Access: read-write
Description: Setting this object will start the output after the indicated number of ticks (1 tick = 10 seconds), including starting the UPS, if necessary. Setting this object to 0 will cause the startup to occur immediately. Setting this object to -1 will disable autorestart.
What is lcUpsConfigAutoRestart?
This read-write value sets how many 10-second ticks the UPS waits before automatically restarting its output once conditions allow, starting the UPS itself if necessary; 0 means restart immediately, and -1 disables auto-restart entirely. Admins set this to -1 in environments where an unattended automatic power-up after an outage would be unsafe, requiring manual intervention instead.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.14.7 snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-GXT-UPS-MIB::lcUpsConfigAutoRestart
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.1.14.7.1 snmpget -v2c -c public <target> LIEBERT-UPSTATION-GXT-UPS-MIB::lcUpsConfigAutoRestart.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.1.1.1.14.7.1 i <value>
Start monitoring Liebert UPStation GXT uninterruptible power supply with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-GXT-UPS-MIB::lcUpsConfigAutoRestart OID value, configure state conditions and alerts, and monitor any Liebert UPStation GXT uninterruptible power supply from a single console.
OID Breakdown
Upper-level ancestors (12 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.1 | liebertUps | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1 | luExtensions | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1 | luCore | LIEBERT-MICRO-UPS-MIB |
| 1.3.6.1.4.1.476.1.1.1.1.14 | lcUpsConfig | LIEBERT-UPS-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.1.1.1.14.7 | lcUpsConfigAutoRestart | LIEBERT-UPSTATION-GXT-UPS-MIB |