052.40.2.9.7INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps
INT contact9Severity1.3.6.1.4.1.3052.40.2.9.8INTEGERread-write1-minor 2-major 3-critical 4-severe 5-warning
relays1.3.6.1.4.1.3052.40.3
relay11.3.6.1.4.1.3052.40.3.1
STR relay1Name1.3.6.1.4.1.3052.40.3.1.1DisplayStringread-writeName for relay, up to 30 characters
INT relay1CurrentState1.3.6.1.4.1.3052.40.3.1.2INTEGERread-write0-opened, 1-closed
INT relay1PowerupState1.3.6.1.4.1.3052.40.3.1.3INTEGERread-write0-opened, 1-closed
relay21.3.6.1.4.1.3052.40.3.2
STR relay2Name1.3.6.1.4.1.3052.40.3.2.1DisplayStringread-writeName for relay, up to 30 characters
INT relay2CurrentState1.3.6.1.4.1.3052.40.3.2.2INTEGERread-write0-opened, 1-closed
INT relay2PowerupState1.3.6.1.4.1.3052.40.3.2.3INTEGERread-write0-opened, 1-closed
tempsensor1.3.6.1.4.1.3052.40.4
INT tempValue1.3.6.1.4.1.3052.40.4.1INTEGERread-onlyCurrent Temperature Value, in C or F based on 1.3.6.1.4.1.3052.40.4.10
INT tempAlarmEnable1.3.6.1.4.1.3052.40.4.2INTEGERread-write0=alarms disabled, 1=alarms enabled
INT tempHighLevel1.3.6.1.4.1.3052.40.4.3INTEGERread-writeLevel at which the High alarm goes active
INT tempVeryHighLevel1.3.6.1.4.1.3052.40.4.4INTEGERread-writeLevel at which the Very High alarm goes active
INT tempLowLevel1.3.6.1.4.1.3052.40.4.5INTEGERread-writeLevel at which the Low alarm goes active
INT tempVeryLowLevel1.3.6.1.4.1.3052.40.4.6INTEGERread-writeLevel at which the Very Low alarm goes active
INT tempAlarmThreshold1.3.6.1.4.1.3052.40.4.7INTEGERread-writeSeconds must be in a range to be an alarm
INT tempReturnNormalTrap1.3.6.1.4.1.3052.40.4.8INTEGERread-write0-not sent, 1-send trap on return to normal range
INT tempTrapRepeat1.3.6.1.4.1.3052.40.4.9INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps.
INT tempMode1.3.6.1.4.1.3052.40.4.10INTEGERread-write0=all temp readings and levels in degrees F, 1=in degrees C
INT tempHighSeverity1.3.6.1.4.1.3052.40.4.11INTEGERread-writeHigh Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT tempVeryHighSeverity1.3.6.1.4.1.3052.40.4.12INTEGERread-writeVery High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT tempLowSeverity1.3.6.1.4.1.3052.40.4.13INTEGERread-writeLow Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT tempVeryLowSeverity1.3.6.1.4.1.3052.40.4.14INTEGERread-writeVery Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
STR tempName1.3.6.1.4.1.3052.40.4.15DisplayStringread-writeName for temperature sensor, up to 30 characters
humiditysensor1.3.6.1.4.1.3052.40.5
INT humidityValue1.3.6.1.4.1.3052.40.5.1INTEGERread-onlyCurrent Relative Humidity Value (0-100%)
INT humidityAlarmEnable1.3.6.1.4.1.3052.40.5.2INTEGERread-write0=alarms disabled, 1=alarms enabled
INT humidityHighLevel1.3.6.1.4.1.3052.40.5.3INTEGERread-writeLevel at which the High alarm goes active
INT humidityVeryHighLevel1.3.6.1.4.1.3052.40.5.4INTEGERread-writeLevel at which the Very High alarm goes active
INT humidityLowLevel1.3.6.1.4.1.3052.40.5.5INTEGERread-writeLevel at which the Low alarm goes active
INT humidityVeryLowLevel1.3.6.1.4.1.3052.40.5.6INTEGERread-writeLevel at which the Very Low alarm goes active
INT humidityAlarmThreshold1.3.6.1.4.1.3052.40.5.7INTEGERread-writeSeconds must be in a range to be an alarm
INT humidityReturnNormalTrap1.3.6.1.4.1.3052.40.5.8INTEGERread-write0-not sent, 1-send trap on return to normal range
INT humidityTrapRepeat1.3.6.1.4.1.3052.40.5.9INTEGERread-write0-no repeats. 1-255 number of minutes between repeats of alarm traps.
