PSNA-PS-psmA-MIB

MIB Reference — IPNetwork Monitor

All MIBsPSNA-PS-psmA-MIB

Category: System Management, UPS and Power

Description:

Manages power supply module A configuration, input voltage status, and fault notification for modular chassis systems.

Imported Objects

From RFC-1212

OBJECT-TYPE

From RFC-1215

TRAP-TYPE

From RFC1155-SMI

IpAddress
enterprises

What Is PSNA-PS-psmA-MIB?

PSNA-PS-psmA-MIB is a vendor enterprise MIB focused on power supply module A within a modular chassis system, placing it squarely in the hardware environmental-monitoring technology area. Though its sample content is sparse (only import statements retrieved), the module name and short description indicate it exposes power-supply-specific data: module presence/configuration, input voltage status, and fault condition. Its entire purpose is hardware status monitoring -- confirming whether power supply module A is present, receiving proper input voltage, and operating without fault, with notifications raised on failure conditions. Chassis power-supply MIBs of this kind typically rely on a companion entity/physical-inventory convention (similar to ENTITY-MIB) to identify the module's physical slot, though this cannot be confirmed from the available content. It is deployed in modular/chassis-based network or server equipment where redundant power supplies must be monitored for input power loss or failure. Engineers can download the PSNA-PS-psmA-MIB file directly to load it into their MIB browser.

IPNetwork Monitor allows you to monitor SNMP objects defined in PSNA-PS-psmA-MIB. Use the built-in SNMP Monitoring Browser to explore available variables, view their current values and descriptions, and select the objects you want to monitor. You can then create SNMP monitors, configure thresholds, and receive alerts when monitored values change.

What Can Be Monitored

  • power supply module presence
  • input voltage status
  • power supply fault condition

Supported Devices

  • modular chassis network/server equipment with redundant power supplies

Monitoring Examples

An operator would poll the power-supply-A status object to confirm presence and normal input voltage, and would watch for a fault notification if psmA loses input power or reports an internal failure. Comparing status across redundant power modules (A and B, if present) would reveal whether the chassis is running on a single remaining supply after a failure. A transition from a normal to a fault or absent state would typically be treated as a critical hardware alert requiring immediate attention.

