GESINGLEUPS-MIB :: upsConfigAudibleStatusgen

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › GESINGLEUPS-MIB › upsConfigAudibleStatusgen

upsConfigAudibleStatusgen

Module: GESINGLEUPS-MIB

OID (symbolic): GESINGLEUPS-MIB::upsConfigAudibleStatusgen

OID (numeric): 1.3.6.1.4.1.818.1.1.10.9.8

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this object to muted(3) when the audible alarm is sounding shall temporarily silence the alarm. It will remain muted until it would normally stop sounding and the value returned for read operations during this period shall equal muted(3). At the end of this period, the value shall revert to enabled(2). Writes of the value muted(3) when the audible alarm is not sounding shall be accepted but otherwise shall have no effect.(*)

What is upsConfigAudibleStatusgen?

Controls the UPS's audible alarm: disabled silences it permanently, enabled lets it sound normally, and muted temporarily silences an alarm that is currently sounding until it would have stopped on its own, after which it reverts to enabled. Setting 'muted' while no alarm is sounding is accepted but has no immediate effect.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.9.8
snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsConfigAudibleStatusgen

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.9.8.1
snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsConfigAudibleStatusgen.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.818.1.1.10.9.8.1 i <value>

Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsConfigAudibleStatusgen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.818imvGE-PARALLELUPS
1.3.6.1.4.1.818.1geHardwareGE-PARALLELUPS
1.3.6.1.4.1.818.1.1geUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10geGenericUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10.9upsConfig_genGE-PARALLELUPS
Numeric OIDNameModule
1.3.6.1.4.1.818.1.1.10.9.8upsConfigAudibleStatusgenGESINGLEUPS-MIB