GESINGLEUPS-MIB :: upsTestResultsSummarygen

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › GESINGLEUPS-MIB › upsTestResultsSummarygen

upsTestResultsSummarygen

Module: GESINGLEUPS-MIB

OID (symbolic): GESINGLEUPS-MIB::upsTestResultsSummarygen

OID (numeric): 1.3.6.1.4.1.818.1.1.10.7.3

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.(*)

What is upsTestResultsSummarygen?

Summarizes the outcome of the current or most recent diagnostic test: passed, passed with warning, failed with error, aborted, still in progress, or no tests ever run. Management software polls this after starting a test (via upsTestIdgen) to know when it has finished and whether it succeeded.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.7.3
snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsTestResultsSummarygen

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.7.3.1
snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsTestResultsSummarygen.1

Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsTestResultsSummarygen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.818imvGE-PARALLELUPS
1.3.6.1.4.1.818.1geHardwareGE-PARALLELUPS
1.3.6.1.4.1.818.1.1geUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10geGenericUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10.7upsTest_genGE-PARALLELUPS
Numeric OIDNameModule
1.3.6.1.4.1.818.1.1.10.7.3upsTestResultsSummarygenGESINGLEUPS-MIB