OIDs
OID symbolicOID numericTypeAccessDescription
emersonNetworkPower1.3.6.1.4.1.13400
products1.3.6.1.4.1.13400.2
psm1.3.6.1.4.1.13400.2.8
NTF psOnNormal1.3.6.1.4.1.13400.2.8.0.1INFORMATION: The Power System is on normal status.
NTF communicationLost1.3.6.1.4.1.13400.2.8.0.2SEVERE: Communication with the Power System lost.
NTF communicationResumed1.3.6.1.4.1.13400.2.8.0.3INFORMATION: Communication with the Power System Resumed.
NTF acFail1.3.6.1.4.1.13400.2.8.0.4SEVERE: AC Power failed.
NTF acResumed1.3.6.1.4.1.13400.2.8.0.5INFORMATION: AC power Resumed.
NTF acVoltageoutofRange1.3.6.1.4.1.13400.2.8.0.6SEVERE: AC voltage is out of normal range.
NTF acVoltageNormal1.3.6.1.4.1.13400.2.8.0.7INFORMATION: AC voltage is normal.
NTF dcVoltageoutofRange1.3.6.1.4.1.13400.2.8.0.8SEVERE: DC voltage is out of normal range.
NTF dcVoltageNormal1.3.6.1.4.1.13400.2.8.0.9INFORMATION: DC voltage is normal.
NTF llvd1.3.6.1.4.1.13400.2.8.0.10SEVERE: Load low voltage disconnected.
NTF llvdResumed1.3.6.1.4.1.13400.2.8.0.11INFORMATION: Load low voltage disconnection resumed.
NTF blvd1.3.6.1.4.1.13400.2.8.0.12SEVERE: Battery low voltage disconnected.
NTF blvdResumed1.3.6.1.4.1.13400.2.8.0.13INFORMATION: Battery low voltage disconnection resumed.
NTF highTemperature1.3.6.1.4.1.13400.2.8.0.14SEVERE: The temperature around battery is too high.
NTF highTemperatureResumed1.3.6.1.4.1.13400.2.8.0.15INFORMATION: The temperature around battery is normal.
NTF dcRouteDisconnect1.3.6.1.4.1.13400.2.8.0.16SEVERE: Some DC route(s) disconnected.
NTF dcRouteDisconnectResumed1.3.6.1.4.1.13400.2.8.0.17INFORMATION: DC route(s) disconnection resumed.
NTF batteryRouteDisconnect1.3.6.1.4.1.13400.2.8.0.18SEVERE: The battery route(s) disconnected.
NTF batteryRouteDisconnectResumed1.3.6.1.4.1.13400.2.8.0.19INFORMATION: The battery route(s) disconnection resumed.
NTF acSPDfault1.3.6.1.4.1.13400.2.8.0.20SEVERE: AC SPD fault.
NTF acSPDfaultResumed1.3.6.1.4.1.13400.2.8.0.21INFORMATION: AC SPD fault resumed.
NTF acCircuitBreakerfault1.3.6.1.4.1.13400.2.8.0.22SEVERE: AC circuit breaker fault.
NTF acCircuitBreakerfaultResumed1.3.6.1.4.1.13400.2.8.0.23INFORMATION: AC circuit breaker fault resumed.
NTF batteryCurrentOver1.3.6.1.4.1.13400.2.8.0.24SEVERE: Battery current is over limit.
NTF batteryCurrentOverResumed1.3.6.1.4.1.13400.2.8.0.25INFORMATION: Battery current over resumed.
NTF rectifierFault1.3.6.1.4.1.13400.2.8.0.26SEVERE: Some Rectifier(s) fault.
NTF rectifierFaultResumed1.3.6.1.4.1.13400.2.8.0.27INFORMATION: Rectifier(s) fault resumed.
NTF rectifierProtection1.3.6.1.4.1.13400.2.8.0.28SEVERE: Some Rectifier(s) protection.
NTF rectifierProtectionResumed1.3.6.1.4.1.13400.2.8.0.29INFORMATION: Rectifier(s) protection resumed.
NTF rectifierFanFault1.3.6.1.4.1.13400.2.8.0.30SEVERE: Some Rectifier(s) fan fault.
NTF rectifierFanFaultResumed1.3.6.1.4.1.13400.2.8.0.31INFORMATION: Rectifier(s) fan fault resumed.
NTF rectifierOverTemperature1.3.6.1.4.1.13400.2.8.0.32SEVERE: Some Rectifier(s) over temperature.
NTF rectifierOverTemperatureResumed1.3.6.1.4.1.13400.2.8.0.33INFORMATION: Rectifier(s) over temperature resumed.
NTF communicationACDLost1.3.6.1.4.1.13400.2.8.0.34SEVERE: Power System communication with ACD lost.
NTF communicationACDResumed1.3.6.1.4.1.13400.2.8.0.35INFORMATION: Power System communication with ACD resumed.
NTF communicationDCDLost1.3.6.1.4.1.13400.2.8.0.36SEVERE: Power System communication with DCD lost.
NTF communicationDCDResumed1.3.6.1.4.1.13400.2.8.0.37INFORMATION: Power System communication with DCD resumed.
NTF communicationRectifierLost1.3.6.1.4.1.13400.2.8.0.38SEVERE: Power System communication with rectifier lost.
NTF communicationRectifierResumed1.3.6.1.4.1.13400.2.8.0.39INFORMATION: Power System communication with rectifier resumed.
NTF dcdcFault1.3.6.1.4.1.13400.2.8.0.40SEVERE: DC/DC convertor fault.
NTF dcdcFaultResumed1.3.6.1.4.1.13400.2.8.0.41INFORMATION: DC/DC convertor fault resumed.
psAgent1.3.6.1.4.1.13400.2.8.1
INT agentRevision1.3.6.1.4.1.13400.2.8.1.1INTEGERread-onlyThe firmware revision of the agent.
INT agentManagersNum1.3.6.1.4.1.13400.2.8.1.2INTEGERread-onlyThe number of managers that can manage the agent.
agentManagersTable1.3.6.1.4.1.13400.2.8.1.3not-accessibleA list of managers of the agent. The number of entries is given by the value of agentManagersNum.
agentManagersEntry1.3.6.1.4.1.13400.2.8.1.3.1not-accessibleThe managers of the agent.
INT managerIndex1.3.6.1.4.1.13400.2.8.1.3.1.1INTEGERread-onlyThe index of the managers entry.