INT humidityHighSeverity1.3.6.1.4.1.3052.40.5.10INTEGERread-writeHigh Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT humidityVeryHighSeverity1.3.6.1.4.1.3052.40.5.11INTEGERread-writeVery High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT humidityLowSeverity1.3.6.1.4.1.3052.40.5.12INTEGERread-writeLow Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT humidityVeryLowSeverity1.3.6.1.4.1.3052.40.5.13INTEGERread-writeVery Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
STR humidityName1.3.6.1.4.1.3052.40.5.14DisplayStringread-writeName for humidity sensor, up to 30 characters
passthrough1.3.6.1.4.1.3052.40.6
INT ptNeedPassword1.3.6.1.4.1.3052.40.6.1INTEGERread-write0-no 1-yes, is password required for passthrough connection.
INT ptSayLoginText1.3.6.1.4.1.3052.40.6.2INTEGERread-write0-no 1-yes, is passthrough login text displayed on connection.
STR ptLoginText1.3.6.1.4.1.3052.40.6.3DisplayStringread-write0-24 char string which may be displayed on socket connection. Requires that ptSayLoginText be enabled to display this string.
INT ptSaySiteID1.3.6.1.4.1.3052.40.6.4INTEGERread-write0-no 1-yes, is SiteID displayed on pass through connection.
STR ptUsername1.3.6.1.4.1.3052.40.6.5DisplayStringread-write0-16 char string for Username used in serial passthrough connections
STR ptPassword1.3.6.1.4.1.3052.40.6.6DisplayStringread-write0-16 char string for Password used in serial passthrough connections
INT ptTimeout1.3.6.1.4.1.3052.40.6.7INTEGERread-writenumber of minutes (1-255) of idle activity (both directions) which causes disconnect. 0-never
INT ptEscChar1.3.6.1.4.1.3052.40.6.8INTEGERread-writeASCII character code (e.g, Escape=27) which if entered on the tcp port three times in a row causes disconnect. 0-none
INT ptLfstripToPort1.3.6.1.4.1.3052.40.6.9INTEGERread-write0-no 1-yes linefeed characters received on TCP connection are removed from stream to serial port
INT ptLfstripFromPort1.3.6.1.4.1.3052.40.6.10INTEGERread-write0-no 1-yes linefeed characters received on serial port are removed from stream to TCP connection
INT ptSerialBaudrate1.3.6.1.4.1.3052.40.6.11INTEGERread-write300 600 1200 2400 4800 9600 19200 baud are allowed values
INT ptSerialWordlength1.3.6.1.4.1.3052.40.6.12INTEGERread-write7 or 8 bit word selection
STR ptSerialParity1.3.6.1.4.1.3052.40.6.13DisplayStringread-writeN E O are allowed values for parity (none, even, odd) [a single-character string]
INT ptTCPPortnumber1.3.6.1.4.1.3052.40.6.14INTEGERread-writeIP port number for passthrough connection (range 1024-65534)
ftp1.3.6.1.4.1.3052.40.7
STR ftpUsername1.3.6.1.4.1.3052.40.7.1DisplayStringread-write0-16 char string for Username used in ftp server for updates
STR ftpPassword1.3.6.1.4.1.3052.40.7.2DisplayStringread-write0-16 char string for Password used in ftp server for updates
analog1.3.6.1.4.1.3052.40.8
analog11.3.6.1.4.1.3052.40.8.1
INT analog1Value1.3.6.1.4.1.3052.40.8.1.1INTEGERread-onlyValue of current analog reading, in 1/100 volt, +- 9999 range
INT analog1AlarmEnable1.3.6.1.4.1.3052.40.8.1.2INTEGERread-write0=no alarms, 1=send alarms
INT analog1HighLevel1.3.6.1.4.1.3052.40.8.1.3INTEGERread-writeLevel at which the High alarm goes active
INT analog1VeryHighLevel1.3.6.1.4.1.3052.40.8.1.4INTEGERread-writeLevel at which the Very High alarm goes active
INT analog1LowLevel1.3.6.1.4.1.3052.40.8.1.5INTEGERread-writeLevel at which the Low alarm goes active
INT analog1VeryLowLevel1.3.6.1.4.1.3052.40.8.1.6INTEGERread-writeLevel at which the Very Low alarm goes active
INT analog1AlarmThreshold1.3.6.1.4.1.3052.40.8.1.7INTEGERread-writeSeconds must be in a range to be an alarm
