Description: The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the system has opened the output breaker.(*)
What is upsOutputSourcegen?
Indicates what is currently supplying the UPS output: other, none, normal (inverter), bypass, battery, booster, or reducer. A value of battery confirms the load is currently riding on stored energy, while bypass or booster/reducer indicate the UPS is using a raw or boosted/trimmed mains path instead of full double conversion.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.4.1 snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsOutputSourcegen
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.4.1.1 snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsOutputSourcegen.1
Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsOutputSourcegen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.818 | imv | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1 | geHardware | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1 | geUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10 | geGenericUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10.4 | upsOutput_gen | GE-PARALLELUPS |