IP managerAddr1.3.6.1.4.1.13400.2.8.1.3.1.2IpAddressread-writeThe IP address of the manager.
STR publicCommunityString1.3.6.1.4.1.13400.2.8.1.3.1.3DisplayStringread-writeThe public community name to use in the query request.
STR privateCommunityString1.3.6.1.4.1.13400.2.8.1.3.1.4DisplayStringread-writeThe private community name to use in the control request.
INT managerPrivilege1.3.6.1.4.1.13400.2.8.1.3.1.5INTEGERread-writeThe privilege of the manager to access the agent. setting forbidden(0) indicates the manager have no any privilege to access the agent, setting query(1) indicates the manager can GET information from agent only, setting control(2) indicates the manager can GET information from agent and send control command to the agent. setting administrator(3) indicates the manager has all management privilege including set or modify this managers table.
INT acceptTrapLevel1.3.6.1.4.1.13400.2.8.1.3.1.6INTEGERread-writeThe severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager. setting noTraps(4) indicates agent do not send any traps to the manager.
INT managerAccept1.3.6.1.4.1.13400.2.8.1.3.1.7INTEGERread-writeAn entry will be added if new(1), will be modified if modify(2), and will be removed if delete(3).
psCommon1.3.6.1.4.1.13400.2.8.2
psIdent1.3.6.1.4.1.13400.2.8.2.1
STR psIdentControllerModel1.3.6.1.4.1.13400.2.8.2.1.1DisplayStringread-onlyThe controller model of the Power System.
STR psIdentFirmwareRevision1.3.6.1.4.1.13400.2.8.2.1.2DisplayStringread-onlyThe firmware revision of the controller of the Power System.
STR psIdentFactory1.3.6.1.4.1.13400.2.8.2.1.3DisplayStringread-onlyThe name of the Power System manufacturer.
psSpecial1.3.6.1.4.1.13400.2.8.3
psm_a1.3.6.1.4.1.13400.2.8.3.1
psBattery1.3.6.1.4.1.13400.2.8.3.1.2
INT psBatteryVoltage1.3.6.1.4.1.13400.2.8.3.1.2.1INTEGERread-onlyThe voltage of battery in 0.1 VDC.
INT psBatteryCurrent1.3.6.1.4.1.13400.2.8.3.1.2.2INTEGERread-onlyThe total current of the batteries in 0.1 ADC.
INT psBatteryTemperature1.3.6.1.4.1.13400.2.8.3.1.2.3INTEGERread-onlyThe temperature around the battery in 0.1 Celsius degree.
psInput1.3.6.1.4.1.13400.2.8.3.1.3
INT psInputLineAVoltage1.3.6.1.4.1.13400.2.8.3.1.3.1INTEGERread-onlyThe AC line A voltage in 0.1 VAC.
INT psInputLineBVoltage1.3.6.1.4.1.13400.2.8.3.1.3.2INTEGERread-onlyThe AC line B voltage in 0.1 VAC.
INT psInputLineCVoltage1.3.6.1.4.1.13400.2.8.3.1.3.3INTEGERread-onlyThe AC line C voltage in 0.1 VAC.
psOutput1.3.6.1.4.1.13400.2.8.3.1.4
INT psOutputVoltage1.3.6.1.4.1.13400.2.8.3.1.4.1INTEGERread-onlyThe DC voltage of the Power System in 0.1 VDC.
INT psOutputCurrent1.3.6.1.4.1.13400.2.8.3.1.4.2INTEGERread-onlyThe DC current of the Power System in 0.1 ADC.
psStatus1.3.6.1.4.1.13400.2.8.3.1.5
INT psStatusAlarm1.3.6.1.4.1.13400.2.8.3.1.5.1INTEGERread-onlyThe alarm status of the Power System.
INT psStatusCommunication1.3.6.1.4.1.13400.2.8.3.1.5.2INTEGERread-onlyThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
INT psStatusControlMode1.3.6.1.4.1.13400.2.8.3.1.5.3INTEGERread-onlyThe AUTO/MANUAL control mode of the Power System.
INT psStatusChargingMode1.3.6.1.4.1.13400.2.8.3.1.5.4INTEGERread-onlyThe status of battery charging, floatCharging(2), equalizeCharging(3), testing(4).
psTest1.3.6.1.4.1.13400.2.8.3.1.6
psControl1.3.6.1.4.1.13400.2.8.3.1.7
psConfig1.3.6.1.4.1.13400.2.8.3.1.8
psm_a91.3.6.1.4.1.13400.2.8.3.2
psAlarm1.3.6.1.4.1.13400.2.8.4
INT psAlarmPresentNum1.3.6.1.4.1.13400.2.8.4.1INTEGERread-onlyThe present number of active alarams.
psAlarmPresentTable1.3.6.1.4.1.13400.2.8.4.2not-accessibleA list of current alarms, The number of entries is given by the value of psAlarmPresentNum.
psAlarmPresentEntry1.3.6.1.4.1.13400.2.8.4.2.1not-accessibleThe present alarms list.
INT presentAlarmIndex1.3.6.1.4.1.13400.2.8.4.2.1.1INTEGERread-onlyThe index of the present alaram entry.
STR presentAlarmTime1.3.6.1.4.1.13400.2.8.4.2.1.2DisplayStringread-onlyThe time of the alarm generated, format as mm/dd/yyyy hh:mm:ss
INT presentAlarmId1.3.6.1.4.1.13400.2.8.4.2.1.3INTEGERread-onlyThe alarm ID.
STR presentAlarmName1.3.6.1.4.1.13400.2.8.4.2.1.4DisplayStringread-onlyThe name of the alarm.
INT presentAlaramLevel1.3.6.1.4.1.13400.2.8.4.2.1.5INTEGERread-onlyThe alarm level.
STR trapArgsString1.3.6.1.4.1.13400.2.8.4.2008DisplayStringread-onlyThis OID allows Power System traps to be sent with an octet string argument that may not be defined in the PSNA_PS_MIB. A get of this OID will return a NULL string.

RFC description

Power supply unit monitoring including battery, input/output and status on Emerson systems.