INT analog1ReturnNormalTrap1.3.6.1.4.1.3052.40.8.1.8INTEGERread-write0-not sent, 1-send trap on return to normal range
INT analog1TrapRepeat1.3.6.1.4.1.3052.40.8.1.9INTEGERread-write0-no repeats else number of minutes between repeats of trap
INT analog1HighSeverity1.3.6.1.4.1.3052.40.8.1.10INTEGERread-writeHigh Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT analog1VeryHighSeverity1.3.6.1.4.1.3052.40.8.1.11INTEGERread-writeVery High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT analog1LowSeverity1.3.6.1.4.1.3052.40.8.1.12INTEGERread-writeLow Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT analog1VeryLowSeverity1.3.6.1.4.1.3052.40.8.1.13INTEGERread-writeVery Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
STR analog1Name1.3.6.1.4.1.3052.40.8.1.14DisplayStringread-writeName for analog sensor 1, up to 30 characters
analog21.3.6.1.4.1.3052.40.8.2
INT analog2Value1.3.6.1.4.1.3052.40.8.2.1INTEGERread-onlyValue of current analog reading, in 1/100 volt, +- 9999 range
INT analog2AlarmEnable1.3.6.1.4.1.3052.40.8.2.2INTEGERread-write0=no alarms, 1=send alarms
INT analog2HighLevel1.3.6.1.4.1.3052.40.8.2.3INTEGERread-writeLevel at which the High alarm goes active
INT analog2VeryHighLevel1.3.6.1.4.1.3052.40.8.2.4INTEGERread-writeLevel at which the Very High alarm goes active
INT analog2LowLevel1.3.6.1.4.1.3052.40.8.2.5INTEGERread-writeLevel at which the Low alarm goes active
INT analog2VeryLowLevel1.3.6.1.4.1.3052.40.8.2.6INTEGERread-writeLevel at which the Very Low alarm goes active
INT analog2AlarmThreshold1.3.6.1.4.1.3052.40.8.2.7INTEGERread-writeSeconds must be in a range to be an alarm
INT analog2ReturnNormalTrap1.3.6.1.4.1.3052.40.8.2.8INTEGERread-write0-not sent, 1-send trap on return to normal range
INT analog2TrapRepeat1.3.6.1.4.1.3052.40.8.2.9INTEGERread-write0-no repeats else number of minutes between repeats of trap
INT analog2HighSeverity1.3.6.1.4.1.3052.40.8.2.10INTEGERread-writeHigh Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT analog2VeryHighSeverity1.3.6.1.4.1.3052.40.8.2.11INTEGERread-writeVery High Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT analog2LowSeverity1.3.6.1.4.1.3052.40.8.2.12INTEGERread-writeLow Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
INT analog2VeryLowSeverity1.3.6.1.4.1.3052.40.8.2.13INTEGERread-writeVery Low Level Severity 1-minor 2-major 3-critical 4-severe 5-warning
STR analog2Name1.3.6.1.4.1.3052.40.8.2.14DisplayStringread-writeName for analog sensor 2, up to 30 characters
eventSensorStatus1.3.6.1.4.1.3052.40.10
esPointTable1.3.6.1.4.1.3052.40.10.1not-accessibleThis table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, relay 5, etc.). The 4 point attributes are its name, whether it's in its event state, the point's value as a number and its value as a string. Points are referenced by a point index. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point).
esPointEntry1.3.6.1.4.1.3052.40.10.1.1not-accessibleEntry for EventSensor point table
INT esIndexES1.3.6.1.4.1.3052.40.10.1.1.1INTEGERread-onlyThe part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). This object's allowable values are 1 through 4, which refer to attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time. If there is an internal sensor in the unit, it will always be the first item in the Sensor Events setup menu. For example, if a new EventSensor is configured as the 2nd entry AFTER the internal EventSensor (if one exists) in the Sensor Events Setup Menu, then that EventSensor will be known from then on as EventSensor 2. All point indeces with esIndexES=2 will now refer to that particular EventSensor.
