Module: GESINGLEUPS-MIB
OID (symbolic): GESINGLEUPS-MIB::upsRebootWithDurationgen
OID (numeric): 1.3.6.1.4.1.818.1.1.10.8.4
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootWithDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall not occur until the utility power is restored.(*)
What is upsRebootWithDurationgen?
Setting this object immediately shuts the UPS output or system down for the specified number of seconds and then automatically restarts it, essentially scripting a timed power-cycle of the load. Reading it shows the seconds remaining in the cycle, or -1 if none is underway; if input power is still absent when the restart is due, the startup is held off until it returns.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.8.4 snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsRebootWithDurationgen
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.8.4.1 snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsRebootWithDurationgen.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.818.1.1.10.8.4.1 i <value>
Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsRebootWithDurationgen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.818 | imv | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1 | geHardware | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1 | geUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10 | geGenericUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10.8 | upsControl_gen | GE-PARALLELUPS |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.818.1.1.10.8.4 | upsRebootWithDurationgen | GESINGLEUPS-MIB |