INT esIndexPC1.3.6.1.4.1.3052.40.10.1.1.2INTEGERread-onlyThe part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessary for getting a piece of data off an event sensor; namely, which EventSensor, point class, and which-sensor-of-that-class (a.k.a. point). The values for this object are: 1=temperature sensor 2=contact closure 3=humidity sensor 4=noise sensor 5=analog input 6=relay
INT esIndexPoint1.3.6.1.4.1.3052.40.10.1.1.3INTEGERread-onlyThe part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSensor) uniquely defines each point (sensor or relay) attached to a unit. For example, if esIndexES is 3, esIndexPC is 1 and esIndexPoint is 4 then this is the Fourth Temperature Sensor on EventSensor number 3.
STR esPointName1.3.6.1.4.1.3052.40.10.1.1.4DisplayStringread-writeThe name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the same point class on an EventSensor (e.g., 8 contact closures) and multiple sensor classes on an EventSensor (e.g., temperature, contact closure, humidity). If the point referenced by a given point index is solitary (e.g., temperature sensor, because there can be only one on an EventSensor), then this object reads as ''. Setting this object for solitary point indices sets the EventSensor name only. On the other hand, if a given point is among other points of the same point class on an EventSensor, then this object reads as ''. Setting this object for these NON- solitary point indices sets the sensor name only - not the EventSensor name.
INT esPointInEventState1.3.6.1.4.1.3052.40.10.1.1.5INTEGERread-writeA number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high For contact closures and relays the values of this object are: 1=point in event state 2=point in normal state For any point class and any point, if the event state is undefined, then the value of this object is 0. For any point class except relay, this object is read-only. For relays, setting this object to 1 puts the relay into its open state. Setting it to 2 puts the relay into its closed state.
INT esPointValueInt1.3.6.1.4.1.3052.40.10.1.1.6INTEGERread-writeA number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit). If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed). If the point class is humidity, then this object is the percent relative humidity. If the point class is analog input, then this object is the signed input value in tenths of the configured units. For any point class except relay, this object is read-only. For relays, setting this object to 1 closes the relay, while setting it to 0 opens it. This works regardless of the control mode of the relay.
STR esPointValueStr1.3.6.1.4.1.3052.40.10.1.1.7DisplayStringread-onlyA string referring to the value of a point on an EventSensor. For contact closures and relays this object is either 'Open' or 'Closed'. For temperature and humidity point classes, this object is the string representation of the esPointValueInt object. For temperature, 'C' or 'F' is including in the string to indicate scale. For analog inputs, this object is the string representation of the plus/minus input in volts.
eventSensorConfig1.3.6.1.4.1.3052.40.11
INT esNumberEventSensors1.3.6.1.4.1.3052.40.11.1INTEGERread-onlyThe number of EventSensors recognized by the s410 Range: 0-4
esTable1.3.6.1.4.1.3052.40.11.2not-accessibleThe table of what EventSensors are attached to the unit
esEntry1.3.6.1.4.1.3052.40.11.2.1not-accessibleTable entry for EventSensor table
INT esIndex1.3.6.1.4.1.3052.40.11.2.1.1INTEGERread-onlyThis number refers to an EventSensor; it has the same meaning as the esIndexES object (see above), except that this object is used only within the esTable branch. This object's allowable values are 1 through 4, which refer to additional attached EventSensors. The number corresponding to an EventSensor is determined by the user at the initial configuration time.
STR esID1.3.6.1.4.1.3052.40.11.2.1.2DisplayStringread-onlyThe factory-assigned ID of the EventSensor
INT esNumberTempSensors1.3.6.1.4.1.3052.40.11.2.1.3INTEGERread-onlyThe number of temperature sensors on the EventSensor
STR esTempReportingMode1.3.6.1.4.1.3052.40.11.2.1.4DisplayStringread-onlyDescription of how temperature values should be interpreted.
INT esNumberCCs1.3.6.1.4.1.3052.40.11.2.1.5INTEGERread-onlyThe number of contact closures on the EventSensor.
STR esCCReportingMode1.3.6.1.4.1.3052.40.11.2.1.6DisplayStringread-onlyDescription of how CC values should be interpreted.
INT esNumberHumidSensors1.3.6.1.4.1.3052.40.11.2.1.7INTEGERread-onlyThe number of humidity sensors on the EventSensor.
STR esHumidReportingMode1.3.6.1.4.1.3052.40.11.2.1.8DisplayStringread-onlyDescription of how humidity sensor values should be interpreted.
INT esNumberNoiseSensors1.3.6.1.4.1.3052.40.11.2.1.9INTEGERread-onlyThe number of noise sensors on the EventSensor.
STR esNoiseReportingMode1.3.6.1.4.1.3052.40.11.2.1.10DisplayStringread-onlyDescription of how noise sensor values should be interpreted.
INT esNumberAirflowSensors1.3.6.1.4.1.3052.40.11.2.1.11INTEGERread-onlyThe number of airflow sensors on the EventSensor.
STR esAirflowReportingMode1.3.6.1.4.1.3052.40.11.2.1.12DisplayStringread-onlyDescription of how airflow sensor values should be interpreted.
INT esNumberAnalog1.3.6.1.4.1.3052.40.11.2.1.13INTEGERread-onlyThe number of analog inputs on the EventSensor.
STR esAnalogReportingMode1.3.6.1.4.1.3052.40.11.2.1.14DisplayStringread-onlyDescription of how analog input values should be interpreted.
INT esNumberRelayOutputs1.3.6.1.4.1.3052.40.11.2.1.15INTEGERread-onlyThe number of relay outputs on the EventSensor
STR esRelayReportingMode1.3.6.1.4.1.3052.40.11.2.1.16DisplayStringread-onlyDescription of how relay output values should be interpreted.
techsupport1.3.6.1.4.1.3052.40.99
IP techsupportIPAddress1.3.6.1.4.1.3052.40.99.1IpAddressread-writeMay read or Set IP Address, takes effect on restart
IP techsupportNetMask1.3.6.1.4.1.3052.40.99.2IpAddressread-writeMay read or Set NetMask, takes effect on restart
IP techsupportRouter1.3.6.1.4.1.3052.40.99.3IpAddressread-writeMay read or Set Router IP Address, takes effect on restart
INT techsupportRestart1.3.6.1.4.1.3052.40.99.4INTEGERread-writeReads as 0, any Write resets unit so new IP, Netmask, Router may be used
STR techsupportSerialNumber1.3.6.1.4.1.3052.40.99.5DisplayStringread-writeRead/Set Serial Number, up to 8-char text string reported as 1.1
INT techsupportBoxTemp1.3.6.1.4.1.3052.40.99.6INTEGERread-onlyEstimate of inside-the-box temp in degrees C, for heater testing
INT techsupportHeaterState1.3.6.1.4.1.3052.40.99.7INTEGERread-only0-off 1-on (acutal heater pin on/off, heat may not be 100% duty cycle)
INT techsupportPSVolts1.3.6.1.4.1.3052.40.99.8INTEGERread-onlyestimate of power supply input voltage (only valid on 48V build)
mibend1.3.6.1.4.1.3052.40.100
INT mibendObject1.3.6.1.4.1.3052.40.100.1INTEGERread-onlyAn object after all active mib items, to help some managers compile

RFC description

Asentria S410 remote monitoring unit for temperature, humidity, and contact sensing.

Start monitoring S410 remote telemetry/alarm monitoring unit, remote site monitoring RTU (alarm/trap status) with a free 30-day trial of IPNetwork Monitor. Import MIBs, browse SNMP OIDs, create custom SNMP monitors, configure alerts, and monitor any SNMP-enabled network device from a single console.